Siemens Sinteso FD20 Product Data
Hide thumbs Also See for Sinteso FD20:
Table of Contents

Advertisement

FD20
Sinteso™ Detector System
Range Description
Product Data
008164_y_en_--
Smart Infrastructure
2019-05-07

Advertisement

Table of Contents
loading

Summary of Contents for Siemens Sinteso FD20

  • Page 1 FD20 Sinteso™ Detector System Range Description Product Data 008164_y_en_-- Smart Infrastructure 2019-05-07...
  • Page 2 All rights created by patent grant or registration of a utility model or design patent are reserved. Issued by: Siemens Switzerland Ltd. Smart Infrastructure Global Headquarters Theilerstrasse 1a CH-6300 Zug Tel. +41 58 724-2424 www.siemens.com/buildingtechnologies Edition: 2019-05-07 Document ID: 008164_y_en_-- © Siemens Switzerland Ltd, 2004 2 | 152 008164_y_en_--...
  • Page 3: Table Of Contents

    Table of contents About this document ................5 STEP download ..................5 Download center ..................5 Revision history ..................6 Automatic fire detectors ................. 7 Point detector FDOOT221, FDO221, FDT221 ..........7 Multi-sensor fire detector FDOOT241-Ax, FDOOT241-8 ......11 Point detector FDOOT241-9, FDOOT241-A, FDO241, FDT241 ....15 Multi-sensor fire detector FDOOTC241 ............21 Detector base and base attachment............
  • Page 4 10.7 Manual call point FDM223-Ex ..............121 10.8 Infrared flame detector DF1101-Ex ............125 10.9 Line adapter (Ex) FDCL221-Ex ..............127 10.10 Safety barrier SB3 ................... 131 Test units and accessories ..............133 11.1 Detector exchanger FDUD291 ..............133 11.2 Detector exchanger and tester FDUD292, intelligent detector tester FDUD293 ....................
  • Page 5: About This Document

    About this document STEP download 1 About this document Goal and purpose This document is an overview of Sinteso FD20 peripheral devices and accessories. This document contains the following excerpts from the data sheets for the individual products: ● Application/functions ●...
  • Page 6: Revision History

    About this document Revision history 1.3 Revision history The reference document's version applies to all languages into which the reference document is translated. The first edition of a language version or a country variant may, for example, be version 'd' instead of 'a' if the reference document is already this version. The table below shows this document's revision history: Version Edition date...
  • Page 7: Automatic Fire Detectors

    Automatic fire detectors Point detector FDOOT221, FDO221, FDT221 2 Automatic fire detectors 2.1 Point detector FDOOT221, FDO221, FDT221 2.1.1 Use Multi-sensor smoke detector FDOOT221 Multi-sensor smoke detector consisting of: ● Point detector with additional heat sensors ● Detector dust cap to protect the point detector during the construction phase Function ●...
  • Page 8 Automatic fire detectors Point detector FDOOT221, FDO221, FDT221 Smoke detector FDO221 Smoke detector consisting of: ● Point detector ● Detector dust cap to protect the point detector during the construction phase Function ● Functions according to the scattered light principle with one sensor: Optical forward scattering ●...
  • Page 9 Automatic fire detectors Point detector FDOOT221, FDO221, FDT221 2.1.2 Type Overview Type Designation Order no. Weight [kg] Point detector FDOOT221 Multi-sensor smoke detector A5Q00001566 0.105 FDO221 Smoke detector A5Q00001565 0.104 FDT221 Heat detector A5Q00001567 0.086 Accessories FDX291 Dummy detector S54319-F2-A1 0.120 You will find information about detector bases and accessories in document 007775.
  • Page 10 Automatic fire detectors Point detector FDOOT221, FDO221, FDT221 FDOOT221 FDO221 FDT221 Standards CEA 4021 EN 54-7 EN 54-5 EN 54-7 EN 54-17 EN 54-17 EN 54-17 Approvals: ● G204006 G204018 G204020 ● LPCB 126bg/01 126bf/01 126bj/01 ● 3029351 3029351 3046115 ●...
  • Page 11: Multi-Sensor Fire Detector Fdoot241-Ax, Fdoot241-8

