CIPer Model 30 Controller
Table 1
Parts and description
Model number
WEB-C3036EPUBNH Honeywell CIPer - IP controller with 3 universal inputs, 6 Binary Outputs, 3 Universal I/O and
WEB-C3036EPVBNH Honeywell CIPer - IP controller with 3 universal inputs, 6 Binary Outputs, 3 Universal I/O, VAV
WEB-O3022H
WEB-O9056H
Specifications:
Power consumption: AC: Max 100VA
Rated input voltage: 20-30 VAC; 50/60Hz
Impulse voltage: 330V
Ambient temperature: -4 to 131F (-20 to 55C)
Storage temperature: -4 to 150F (-20 to 65C)
Humidity: 5% to 95% non-condensing
Differential pressure sensor range (VAV model): 0-2"
WC (0 to 374 Pa) 32 to 122F (0 to 55C)
Universal Inputs / Analog Outputs (configurable): 6
UI / 3 configurable as AO
Flexible UI's to connect external sensors like
20KNTC, PT1000 and other resistive sensors
Digital Output type / rating: Solid-State Relay, 1.5A
Continuous, 3.5A inrush for 100 mS.
Digital Output voltage rating: 20 to 30 VAC @ 50/60
Hz
Pulse Inputs: 100Hz max, minimum duty cycle: 5 mS
ON / 5 mS OFF.
Purpose of Control: Operating Control, Open Energy
Management Equipment
Action: Type 1
Pollution degree: 2
ELV limits realized: 24V
© Honeywell
Description
HOA switches
airflow sensor and HOA switches
IO module with 3 universal inputs, 2 Binary Outputs, 2 Universal I/O and HOA switches
IO module with 9 universal inputs, 6 Binary Outputs, 5 Universal I/O and HOA switches
INSTALLATION INSTRUCTIONS
Introduction
The Honeywell CIPer Model 30 is a compact, Internet
Protocol (IP) edge controller for VAV, Unitary and Plant
applications. With its native Niagara N4 on-board
programming platform; the CIPer controller provides
Internet connectivity, Web serving capability, integrated
control, data logging, alarming, trending, and scheduling
management. The controller can be used to aggregate
information (including real-time data, alarms, trends,
and history) and integrate this data to the Sentience
Cloud for value-added data analytics.
Before Installation
WARNING! Install all equipment in accordance with the
National Electric Code and in a manner acceptable to the local
authority having jurisdiction. Read these instructions and the
CIPer Model 30 controller Installation Instructions (31-00183-
01) carefully before installing equipment. Failure to follow all
instructions may result in equipment damage or a hazardous
condition.
Attention! Installez tout le matériel en conformité avec le
Code national de l'électricité et d'une manière acceptable pour
l'autorité localecompétente. Lisez ces instructions et le guide d'
installation et fonctionnement de l'ACM (LT-ACMIOG) avant
l'installation du matériel. Le non respect des instructions peut
entraîner desdes dommages matériels ou une situation
dangereuse.
WARNING! The CIPer 30 controller and its components may
be
susceptible
to
appropriate ESD grounding techniques while handling the
product. When possible, always handle the product by its non-
electrical components.