hit counter script

Convenience Functions & Controls; Cooling Operations - LG AUUQ18GH1 Svc Manual

Hide thumbs Also See for AUUQ18GH1:
Table of Contents

Advertisement

Part 2 Functions & Controls
6. Convenience Functions & Controls

6.1 Cooling Operations

6.1.1 Cooling Mode
• Operating frequency of compressor depends on the load condition, like the difference between the room temp. and
the set temp., frequency restrictions.
• If the compressor operates at some frequency, the operating frequency of compressor cannot be changed within 30
seconds. ( not emergency conditions)
• Compressor turned off when
- intake air temperature is in between ±0.5°C of the setting temp. limit for three minutes continuously.
- intake air temperature reaches below 1.0°C of the temperature of setting temp..
• Compressors three minutes time delay.
- After compressor off, the compressor can restart minimum 3 minutes later.
Copyright ©2013 LG Electronics. Inc. All right reserved.
Only for training and service purposes
- 25 -
LGE Internal Use Only

Advertisement

Table of Contents
loading

Table of Contents