Manual
+U
H
+
U
--
Figure 2-35
Single--pin wiring of a non--floating voltage supply with negative polarity to ground
-U
H
--
U
+
Figure 2-36
Single--pin wiring of a non--floating voltage supply with positive polarity to ground
Figure 2-35 and Figure 2-36:
The voltage dip on the ground rail between the voltage source and the input amplifier appears
as a measuring error. Only use when ground cables are short or choose a circuit configuration
as shown in figure 2-37!
+U
H
+
U
--
Figure 2-37
Double--pin wiring of a voltage source with positive polarity to ground
SIPART DR24 6DR2410
C79000-G7476-C153-03
2.2.4 Alternative Wiring for I- and U Input
AE+
+
AE--
--
GND
AE+
+
only permitted when
AE--
wired for 1 V
--
GND
AE+
+
AE--
--
GND
2 Installation
2.2 Electrical Connection
127