Bosch Rexroth IndraControl VDP 16.1 Project Planning Manual

Bosch Rexroth IndraControl VDP 16.1 Project Planning Manual

Operator display
Hide thumbs Also See for Rexroth IndraControl VDP 16.1:
Table of Contents

Advertisement

Quick Links

Electric Drives
and Controls
Hydraulics
Rexroth IndraControl
VDP 16.1/40.1/60.1
Operator Display
Project Planning Manual
Linear Motion and
Assembly Technologies
Pneumatics
Service
R911307654
Edition 03

Advertisement

Table of Contents
loading

Summary of Contents for Bosch Rexroth IndraControl VDP 16.1

  • Page 1 Electric Drives Linear Motion and and Controls Hydraulics Assembly Technologies Pneumatics Service Rexroth IndraControl R911307654 Edition 03 VDP 16.1/40.1/60.1 Operator Display Project Planning Manual...
  • Page 2 Bosch Rexroth AG DOK-SUPPL*-VDP16/40/60-PR03-EN-P Rexroth IndraControl VDP 16.1/40.1/60.1 Operator Display Title Rexroth IndraControl VDP 16.1/40.1/60.1 Operator Display Type of Documentation Project Planning Manual Document Typecode DOK-SUPPL*-VDP16/40/60-PR03-EN-P Internal File Reference RS-3819577ef0bf23a20a6846a0007da7dd-1-en-US-5 Purpose of Documentation This documentation describes the displays IndraControl VDP 16.1, VDP 40.1 and VDP 60.1 as well as the Y-repeaters available as accessories.
  • Page 3: Table Of Contents

    DOK-SUPPL*-VDP16/40/60-PR03-EN-P Bosch Rexroth AG I/69 Rexroth IndraControl VDP 16.1/40.1/60.1 Operator Display Table of Contents Table of Contents Page System Presentation...................... 5 Brief Description of the VDP 16.1, VDP 40.1 and VDP 60.1 Operator Displays ........5 Variants..............................5 1.2.1 Characteristic Features........................5 1.2.2...
  • Page 4 II/69 Bosch Rexroth AG DOK-SUPPL*-VDP16/40/60-PR03-EN-P Rexroth IndraControl VDP 16.1/40.1/60.1 Operator Display Table of Contents Page Declaration of Conformity ......................25 Note for the Machine Manufacturer....................25 4.4.3 UL/CSA Certified..........................25 Wear Parts............................26 Compatibility Test..........................26 Dimensions and Installation..................27 Housing Dimensions..........................
  • Page 5 DOK-SUPPL*-VDP16/40/60-PR03-EN-P Bosch Rexroth AG III/69 Rexroth IndraControl VDP 16.1/40.1/60.1 Operator Display Table of Contents Page 7.1.6 XUSB Interfaces..........................47 7.1.7 G4 Display Interface.......................... 48 7.1.8 Combined Keyboard/Mouse Interface....................48 7.1.9 Mouse Interface..........................48 7.1.10 PROFIBUS DP Interface........................49 Intefaces at the Y-Repeater........................50 7.2.1...
  • Page 6 IV/69 Bosch Rexroth AG DOK-SUPPL*-VDP16/40/60-PR03-EN-P Rexroth IndraControl VDP 16.1/40.1/60.1 Operator Display...
  • Page 7: System Presentation

    DOK-SUPPL*-VDP16/40/60-PR03-EN-P Bosch Rexroth AG 5/69 Rexroth IndraControl VDP 16.1/40.1/60.1 Operator Display System Presentation System Presentation Brief Description of the VDP 16.1, VDP 40.1 and VDP 60.1 Operator Displays The VDP 16.1/40.1/60.1 operator displays are passive operator and visualiza‐ tion terminals. They form a PC-based operator terminal when used with a control cabinet PC (IPC) equipped with a G4 display interface.
  • Page 8: Displays With Foil Keyboard

