IDS1000 Container Data Center Single-Zone Fire Extinguishing System User Manual Issue Date 2014-3-15 HUAWEI TECHNOLOGIES CO., LTD.
Page 2
Notice The purchased products, services and features are stipulated by the contract made between Huawei and the customer. All or part of the products, services and features described in this document may not be within the purchase scope or the usage scope. Unless otherwise specified in the contract, all statements, information, and recommendations in this document are provided "AS IS"...
Purpose This document describes the operation methods and precautions for the fire extinguishing system in the IDS1000 container data center in terms of configurations, power-on commissioning, maintenance, alarm references, troubleshooting, and parts replacement. It provides you a quick grasp of the operations of the fire extinguishing system in the container data center.
For more information about emergency operations, contact Huawei technical support. Common Critical Alarms and Faults Table 2-1 describes the common critical alarms and faults of the container data center.
Y => Rectify the connection fault. Check whether the fault is rectified. If yes, no further action is required. If no, contact Huawei technical support. N => Contact Huawei technical support. ----End 6.2 Heat Detector Fault Possible Causes ...
Y => Rectify the connection fault. Check whether the fault is rectified. If yes, no further action is required. If no, contact Huawei technical support. N => Contact Huawei technical support. ----End 6.3 Gas Release Indicator Fault Possible Causes ...
Use a multimeter to check whether there is any short circuit or open circuit. Y => Rectify the connection fault. Check whether the fault is rectified. If yes, no further action is required. If no, contact Huawei technical support. N => Contact Huawei technical support. ----End 6.4 Audible and Visual Alarm Fault Possible Causes ...
Page 47
Check whether the fault is rectified. Check whether the fault is rectified. If yes, no further action is required. If no, contact Huawei technical support. N => Contact Huawei technical support. ----End Issue 01 (2014-3-15) Huawei Proprietary and Confidential...
Y => Rectify the connection fault. Check whether the fault is rectified. If yes, no further action is required. If no, contact Huawei technical support. N => Contact Huawei technical support. ----End Issue 01 (2014-3-15) Huawei Proprietary and Confidential...
Screwdriver Procedure Step 1 Check whether the gas cylinder is driven successfully. Y => Contact Huawei technical support. N => Go to Step Step 2 Replace the driving device of the gas cylinder. Check whether the fault is rectified.
Page 50
Check whether the gas extinguishing controller is faulty. Y => Go to Step 2.2. N => Contact Huawei technical support. Replace the gas extinguishing controller. Check whether the fault is rectified. Y => No further action is required. N => Contact Huawei technical support.
Step 6 Check that the new smoke detector is working properly. ----End Follow-up Procedure Send the faulty smoke detector together with a Repair Notice to your local Huawei office for repair. 7.2 Replacing a Heat Detector Prerequisites ...
Step 6 Check that the new heat detector is working properly. ----End Follow-up Procedure Send the faulty heat detector together with a Repair Notice to your local Huawei office for repair. 7.3 Replacing a Gas Release Indicator Prerequisites ...
Step 4 Check that the new audible and visual alarm is working properly. ----End Follow-up Procedure Send the faulty audible and visual alarm together with a Repair Notice to your local Huawei office for repair. Issue 01 (2014-3-15) Huawei Proprietary and Confidential...
Step 3 Check that the new fire alarm bell is working properly. ----End Follow-up Procedure Send the faulty fire alarm bell together with a Repair Notice to your local Huawei office for repair. 7.6 Replacing a Fire Cylinder Contact Huawei technical support.
Step 2 Install a new gas extinguisher and attach a label to it. ----End Follow-up Procedure Send the faulty gas extinguisher together with a Repair Notice to your local Huawei office for repair. 7.8 Replacing the Emergency Start/Abort Switch Prerequisites ...
Page 63
IDS1000 Container Data Center User Manual 8 Emergency Operation If gas is released, contact Huawei technical support. If gas is not released, go to the next step. Step 4 Check whether there are alarms on the gas fire extinguishing controllers outside the container.
Do not enter the fire alarm area without determining the severity and impact of the fire. Step 3 Observe the gas release indicator to check whether gas is released to extinguish the fire. If gas is released, contact Huawei technical support. If gas is not released, go to the next step.
Step 8 Rapidly power off the devices in the smoke area or near the combustibles and switch off the circuit breakers. Step 9 After the fire alarm is cleared, report the event to the management department of the data center and contact Huawei technical support. ----End Follow-up Procedure Analyze the cause of the fault, and work out and record the preventive measures.
Page 66
Do not enter the fire alarm area without determining the severity and impact of the fire. Step 3 Observe the gas release indicator to check whether gas is released to extinguish the fire. If gas is released, contact Huawei technical support. If gas is not released, go to the next step.