Diagnostics and troubleshooting
10.2 Fault codes and corrective actions (Segment display)
ID
Symbols
Message
AJ
Limit monitoring 1
Above limit
AL
Limit monitoring 1
Below limit
An
Limit monitoring 2
Above limit
Ao
Limit monitoring 2
Below limit
AP
Limit monitoring 3
Above limit
Ar
Limit monitoring 3
Below limit
AU
Event counter 1
Number overruns above
threshold
Process alarm
AY
Event counter 1
Number overruns above
threshold
Maintenance required
b0
Event counter 3
Number underruns above
threshold
Process alarm
114
Cause/action
Monitored value is above limit (set in parameter "Upper limit").
Monitored value is below limit (set in parameter "Lower limit").
Monitored value is above limit (set in parameter "Upper limit").
Monitored value is below limit (set in parameter "Lower limit").
Monitored value is above limit (set in parameter "Upper limit").
Monitored value is below limit (set in parameter "Lower limit").
The number of overruns of the process value (set in parameters "Upper
limit" and "Monitored value") has reached the threshold.
Reset and acknowledge event counter.
Check process conditions.
Check limit monitoring and event counter settings.
The number of overruns of the process value (set in parameters "Upper
limit" and "Monitored value") has reached the threshold.
Reset and acknowledge event counter.
Check process conditions.
Check limit monitoring and event counter settings.
The number of underruns of the process value (set in parameters "Lower
limit" and "Monitored value") has reached the threshold.
Reset and acknowledge event counter.
Check process conditions.
Check limit monitoring and event counter settings.
FC310 (From firmware 4.0)
Operating Instructions, 06/2018, A5E44036384-AA