    VDP 16.1BB with touch screen Fig.1-4: VDP 16.1 with touch screen VDP 16.1AC with touch screen, without front USB, customized Bosch design Principally, they differ from the standard variant in its rounded edges, the miss‐ ing USB connection and the different mounting dimensions.
  • Page 9: Vdp 40.1 - Variants

    VDP 40.1BE with touch screen Fig.1-6: VDP 40.1 with touch screen VDP 40.1AG with touch screen, without front USB, customized Bosch design Principally, they differ from the standard variant in its rounded edges, the miss‐ ing USB connection and the different mounting dimensions.
  • Page 10: Vdp 60.1

    8/69 Bosch Rexroth AG DOK-SUPPL*-VDP16/40/60-PR03-EN-P Rexroth IndraControl VDP 16.1/40.1/60.1 Operator Display System Presentation VDP 40.1BI with foil keyboard and 16 machine function keys, standard variant Fig.1-7: VDP 40.1 with foil keyboard 1.2.6 VDP 60.1 VDP 60.1BL with foil keyboard, 16 machine function keys, alphanumeric keys and 12"...
  • Page 11: Accessories

    DOK-SUPPL*-VDP16/40/60-PR03-EN-P Bosch Rexroth AG 9/69 Rexroth IndraControl VDP 16.1/40.1/60.1 Operator Display System Presentation Accessories Using the Y-repeater (VAC01.1S-YG4-EXTN) provided as accessory part, two VDP displays can be connected to a control cabinet PC (IPC). The Y-repeater can be cascaded. Therefore, three or more VDPs can be connected to a control cabinet PC.
  • Page 12 10/69 Bosch Rexroth AG DOK-SUPPL*-VDP16/40/60-PR03-EN-P Rexroth IndraControl VDP 16.1/40.1/60.1 Operator Display...
  • Page 13: Important Instructions On Use

    DOK-SUPPL*-VDP16/40/60-PR03-EN-P Bosch Rexroth AG 11/69 Rexroth IndraControl VDP 16.1/40.1/60.1 Operator Display Important Instructions on Use Important Instructions on Use Appropriate Use 2.1.1 Introduction Rexroth products represent state-of-the-art developments and manufacturing. They are tested prior to delivery to ensure operational safety and reliability.
  • Page 14: Inappropriate Use

    12/69 Bosch Rexroth AG DOK-SUPPL*-VDP16/40/60-PR03-EN-P Rexroth IndraControl VDP 16.1/40.1/60.1 Operator Display Important Instructions on Use ● Handling systems and assembly systems ● Packaging and food processing machines ● Printing machines and paper converting machines ● Machine tools ● Wood processing machines The VDP 16.1/40.1/60.1 operator displays may only be operated under the as‐...
  • Page 15: Safety Instructions For Electric Drives And Controls

    DOK-SUPPL*-VDP16/40/60-PR03-EN-P Bosch Rexroth AG 13/69 Rexroth IndraControl VDP 16.1/40.1/60.1 Operator Display Safety Instructions for Electric Drives and Controls Safety Instructions for Electric Drives and Controls Definitions of Terms Application Documentation Application documentation comprises the entire documentation used to inform the user of the product about the use and safety-relevant features for config‐...
  • Page 16: General Information

    You must follow these safety instructions. ● Bosch Rexroth is not liable for damages resulting from failure to observe the safety instructions. ●...
  • Page 17: Hazards By Improper Use

    DOK-SUPPL*-VDP16/40/60-PR03-EN-P Bosch Rexroth AG 15/69 Rexroth IndraControl VDP 16.1/40.1/60.1 Operator Display Safety Instructions for Electric Drives and Controls concept in which measures of risk reduction for personal safety depend on electrical, electronic or programmable control systems. ● The information given in the application documentation with regard to the use of the delivered components contains only examples of applications and suggestions.
  • Page 18: Instructions With Regard To Specific Dangers