    FDOOT241-A3 (AlgoRex AnalogPLUS, FDnet) – FDOOT241-A4 (SIGMALOOP, FDnet) – FDOOT241-A5 (AlgoRex Interactive, FDnet) – FDOOT241-A9: Collective / GMT (Cerberus / Siemens) / SynoLINE300, FDnet – FDOOT241-8 (MS8/PMT, FDnet) ● For early detection of flaming fires of solid and liquid substances as well as of smoldering fires ●...
  • Page 12 Automatic fire detectors Multi-sensor fire detector FDOOT241-Ax, FDOOT241-8 2.2.2 Type Overview Type Order number Designation Weight [kg] Point detector FDOOT241-A3 S54310-F10-A1 Multi-sensor fire detector Sinteso (A+) 0.106 FDOOT241-A4 S54310-F9-A1 Multi-sensor fire detector Sinteso (SIGMA) 0.106 Multi-sensor fire detector Sinteso FDOOT241-A5 S54310-F14-A1 0.106 (Interactive)
  • Page 13 Automatic fire detectors Multi-sensor fire detector FDOOT241-Ax, FDOOT241-8 Base adapter FDB251 Function: ● For adapting Interactive for Sinteso detector systems ● Can be set with jumper on replaced detector Base adapter FDB281 Function: ● For adapting MS8/PMT for Sinteso detector systems Base adapter FDB299 Function: ●...
  • Page 14 Automatic fire detectors Multi-sensor fire detector FDOOT241-Ax, FDOOT241-8 2.2.3 Technical data FDOOT241-A3, FDOOT241-A4, FDOOT241-A3 FDOOT241-A4 FDOOT241-A5 FDOOT241-A9 FDOOT241-8 FDOOT241-A5, FDOOT241-A9 FDOOT241-8 In the In the In the In the collective In the MS8 In FDnet AnalogPLUS SIGMALOOP Interactive detector detector system detector system detector system detector...
  • Page 15: Point Detector Fdoot241-9, Fdoot241-A, Fdo241, Fdt241

    ● Selectable detection behavior thanks to application-specific ASA parameter sets ● Multi-protocol: Collective / GMT (Cerberus / Siemens) / SynoLINE300, FDnet ● For early detection of flaming fires of solid and liquid substances as well as of smoldering fires ●...
  • Page 16 Automatic fire detectors Point detector FDOOT241-9, FDOOT241-A, FDO241, FDT241 Multi-sensor fire detector FDOOT241-A ● Point detector with additional heat sensors ● Optional detector dust cap to protect the point detector during the construction phase Function ● Functions according to the scattered light principle with two sensors: Optical forward and backward scattering ●...
  • Page 17 Automatic fire detectors Point detector FDOOT241-9, FDOOT241-A, FDO241, FDT241 Heat detector FDT241 ● Optional detector dust cap to protect the point detector during the construction phase Function ● Two heat sensors prevent the total failure of the thermal detection capacity of in the event of a fault affecting a sensor.
  • Page 18 Automatic fire detectors Point detector FDOOT241-9, FDOOT241-A, FDO241, FDT241 2.3.2.1 Accessories You will find more information about detector bases and accessories in document 007775. Addressable detector base FDB221 / FDB221-AA Function: ● Detector base with stilts for fire detectors with addressable signal processing ●...
  • Page 19 Automatic fire detectors Point detector FDOOT241-9, FDOOT241-A, FDO241, FDT241 Base attachment wet FDB295 ● Base attachment wet with additional integrated rubber seal for mounting in wet or humid environments ● For achieving a higher protection category ● For mounting in wet or humid environments ●...
  • Page 20 Automatic fire detectors Point detector FDOOT241-9, FDOOT241-A, FDO241, FDT241 2.3.3 Technical data FDOOT241-9 FDOOT241-A FDO241 FDT241 DC 12…33 V Operating voltage (modulated) 65…230 μA 180…230 μA 130…200 μA Operating current (quiescent) External alarm Without sounder base indicators (EAI) which can be With sounder connected base...
  • Page 21: Multi-Sensor Fire Detector Fdootc241

    Automatic fire detectors Multi-sensor fire detector FDOOTC241 2.4 Multi-sensor fire detector FDOOTC241 2.4.1 Use Alongside its fire detection functionality, the FDOOTC241 also has a CO detection functionality. Multi-sensor fire detector, neural ASA (S-LINE), FDOOTC241 Fire detection function: ● Functions according to the scattered light principle with two sensors, optical forward and backward scattering ●...
  • Page 22 Automatic fire detectors Multi-sensor fire detector FDOOTC241 2.4.2 Type Overview Type Designation Order number Weight [kg] FDOOTC241 Multi-sensor fire detector, neural ASA (S-LINE) S54311-F1-A1 0.107 Accessories FDB221 Detector base, addressable A5Q00001664 0.026 Detector base, addressable incl. 1 micro FDB221-AA A5Q00012741 0.029 terminal DBZ1190-AA FDB222...
  • Page 23: Detector Base And Base Attachment

