0.3.2 Copyright This document may be duplicated and distributed only with the express permission of Siemens, and may be passed on only to authorized persons or companies with the required technical knowledge. 4 / 22 Siemens Desigo Touch and Web...
· From the support team at headquarters fieldsupport-zug.ch.sbt@siemens.com no local POC is available. Siemens assumes no liability to the extent allowed under the law for any losses resulting from a failure to comply with the aforementioned points or for the improp- er compliance of the same.
Siemens PXM40 and PXM5 nology to be able to install and configure the Siemens PXM40 and PXM5 nology to be able to install and configure the Siemens PXM40 and PXM50 touch panels.
Displaying system texts, plant overviews, plant diagrams, simple alarm lists, schedules, and trends. schedules, and trends. · Saving Favorites. Saving Favorites. Context of the descriptions in this manual. 7 / 22 Siemens Desigo Touch and Web Desigo Touch and Web CM111029en_04 Building Technologies Commissioning Commissioning – Topology...
See the XWP online help CM111006en (chm). Note: You can browse the pages at any time during commissioning by using the buttons < Back and Next >. 8 / 22 Siemens Desigo Touch and Web CM111029en_04 Building Technologies Commissioning – IT security...
Manual via the alphanumeric keypad. Below, we describe how to proceed with a manual entry. The procedure for IPv4 is virtually automatic for the DHCP method. 9 / 22 Siemens Desigo Touch and Web CM111029en_04 Building Technologies Commissioning – Touch panel commissioning – Step-by-step...
Page 10
> This concludes “Binding”. The main view for the desired project is di . The main view for the desired project is dis- played within a few seconds. played within a few seconds. 10 / 22 Siemens Desigo Touch and Web Desigo Touch and Web CM111029en_04 Building Technologies Commissioning Commissioning –...
Page 11
Users immediately receive the following feedback for incorrect or improperly immediately receive the following feedback for incorrect or improperly entered login information: entered login information: 11 / 22 Siemens Desigo Touch and Web Desigo Touch and Web CM111029en_04 Building Technologies Commissioning Commissioning –...
Page 12
This completes the technical part of commissioning. Different settings are availa- ble, however, for user-friendly operation of the touch panel. They can be edited after login. To do this, see a detailed description in the operating instructions [4]. 12 / 22 Siemens Desigo Touch and Web CM111029en_04 Building Technologies Commissioning –...
· No end user access to lower operating system functions. · Alarms are displayed on the operator unit even if the screen is inactive. · Siemens guarantees compatibility and product replacement or system up- grades throughout the entire life cycle.
Firefox ≥ 4.0, Internet Explorer ≥ 10.0 Recommended web browser for standard operator units. · Fully tested and approved browser. · Supported officially by Siemens BT. · All functions are available and can be executed as documented. Grade B Safari–iPad2, Safari–iPad3 Compatible web browser.
Number of graphic pages per customized view. 2.5.2.3 Graphics pages Item Limits Description BACnet objects Max. number of BACnet objects per graphics page 15 / 22 Siemens Desigo Touch and Web CM111029en_04 Building Technologies Compatibility & limitations – System limits 2014-08-15...
· 10 trends per customized view · 10 schedulers per customized view ð Important: The configuration data size < 7MB applies to all of the above 16 / 22 Siemens Desigo Touch and Web CM111029en_04 Building Technologies Compatibility & limitations – System limits...
General recommendation: Format png or jpg is the preferred format depend- ing on the application, as this format allows for achieving best results relative to resolution and min. memory requirements. 17 / 22 Siemens Desigo Touch and Web CM111029en_04 Building Technologies Compatibility &...
– The PXG3.W100 web interface supports user profiles with access level ≥ Extended Operation, allowing for resetting and confirming alarms. – Read/write access rights to the BACnet object level are not processed. 18 / 22 Siemens Desigo Touch and Web CM111029en_04 Building Technologies Compatibility &...
Extra-low voltage fuse for max. power consumption at AC 24 V, low voltage fuse for max. power consumption at AC 24 V, depending on line cross depending on line cross-section 19 / 22 Siemens Desigo Touch and Web Desigo Touch and Web CM111029en_04 Building Technologies Compatibility &...
The Select the firmware version dropdown list will appear only if there’s more than one firmware version available. Click Start Loading. ---> FWDT starts uploading and displays a progress bar. 20 / 22 Siemens Desigo Touch and Web CM111029en_04 Building Technologies Compatibility & limitations – Firmware updates...
Release SVC button. Wait for the device to fully start up unconfigured. (RUN LED is on, SVC LED flashes.) Start firmware download process with SSA-DNT. 21 / 22 Siemens Desigo Touch and Web CM111029en_04 Building Technologies Compatibility & limitations – Firmware updates...