    16/69 Bosch Rexroth AG DOK-SUPPL*-VDP16/40/60-PR03-EN-P Rexroth IndraControl VDP 16.1/40.1/60.1 Operator Display Safety Instructions for Electric Drives and Controls ● Risk of injury by improper handling! Injury by crushing, shearing, cutting, hitting! ● Risk of injury by improper handling of batteries! ●...
  • Page 19: Protective Extra-Low Voltage As Protection Against Electric Shock

    Protective extra-low voltage is used to allow connecting devices with basic in‐ sulation to extra-low voltage circuits. On components of an electric drive and control system provided by Bosch Rexroth, all connections and terminals with voltages between 5 and 50 volts are PELV ("Protective Extra-Low Voltage") systems.
  • Page 20 18/69 Bosch Rexroth AG DOK-SUPPL*-VDP16/40/60-PR03-EN-P Rexroth IndraControl VDP 16.1/40.1/60.1 Operator Display Safety Instructions for Electric Drives and Controls Dangerous movements! Danger to life, risk of injury, serious injury or property damage! A risk assessment must be prepared for the installation or machine, with its specific conditions, in which the components of the electric drive and control system are installed.
  • Page 21: Protection Against Magnetic And Electromagnetic Fields During Operation And Mounting

    DOK-SUPPL*-VDP16/40/60-PR03-EN-P Bosch Rexroth AG 19/69 Rexroth IndraControl VDP 16.1/40.1/60.1 Operator Display Safety Instructions for Electric Drives and Controls 3.3.4 Protection Against Magnetic and Electromagnetic Fields During Oper‐ ation and Mounting Magnetic and electromagnetic fields generated by current-carrying conductors or permanent magnets of electric motors represent a serious danger to persons with heart pacemakers, metal implants and hearing aids.
  • Page 22: Battery Safety

    20/69 Bosch Rexroth AG DOK-SUPPL*-VDP16/40/60-PR03-EN-P Rexroth IndraControl VDP 16.1/40.1/60.1 Operator Display Safety Instructions for Electric Drives and Controls ● Always use suitable tools. Use special tools if specified. ● Use lifting equipment and tools in the correct manner. ● Use suitable protective equipment (hard hat, safety goggles, safety shoes, safety gloves, for example).
  • Page 23: Explanation Of Signal Words And The Safety Alert Symbol

    DOK-SUPPL*-VDP16/40/60-PR03-EN-P Bosch Rexroth AG 21/69 Rexroth IndraControl VDP 16.1/40.1/60.1 Operator Display Safety Instructions for Electric Drives and Controls Environmental protection and disposal! The agents (e.g., fluids) used to operate the product might not be environmentally friendly. Dispose of agents harmful to the environment separately from other waste.
  • Page 24 22/69 Bosch Rexroth AG DOK-SUPPL*-VDP16/40/60-PR03-EN-P Rexroth IndraControl VDP 16.1/40.1/60.1 Operator Display...
  • Page 25: Technical Data

    DOK-SUPPL*-VDP16/40/60-PR03-EN-P Bosch Rexroth AG 23/69 Rexroth IndraControl VDP 16.1/40.1/60.1 Operator Display Technical Data Technical Data Front Panel VDP 16.1BB VDP 16.1AC VDP 16.1BK Display 304.8 mm TFT (12"), 800 x 600 pixels, 256,000 colors Operation Touch screen operation Key operation Surface −...
  • Page 26: Ambient Conditions

    24/69 Bosch Rexroth AG DOK-SUPPL*-VDP16/40/60-PR03-EN-P Rexroth IndraControl VDP 16.1/40.1/60.1 Operator Display Technical Data Ambient Conditions In operation Transport Storage Max. ambient temper‐ +5 ℃ to +45 ℃ -20 ℃ to +60 ℃ -20 ℃ to +60 ℃ ature Max. temperature gra‐...
  • Page 27: Ce Marking