    Detector base and base attachment Detector base FDB201, FDB202, FDB221, FDB222 3 Detector base and base attachment 3.1 Detector base FDB201, FDB202, FDB221, FDB222 3.1.1 Use Collective detector base FDB201 / FDB201-AA Function: ● Detector base with stilts for fire detectors with collective signal processing ●...
  • Page 24 Detector base and base attachment Detector base FDB201, FDB202, FDB221, FDB222 Flat, addressable detector base FDB222 Function: ● Flat detector base for fire detectors with addressable signal processing ● 'Orange' connection terminals, 0.2…1.5 mm conductor cross-section Use: ● For flush mounting; only for recess-mounted cable entry FDB2x1 / FDB2x1-AA ●...
  • Page 25 Detector base and base attachment Detector base FDB201, FDB202, FDB221, FDB222 Detector base FDB2xx / FDB2x1-AA Micro terminal DBZ1190-AA Connection terminal DBZ1190-AB Sealing element FDBZ295 Function: ● For improving the protection category. However, detectors can no longer be installed or removed using the detector exchanger. Note: Cannot be used in conjunction with designation plate FDBZ291! Designation plate FDBZ291 ●...
  • Page 26 Detector base and base attachment Detector base FDB201, FDB202, FDB221, FDB222 ● Base attachment humid FDB293 ● Base attachment wet FDB295 Detector base FDB2x1 / FDB2x1-AA, FDB2x2 Detector heating unit FDBH291 Connection terminal DBZ1190-AB Micro terminal DBZ1190-AA Detector locking device FDBZ293 ●...
  • Page 27 Detector base and base attachment Detector base FDB201, FDB202, FDB221, FDB222 Set screw Allen key Base attachment FDB291 Function: ● For routing surface-mounted cables larger than Ø 6 mm ● Detector base is secured with a snap fastener 008164_y_en_-- 27 | 152...
  • Page 28 Detector base and base attachment Detector base FDB201, FDB202, FDB221, FDB222 ● Base height: 25 mm ● When using the point detector: 60 mm Opening for cable entry Mounting slits Base attachment humid FDB293 ● For achieving a higher protection category ●...
  • Page 29 Detector base and base attachment Detector base FDB201, FDB202, FDB221, FDB222 ● SPF3600 detector base (SIGMALOOP) ● DB1131A detector base (AnalogPLUS) ● Base height: 29.5 mm ● When using the point detector: 74.5 mm Adapter incl. detector base, 'orange' connection terminals Base adapter FDB251 Function: ●...
  • Page 30 Detector base and base attachment Detector base FDB201, FDB202, FDB221, FDB222 DB1151A detector base (interactive) ● Base height: 29.5 mm ● When using the point detector: 74.5 mm Adapter incl. detector base, 'orange' connection terminals Base adapter FDB281 Function: ● For adapting MS8/PMT for Sinteso detector systems Detector base Z84 (MS8/PMT) ●...
  • Page 31 Detector base and base attachment Detector base FDB201, FDB202, FDB221, FDB222 Base adapter FDB299 Function: ● For adapting AlgoRex (collective) and SIGMACON for Sinteso detector systems ● DB1101A detector base (collective, AlgoRex) ● SPF600 detector base (SIGMACON) ● Base height: 29.5 mm ●...
  • Page 32 Detector base and base attachment Detector base FDB201, FDB202, FDB221, FDB222 Detector base Base adapter FDB241, FDB251 or FDB299 FDUD290 removal tool for adapter ● FDUD291 detector exchanger ● FDUD292 Detector exchanger and tester ● FDUD293 intelligent detector tester Protective cage DBZ1194 ●...
  • Page 33 Detector base and base attachment Detector base FDB201, FDB202, FDB221, FDB222 158.5 ● FDB293 base attachment humid ● FDB295 base attachment wet Screw Protective cage DBZ1194 EMC-protective cage FDBZ294 ● To protect the point detector from strong electromagnetic fields ● Can only be mounted in combination with the base attachment humid FDB293 or base attachment wet FDB295 ●...
  • Page 34 Detector base and base attachment Detector base FDB201, FDB202, FDB221, FDB222 Detector dust cap FDZ291 ● To cover detectors as protection against dust during the construction phase Point detector Detector dust cap FDZ291 34 | 152 008164_y_en_--...
  • Page 35 Detector base and base attachment Detector base FDB201, FDB202, FDB221, FDB222 3.1.2 Type Overview Type Designation Order no. Weight [kg] FDB201 Detector base collective A5Q00003814 0.026 FDB202 Collective detector base, flat S54319-F3-A1 0.025 Collective detector base incl. 1 micro FDB201-AA A5Q00012742 0.029 terminal DBZ1190-AA...
  • Page 36 Detector base and base attachment Detector base FDB201, FDB202, FDB221, FDB222 3.1.3 Technical data Detector base Conductor cross-sections: ● Connection terminals in the base 0.2…1.5 mm ● Connection terminals DBZ1190-AB 0.5…2.5 mm ● Micro terminals DBZ1190-AA 0.28…0.5 mm Operating temperature, storage temperature, air humidity, You will find information in the following protection category (IEC 60529) documents:...
  • Page 37: Colored Detector And Base

