14 Operating Parameters
14.4 Recording and Reporting
14.4.5

Report Configuration

Parameter
Company:
Department:
Supervisor:
Inspector:
Location:
Comment:
Evaluation mode according to:
Flagging acc. to
IEC 61000-4-30
Power frequency:
99.5 % of measurand should be in -1.0 % to 1.0 % deviation of the power
frequency.
100 % of measurand should be in -6.0 % to 4.0 % deviation of the power
frequency.
Power supply voltage magnitude:
95 % of measurand should be in -10.0 % to 10.0 % deviation of the
clared input voltage Udin.
100 % of measurand should be in -15.0 % to 10.0 % deviation of the
clared input voltage Udin.
Voltage unbalance:
95 % of measurand should be less than 2.0 %.
100 % of measurand should be less than 3.0 %.
Subgroup Total Harmonic Distortion (THDS):
95 % of measurand should be less than 8.0 %.
Supply voltage interruptions:
1. Short interruption until 1 second duration
2. Short interruption until 3 minute duration
3. Long interruption longer than 3 minute duration
Harmonic voltages:
Even harmonics
Odd harmonics: multiples of 3
Odd harmonics: not multiples of 3
1)
According to EN 50160, up to 3 % unbalance can occur in 3-wire networks in areas with many 1-wire and
2-wire connections.
256
Default Setting
General Information
Power Quality Report
EN 50160 LV&MV
no
1)
-
Any text displayed in the print-
out of the power quality report
EN 50160 LV&MV
EN 50160 HV
User defined
no
yes
Any setting for user-defined
evaluation mode
Any setting for user-defined
evaluation mode
Any setting for user-defined
evaluation mode
Any setting for user-defined
evaluation mode
Any setting for user-defined
evaluation mode
Any setting for user-defined
evaluation mode
SENTRON PAC5100/5200, 7KM5212/5412, Device Manual
E50417-H1040-C568-A1, Edition 03.2015