    DOK-SUPPL*-VDP16/40/60-PR03-EN-P Bosch Rexroth AG 25/69 Rexroth IndraControl VDP 16.1/40.1/60.1 Operator Display Technical Data Standard Meaning EN 60 068-2-6 Vibration test EN 60 068-2-27 Shock test Fig.4-5: Used standards 4.4.2 CE Marking Declaration of Conformity The electronic products described in the project planning manual comply with...
  • Page 28: Wear Parts

    26/69 Bosch Rexroth AG DOK-SUPPL*-VDP16/40/60-PR03-EN-P Rexroth IndraControl VDP 16.1/40.1/60.1 Operator Display Technical Data The devices of the IndraControl VDP 16.1/40.1/60.1 family are certificated ac‐ cording to ● UL508 (Industrial Control Equipment) and ● C22.2 no. 142-M1987 (CSA) UL file no. E210730 However, there can be combinations or extension stages with limited or missing certification.
  • Page 29: Dimensions And Installation

    DOK-SUPPL*-VDP16/40/60-PR03-EN-P Bosch Rexroth AG 27/69 Rexroth IndraControl VDP 16.1/40.1/60.1 Operator Display Dimensions and Installation Dimensions and Installation Housing Dimensions 5.1.1 Housing Dimensions VDP 16.1 VDP 16.1 standard version Independent of the design of the VDP 16.1 standard variants with M-keys or touch screen the front panel width is 350 mm and the height is 290 mm.
  • Page 30 28/69 Bosch Rexroth AG DOK-SUPPL*-VDP16/40/60-PR03-EN-P Rexroth IndraControl VDP 16.1/40.1/60.1 Operator Display Dimensions and Installation Fig.5-2: Dimensions: Front panel of the VDP 16.1AC Fig.5-3: VDP 16.1BB and VDP 16.1BK: Top View Fig.5-4: VDP 16.1BB and VDP 16.1BK: Bottom view VDP 16.1BB + BK VDP 16.1AC...
  • Page 31: Housing Dimensions Vdp 40.1

    DOK-SUPPL*-VDP16/40/60-PR03-EN-P Bosch Rexroth AG 29/69 Rexroth IndraControl VDP 16.1/40.1/60.1 Operator Display Dimensions and Installation 5.1.2 Housing Dimensions VDP 40.1 Independent of the design of the VDP 40.1 standard variants with M-keys or touch screen the front panel width is 407 mm and the height is 370 mm.
  • Page 32 30/69 Bosch Rexroth AG DOK-SUPPL*-VDP16/40/60-PR03-EN-P Rexroth IndraControl VDP 16.1/40.1/60.1 Operator Display Dimensions and Installation Fig.5-7: Dimensions: VDP 40.1AG Fig.5-8: VDP 40.1BE and VDP 40.1BI: Top View Fig.5-9: VDP 40.1BE and VDP 40.1BI: Bottom view VDP 40.1BE + BI VDP 40.1AG...
  • Page 33: Housing Dimensions Vdp 60.1

    DOK-SUPPL*-VDP16/40/60-PR03-EN-P Bosch Rexroth AG 31/69 Rexroth IndraControl VDP 16.1/40.1/60.1 Operator Display Dimensions and Installation 5.1.3 Housing Dimensions VDP 60.1 The front panel width of the display VDP 60.1BL is 483 mm (19") and the height is 266 mm. Fig.5-11: Dimensions: Front panel of the VDP 60.1BL Fig.5-12:...
  • Page 34: Installation

