Room thermostat with 24-hour time switch and large LCD RDJ100 Programmable, for heating systems 2-position or PID control to switch on/off heating systems Operating modes: Automatic, Comfort, Energy saving, and Frost protection 24-hour time switch Service interval reminder Large LCD display Minimum and maximum setpoint limitation Battery powered: 2 x alkaline type AA batteries, 1.5 V...
Page 2
Pumps Functions Temperature control RDJ100 offers both 2-position and PID intelligent learning temperature control, configurable via parameter P01 (control behaviour). 2-position control algorithm to switch on and off the heating system within a switching differential (SD) as per the difference between setpoint setting and measured room temperature.
Page 3
Approximately 6 minutes WARNING Do not use PID fast for oil boilers or electric mechanical actuators! Backup When removing the batteries, the setpoints and information required for operating mode changeover are retained for max. 2 minutes. Siemens Datasheet A6V10954415_en--_e Building Technologies 2018-11-20...
Page 4
Exit parameter setting Parameter setting The parameter setting remains in non-volatile memory and is not erased when the battery is removed. The reset function on the rear of the thermostat reloads the factory settings. Siemens Datasheet A6V10954415_en--_e Building Technologies 2018-11-20...
Page 5
60 minutes by turning the setting knob or pressing the advance button. The thermostat will control under comfort mode regardless of the selected operating mode (automatic, comfort or energy saving). Siemens Datasheet A6V10954415_en--_e...
Page 6
(for small valves 2.5mm) Electromotoric SFA21.. 4863 actuator *) The documents can be downloaded from http://siemens.com/bt/download. Ordering When ordering, specify both name and product number e.g. room temperature controller RDJ100. Order valves and actuators as separate items. Mechanical design...
Page 7
RDJ100 Elements Functions Room temperature display in °C The device controls to the adjusted comfort temperature setpoint The device controls to the adjusted energy saving temperature setpoint The device controls to the preset frost protection temperature setpoint Setpoint temporarily overridden until the next switching time Indicates low battery power;...
Page 8
RDJ100 Elements Functions Time setting position First switch-on time First switch-off time Second switch-on time Second switch-off time Comfort temperature setting Energy saving temperature setting RUN position Program slider Advance button (override / presence button) Temperature setting knob Battery compartment...
Page 9
Mount the device on a flat wall and in compliance with local regulations. If the reference room contains thermostatic radiator valves, set them to their fully open position. The devices are suitable for wall mounting. Recommended height: 1.5 m above the floor. Siemens Datasheet A6V10954415_en--_e Building Technologies 2018-11-20...
Page 10
Switching current Max. 5 A res., 2 A ind. At AC 250 V Min. 8 mA Insulating strength Between relay AC 3,750 V contacts and coil Between relay AC 1,000 V contacts (same pole) Siemens Datasheet A6V10954415_en--_e Building Technologies 2018-11-20...
Page 11
Class 2M2 Storage IEC 60721-3-1 Climatic conditions Class 1K3 Temperature -10…+60 °C Humidity <90% r.h. Standards, directives and approvals EU conformity (CE) A6V101123363 *) RCM conformity A6V11161600 *) Safety class II as per EN 60730-1 Siemens Datasheet A6V10954415_en--_e Building Technologies 2018-11-20...
Page 12
(RoHS compliance, materials composition, packaging, environmental benefit, disposal). *) The documents can be downloaded from http://siemens.com/bt/download. Eco design and labeling directives Based on EU Regulation 813/2013 (Eco design directive) and 811/2013 (Labeling directive) concerning space heaters, the following classes apply:...
Page 13
Room temperature controller with direct control of a heating circuit pump (pre-control by manual mixing valve) F1 Thermal reset limit thermostat N1 Room temperature controller RDJ100 F2 Safety limit thermostat Y1 3-port valve with manual adjustment M1 Circulating pump Y2 Magnetic valve...
Page 14
June 2018 control behavior, parameter settings and service interval reminder. Z, A March First release. 2017 1) Product index can be found next to the production date on the rear of the device "YYMMDDX". Siemens Datasheet A6V10954415_en--_e Building Technologies 2018-11-20...
Page 15
Siemens Datasheet A6V10954415_en--_e Building Technologies 2018-11-20...