Alarm Control process ......................19 TURN ON process at HEAT..................19 Protection function......................20 10 Paramter Tables......................22 Compressor Settings....................22 Condenser Settings......................22 Evaporator Settings......................22 Special Functions......................23 User Settings........................24 User Interface.......................24 Alarm Settings......................24 3/28 Siemens Building Technologies SIEMENS Controller HEAT PUMP controller HVAC Products 27.11.2006...
RWR470.10 in building services plant. Type of document Ordering no. Datasheet CB1Q3901en Key Features Its main features are as follows: • Non-programmable stand-alone controller, or networked via the communication of PCLBUS 1/28 Siemens Building Technologies SIEMENS Controller HEAT PUMP controller HVAC Products 27.11.2006...
Siemens Building Technologies. Operation RWR470.10 controller may only be operated by staffs who have been instructed by Siemens Building Technologies or their delegates and whose attention has been drawn to potential risks. Wiring...
Page 7
As for how to access the Query/Warning/Alarm/Parameter menus above, see also <Chapter 4.2 Accessing the Menus> Notes Parameters listed under the menu vary with the password privileged user. 3/28 Siemens Building Technologies SIEMENS Controller HEAT PUMP controller HVAC Products 27.11.2006...
Page 8
Indoor pump Blinking: alarms detected Outdoor pump Notes For any warning/alarm detected, the corresponding device icon and the icon will blink continuously until the alarm is acknowledged or reset 4/28 Siemens Building Technologies SIEMENS Controller HEAT PUMP controller HVAC Products 27.11.2006...
• No password is required • Adjust limited values of parameters User (by default , can only adjust values of parameters in the “ST” group) 5/28 Siemens Building Technologies SIEMENS Controller HEAT PUMP controller HVAC Products 27.11.2006...
B- connector for RS485 Air condition switch Optional for RS485 communication Service interface for parameters Hot water switch RJ45 uploading and downloading Common reference point for digital input 6/28 Siemens Building Technologies SIEMENS Controller HEAT PUMP controller HVAC Products 27.11.2006...
Before wiring with passive sensor, pay attention to the following: • Terminals X1…X6 can be wired with NTC 10K sensor. G G0 PE QAZ36.526/109, NTC 10 kΩ temperature sensor 7/28 Siemens Building Technologies SIEMENS Controller HEAT PUMP controller HVAC Products 27.11.2006...
Wiring with Digital Outputs The following is a wiring example with relay output. Q13 Q14 Q24 Q34 Q44 Q54 Q64 Fuse E-heater E-heater with 220/230 VAC supply voltage 8/28 Siemens Building Technologies SIEMENS Controller HEAT PUMP controller HVAC Products 27.11.2006...
For end users, select “NO,” and press <Enter > to proceed. − For service men and factory users, select “EU” or”ID”and press <Enter> to input − the password. 9/28 Siemens Building Technologies SIEMENS Controller HEAT PUMP controller HVAC Products 27.11.2006...
Outlet water temperature of indoor side Atmospheric temperature of outdoor Hot water temperature Outlet water temperature of outdoor side Inlet water temperature of outdoor side or evaporating temperature 10/28 Siemens Building Technologies SIEMENS Controller HEAT PUMP controller HVAC Products 27.11.2006...
Band of hotwater temperature in the life ºC Minimum setpoint in cooling ST11 ST12 ºC setpoint in cooling ST12 Maximum ST11 ºC ST17 Band of adjusting time 1000 11/28 Siemens Building Technologies SIEMENS Controller HEAT PUMP controller HVAC Products 27.11.2006...
• For service men and factory users, select “EU” or “ID”and press <Enter>. Input the 4-digit password when the following screen is displayed Press <Enter> to confirm and continue to input the password. 12/28 Siemens Building Technologies SIEMENS Controller HEAT PUMP controller HVAC Products 27.11.2006...
Press <Plus> or <Minus> to increase or blinking decrease the value, and press <Enter> to confirm. Notes Continuously press <Esc> to exit out of the current level and back to the desired menu level. 13/28 Siemens Building Technologies SIEMENS Controller HEAT PUMP controller HVAC Products 27.11.2006...
If no warning is generated, the word “NoNE” will be displayed. Continuously press <Exit> to exit out of the current level, and back to the normal running mode. 14/28 Siemens Building Technologies SIEMENS Controller HEAT PUMP controller HVAC Products 27.11.2006...
Alarm number of compressor low pressure within 24 hours is over the limit(AL06) AL19 Alarm number of compressor high pressure within 24 hours is over the limit(AL07) AL20 Low evaporator temperature protection(AL08) 15/28 Siemens Building Technologies SIEMENS Controller HEAT PUMP controller HVAC Products 27.11.2006...
• Press <Enter> to acknowledge the alarm. • If the alarm status is cleared, the corresponding device icon and alarm icon that are flashing will accordingly disappear. • Restart the system, as appropriate. 16/28 Siemens Building Technologies SIEMENS Controller HEAT PUMP controller HVAC Products 27.11.2006...
• When the actual supply/return temperature is higher than the heating setpoint (ST02) + temperature band (ST04), the compressor capacity will be gradually decreased by stages every a preset time (ST17). 17/28 Siemens Building Technologies SIEMENS Controller HEAT PUMP controller HVAC Products...
When operate TURN OFF at heat mode, the controller will work as the following process: 9.6.2.1 CM01 meeted, turn off one compressor; 9.6.2.2 With CM04 delay, CM01 meeted, turn off the other compressor if has; 18/28 Siemens Building Technologies SIEMENS Controller HEAT PUMP controller HVAC Products 27.11.2006...
A continuous blink code AL01 will appear on the LCD, until DI2=ON, the unit will turn to its normal work. 19/28 Siemens Building Technologies SIEMENS Controller HEAT PUMP controller HVAC Products...
Page 24
During normal working, if ET≤AL08, all the compressors will be stopped, other parts will keep its original state, a continuous blink warning code AL20 will appear on the LCD. 20/28 Siemens Building Technologies SIEMENS Controller HEAT PUMP controller HVAC Products...
The water pump with the compressor ON/ OFF but ON/ OFF EV02 Indoor reference sensor: - - 0=RT (return temperature sensor) 1=ST (supply temperature sensor) EV03 indoor pump Off delay (compressor OFF) CN02 1000 21/28 Siemens Building Technologies SIEMENS Controller HEAT PUMP controller HVAC Products 27.11.2006...
SF09 temperature point of inlet/outlet water for antifreeze turned off SF10 The compatibility between the Indoor water pump and hot water pump 22/28 Siemens Building Technologies SIEMENS Controller HEAT PUMP controller HVAC Products 27.11.2006...
AL01 Protecting Setpoint for low outlet water temperature ºC AL02 Band of low outlet water temperature ºC AL03 Protecting Setpoint for high outlet water temperature ºC 23/28 Siemens Building Technologies Titel des Dokumentes CE1P0000de HVAC Products dd.mm.jjjj...