    32/69 Bosch Rexroth AG DOK-SUPPL*-VDP16/40/60-PR03-EN-P Rexroth IndraControl VDP 16.1/40.1/60.1 Operator Display Dimensions and Installation Fig.5-15: Dimensions: Y-repeater Installation 5.3.1 Installation Notes ● The display is to be installed in such a way that an ergonomic operation is ensured. Additionally, ensure that all machine components can be seen by the operator! ●...
  • Page 35 DOK-SUPPL*-VDP16/40/60-PR03-EN-P Bosch Rexroth AG 33/69 Rexroth IndraControl VDP 16.1/40.1/60.1 Operator Display Dimensions and Installation DANGER Loss of degree of protection IP 65! The mounting surface of the operator display must be: ● free of impurities and ● has to be provided with sufficient mechanical strength and flatness These criteria influence the required degree of protection IP to a great extent.
  • Page 36: Mounting Dimensions Vdp 16.1

    34/69 Bosch Rexroth AG DOK-SUPPL*-VDP16/40/60-PR03-EN-P Rexroth IndraControl VDP 16.1/40.1/60.1 Operator Display Dimensions and Installation 5.3.3 Mounting Dimensions VDP 16.1 Fig.5-17: Mounting dimensions of the VDP 16.1 devices...
  • Page 37: Mounting Dimensions Vdp 40.1

    DOK-SUPPL*-VDP16/40/60-PR03-EN-P Bosch Rexroth AG 35/69 Rexroth IndraControl VDP 16.1/40.1/60.1 Operator Display Dimensions and Installation 5.3.4 Mounting Dimensions VDP 40.1 Fig.5-18: Mounting dimensions of the VDP 40.1 devices 5.3.5 Mounting Dimensions VDP 60.1 Fig.5-19: Mounting dimensions of the VDP 60.1 devices...
  • Page 38 36/69 Bosch Rexroth AG DOK-SUPPL*-VDP16/40/60-PR03-EN-P Rexroth IndraControl VDP 16.1/40.1/60.1 Operator Display...
  • Page 39: Display And Operating Components

    DOK-SUPPL*-VDP16/40/60-PR03-EN-P Bosch Rexroth AG 37/69 Rexroth IndraControl VDP 16.1/40.1/60.1 Operator Display Display and Operating Components Display and Operating Components Backlight Switch-off 6.1.1 General Information The service life of the backlight of the display is limited, see chapter 4.5 "Wear Parts" on page To extend the service life of the LCD backlight, the flat screen display is provi‐...
  • Page 40: Foil Keyboard

    38/69 Bosch Rexroth AG DOK-SUPPL*-VDP16/40/60-PR03-EN-P Rexroth IndraControl VDP 16.1/40.1/60.1 Operator Display Display and Operating Components Fig.6-2: LEDs for operating and error display on the front panel NOTICE Depending on the connected control cabinet PC (IPC), not all LEDs are activated, therefore not all warnings/messages are displayed.
  • Page 41: Position Of The Buttons

    DOK-SUPPL*-VDP16/40/60-PR03-EN-P Bosch Rexroth AG 39/69 Rexroth IndraControl VDP 16.1/40.1/60.1 Operator Display Display and Operating Components 6.3.2 Position of the Buttons ① Machine function keys (M-keys) L1 to L8 ② Function keys F2 to F9 ③ Operating keys OP2 to OP9 ④...
  • Page 42: M-Keys

    40/69 Bosch Rexroth AG DOK-SUPPL*-VDP16/40/60-PR03-EN-P Rexroth IndraControl VDP 16.1/40.1/60.1 Operator Display Display and Operating Components Keys of the VDP 16.1BK and VDP 40.1BI Corresponding shortcut of a standard keyboard <CTRL> + <SHIFT> + <ALT> + <F2> <CTRL> + <SHIFT> + <ALT> + <F9>...
  • Page 43: Keys Vdp 60.1

    DOK-SUPPL*-VDP16/40/60-PR03-EN-P Bosch Rexroth AG 41/69 Rexroth IndraControl VDP 16.1/40.1/60.1 Operator Display Display and Operating Components Byte 3 Byte 2 Byte 1 Byte 0 M-keys, right M-keys, left Status (Bit 0 = R1 to Bit 7 = (Bit 0 = L1 to Bit 7 = Fig.6-7:...
  • Page 44: M-Keys

    42/69 Bosch Rexroth AG DOK-SUPPL*-VDP16/40/60-PR03-EN-P Rexroth IndraControl VDP 16.1/40.1/60.1 Operator Display Display and Operating Components Corresponding shortcut of a standard key‐ Key of the VDP 60.1BL board Function keys F1 to F8 F1 to F8 Special key SHIFT + F1-...
  • Page 45: Alphanumeric Block

    DOK-SUPPL*-VDP16/40/60-PR03-EN-P Bosch Rexroth AG 43/69 Rexroth IndraControl VDP 16.1/40.1/60.1 Operator Display Display and Operating Components Alphanumeric Block The keys of the alphanumeric block send the default PS/2 codes to the PC. The alpha key is locking "toggling" and its output is no code, but only controls the keyboard controller.
  • Page 46 44/69 Bosch Rexroth AG DOK-SUPPL*-VDP16/40/60-PR03-EN-P Rexroth IndraControl VDP 16.1/40.1/60.1 Operator Display Display and Operating Components Meaning Y-Repeater is supplied by the control cab‐ inet PC (IPC) with power The control cabinet PC (IPC) is connected VDP1 to VDP1 The control cabinet PC (IPC) is connected...
  • Page 47: Interfaces

    DOK-SUPPL*-VDP16/40/60-PR03-EN-P Bosch Rexroth AG 45/69 Rexroth IndraControl VDP 16.1/40.1/60.1 Operator Display Interfaces Interfaces Interfaces at the VDP 7.1.1 View on the Connector Panel Fig.7-1: Interface to the control cabinet PC 7.1.2 General Information NOTICE Malfunctions due to insufficient shielding! Use only shielded cables and metallic, conductive connectors or coupling hous‐...
  • Page 48: S3/S4 Rotary Switch

    46/69 Bosch Rexroth AG DOK-SUPPL*-VDP16/40/60-PR03-EN-P Rexroth IndraControl VDP 16.1/40.1/60.1 Operator Display Interfaces Designa‐ Connector type / in‐ Mating connector or tion at the Connection type tegrated cable (from outside) housing XIPC G4 display interface D-Sub connector, D-Sub female con‐ nector, >...
  • Page 49: Xusb Interfaces

    DOK-SUPPL*-VDP16/40/60-PR03-EN-P Bosch Rexroth AG 47/69 Rexroth IndraControl VDP 16.1/40.1/60.1 Operator Display Interfaces n. c. A standard 24 V industrial power supply unit can be used for the voltage supply. NOTICE Possible damages if an inadequate power sup‐ ply unit is used.
  • Page 50: G4 Display Interface

    48/69 Bosch Rexroth AG DOK-SUPPL*-VDP16/40/60-PR03-EN-P Rexroth IndraControl VDP 16.1/40.1/60.1 Operator Display Interfaces NOTICE The general function of non-specification-com‐ pliant USB devices can not be guaranteed, even if they are functioning e.g. at the USB in‐ terface directly at the control cabinet PC.
  • Page 51: Profibus Dp Interface

    DOK-SUPPL*-VDP16/40/60-PR03-EN-P Bosch Rexroth AG 49/69 Rexroth IndraControl VDP 16.1/40.1/60.1 Operator Display Interfaces PS/2 Mini DIN female connector, 6-pin Interrupt (IRQ): PS/2 mouse support: Enabled PS/2 BIOS presetting: Mouse: Auto detect Fig.7-8: Mouse interface XPS2MS max. 1,5 m Mouse Data XPS2MS...
  • Page 52: Intefaces At The Y-Repeater

    50/69 Bosch Rexroth AG DOK-SUPPL*-VDP16/40/60-PR03-EN-P Rexroth IndraControl VDP 16.1/40.1/60.1 Operator Display Interfaces Fig.7-11: PROFIBUS DP interface XDPSLAVE The bus cable is specified as cable type A according to EN 50170, part 8-2. It must comply with the following cable parameters:...
  • Page 53: Description Of The Interfaces - Overview

    DOK-SUPPL*-VDP16/40/60-PR03-EN-P Bosch Rexroth AG 51/69 Rexroth IndraControl VDP 16.1/40.1/60.1 Operator Display Interfaces Fig.7-15: Interface to the VDP displays 7.2.2 Description of the Interfaces - Overview Designation at the Connector type (in‐ Mating connector or Connection type housing tegrated) cable (from outside) Weidmüller connec‐...
  • Page 54: Digital 24 V Input (Changeover Input)

    52/69 Bosch Rexroth AG DOK-SUPPL*-VDP16/40/60-PR03-EN-P Rexroth IndraControl VDP 16.1/40.1/60.1 Operator Display Interfaces Connection Function G4 display interface to control cabinet PC (IPC) G4 display interface to VDP 1 G4 display interface to VDP 2 Fig.7-18: Assignment of the three G4 display interfaces Via the G4 display interfaces image data as well as the keyboard and mouse signals are transmitted from VDP displays to the control cabinet PC (IPC).
  • Page 55 DOK-SUPPL*-VDP16/40/60-PR03-EN-P Bosch Rexroth AG 53/69 Rexroth IndraControl VDP 16.1/40.1/60.1 Operator Display Interfaces Input voltage: Nominal value for "0" -3 V ... + 5 V Nominal value for "1" 11 V ... 30 V Input current: Nominal value for "0" < 2.5 mA Nominal value for "1"...
  • Page 56 54/69 Bosch Rexroth AG DOK-SUPPL*-VDP16/40/60-PR03-EN-P Rexroth IndraControl VDP 16.1/40.1/60.1 Operator Display...
  • Page 57: Maintenance

    LCD Display A fading backlight causes a progressive deterioration of the readability of the LCD display, so that a backlight exchange is necessary. For further information please contact the Bosch Rexroth Service, see also chapter 12 "Service and Support" on page...
  • Page 58: Connecting Two Vdps Via The Y-Repeater

    56/69 Bosch Rexroth AG DOK-SUPPL*-VDP16/40/60-PR03-EN-P Rexroth IndraControl VDP 16.1/40.1/60.1 Operator Display Maintenance Connecting two VDPs via the Y-Repeater To connect two VDP displays to one control cabinet PC (IPC), the Y-repeater is available as accessories. The Y-Repeater is located between the control cabinet PC (IPC) and the two VDP displays.
  • Page 59: Software

    DOK-SUPPL*-VDP16/40/60-PR03-EN-P Bosch Rexroth AG 57/69 Rexroth IndraControl VDP 16.1/40.1/60.1 Operator Display Software Software Touch Screen Software In the VDP 16.1BB and VDP 16.2AC as well as VDP 40.2BE and VDP 40.2AG displays a touch screen is integrated, that allows the operation via the touch- sensitive surface of the displays.
  • Page 60 58/69 Bosch Rexroth AG DOK-SUPPL*-VDP16/40/60-PR03-EN-P Rexroth IndraControl VDP 16.1/40.1/60.1 Operator Display...
  • Page 61: Environmental Protection And Disposal

    DOK-SUPPL*-VDP16/40/60-PR03-EN-P Bosch Rexroth AG 59/69 Rexroth IndraControl VDP 16.1/40.1/60.1 Operator Display Environmental Protection and Disposal Environmental Protection and Disposal 10.1 Environmental Protection Production Processes The products are made with energy- and resource-optimized production pro‐ cesses which allow re-using and recycling the resulting waste. We regularly try to replace pollutant-loaded raw materials and supplies by more environment- friendly alternatives.
  • Page 62 60/69 Bosch Rexroth AG DOK-SUPPL*-VDP16/40/60-PR03-EN-P Rexroth IndraControl VDP 16.1/40.1/60.1 Operator Display Environmental Protection and Disposal Metals contained in electric and electronic modules can also be recycled by means of special separation processes. Products made of plastics can contain flame retardants. These plastic parts are labeled according to EN ISO 1043.
  • Page 63: Ordering Information

    DOK-SUPPL*-VDP16/40/60-PR03-EN-P Bosch Rexroth AG 61/69 Rexroth IndraControl VDP 16.1/40.1/60.1 Operator Display Ordering Information Ordering Information 11.1 Type Designation Code 11.1.1 General Information According to the following type designation codes there are different variants of the VDP 16.1, VDP 40.1, and VDP 60.1 displays.
  • Page 64: Vdp 60.1

    62/69 Bosch Rexroth AG DOK-SUPPL*-VDP16/40/60-PR03-EN-P Rexroth IndraControl VDP 16.1/40.1/60.1 Operator Display Ordering Information 11.3 VDP 40.1 Fig.11-2: Type designation code VDP 40.1...
  • Page 65 DOK-SUPPL*-VDP16/40/60-PR03-EN-P Bosch Rexroth AG 63/69 Rexroth IndraControl VDP 16.1/40.1/60.1 Operator Display Ordering Information 11.4 VDP 60.1 Fig.11-3: Type designation code VDP 60.1...
  • Page 66: Accessories

    64/69 Bosch Rexroth AG DOK-SUPPL*-VDP16/40/60-PR03-EN-P Rexroth IndraControl VDP 16.1/40.1/60.1 Operator Display Ordering Information 11.5 Accessories 11.5.1 Y-Repeater Connection unit for connecting two operating units (VDP 16.1/40.1/60.1) with the same resolution and of the same design with a control cabinet PC (IPC).
  • Page 67: Service And Support

    DOK-SUPPL*-VDP16/40/60-PR03-EN-P Bosch Rexroth AG 65/69 Rexroth IndraControl VDP 16.1/40.1/60.1 Operator Display Service and Support Service and Support Our service helpdesk at our headquarters in Lohr, Germany and our worldwide service will assist you with all kinds of enquiries. You can reach us around the clock - even on weekend and on holidays.
  • Page 68 66/69 Bosch Rexroth AG DOK-SUPPL*-VDP16/40/60-PR03-EN-P Rexroth IndraControl VDP 16.1/40.1/60.1 Operator Display...
  • Page 69: Index

    DOK-SUPPL*-VDP16/40/60-PR03-EN-P Bosch Rexroth AG 67/69 Rexroth IndraControl VDP 16.1/40.1/60.1 Operator Display Index Index Accessories............64 Hazardous substances........59 Accumulators............59 Alphanumeric block VDP 60.1......43 Ambient conditions..........24 Inappropriate use..........12 Appropriate use........... 11 Consequences, exclusion of liability .... 11...
  • Page 70 68/69 Bosch Rexroth AG DOK-SUPPL*-VDP16/40/60-PR03-EN-P Rexroth IndraControl VDP 16.1/40.1/60.1 Operator Display Index Recycling............59 Touch screen............43 Return of products..........59 Touch screen software........57 Type designation code........61 Safety instructions for electric drives and con‐ trols..............13 UL/CSA certified..........25 Service life Backlight ............
  • Page 71 DOK-SUPPL*-VDP16/40/60-PR03-EN-P Bosch Rexroth AG 69/69 Rexroth IndraControl VDP 16.1/40.1/60.1 Operator Display Notes...
  • Page 72 Bosch Rexroth AG Electric Drives and Controls P.O. Box 13 57 97803 Lohr, Germany Bgm.-Dr.-Nebel-Str. 2 97816 Lohr, Germany Tel. +49 (0)93 52-40-0 +49 (0)93 52-48 85 www.boschrexroth.com Printed in Germany R911307654 DOK-SUPPL*-VDP16/40/60-PR03-EN-P...