    Colored detector and base Type Overview 4 Colored detector and base 4.1 Type Overview NOTICE You will find information on the technical data for the devices in the corresponding datasheets. The devices in the colors 'Jet black' and 'White aluminium' are always supplied with a glossy finish and can be ordered directly using the order number.
  • Page 38 Colored detector and base Type Overview Device Short name Designation Order no. FDOOT271 radio fire detector (colored) S54313-F1-A2 FDCW241 radio gateway (colored) S54370-F11-A3 FDB202 Flat, collective detector base (colored) A5Q00016446 FDB222 Flat, addressable detector base (colored) A5Q00016447 FDB222 Flat, addressable detector base S54319-F33-A3 (Jet black, RAL9005) FDB222...
  • Page 39 Colored detector and base Type Overview Ordering information The devices are ordered in SAP via EDI. For an electronic order, the color code can be entered as free text with COI1. Ordering via SAP: ● Enter the required color number on the 'Texts' tab, in the 'Header note 1' text box (e.g., RAL 8004) –...
  • Page 40: Manual Call Point

    Manual call point Manual call point FDM221/223/224 5 Manual call point 5.1 Manual call point FDM221/223/224 5.1.1 Functions Manual call point FDM221 ● Direct alarm activation by pushing in the glass insert ● Manual call point reset by replacing the glass insert ●...
  • Page 41 Manual call point Manual call point FDM221/223/224 Manual call point FDM223 ● Indirect alarm activation by pushing in the glass insert and pressing the alarm button ● Open the door of the detector with the key to replace the glass insert. Reset the alarm button before closing the door.
  • Page 42 Manual call point Manual call point FDM221/223/224 5.1.2 Type Overview Manual call point FDM221 Type Designation Order number Weight [kg] FDMH291-R Red housing with key A5Q00002217 0.099 FDMH291-Y Yellow housing with key A5Q00004979 0.099 FDMH291-B Blue housing with key A5Q00004980 0.099 FDMH291-G Green housing with key...
  • Page 43 Manual call point Manual call point FDM221/223/224 Accessories for manual call point FDM223/FDM224 Type Designation Order number Weight [kg] DMZ1197-AC Protective cover BPZ:5223550001 0.012 DMZ1197-AD Sealing for wet areas BPZ:5470680001 0.022 Spare parts for manual call point FDM223/FDM224 Type Designation Order number Weight [kg] DMZ1196-AC...
  • Page 44: Manual Call Point Fdm223H/224H 'Heavy Duty

    Manual call point Manual call point FDM223H/224H 'Heavy Duty' 5.2 Manual call point FDM223H/224H 'Heavy Duty' 5.2.1 Functions Manual call point FDM223H ● Indirect alarm activation by pushing in the glass insert and pressing the alarm button ● Open the door of the detector with the key to replace the glass insert. Reset the alarm button before closing the door.
  • Page 45 Manual call point Manual call point FDM223H/224H 'Heavy Duty' Manual call point FDM224H ● Direct alarm activation by pushing in the glass insert ● Open the door of the detector with the key to replace the glass insert. The alarm button is reset when the door is closed. ●...
  • Page 46 Manual call point Manual call point FDM223H/224H 'Heavy Duty' 5.2.3 Technical data FDM223H / FDM224H Operating voltage DC 12…33 V Operating current (quiescent) 200 µA Ext. alarm indicator (AI) Operating temperature -25…+70°C Storage temperature -30…+75°C Air humidity (no moisture condensation) ≤95 % rel.
  • Page 47: Manual Call Point Fdm225/226 (Direct Alarm Activation)

    Manual call point Manual call point FDM225/226 (direct alarm activation) 5.3 Manual call point FDM225/226 (direct alarm activation) 5.3.1 Use ● For the immediate manual activation of a fire alarm ● FDM225-xx: Suitable for indoor applications ● FDM226-xx: Suitable for indoor and outdoor applications Types of mounting The manual call points are suitable for surface and recessed mounting (FDM225- xx) or for surface mounting (FDM226-xx) in easily accessible locations.
  • Page 48 Manual call point Manual call point FDM225/226 (direct alarm activation) FDMH295-R FDMH295-S FDM225 FDM225 FDM226 FDM225-xx FDM225-xx with back box FDMH295-x FDM226-xx ● If you use back box FDMH295-R with the FDM225-xx, a hole with Ø ≤20 mm must be drilled in the back box for the surface-mounted cable entry. Use metal cable gland M20 x 1.5 with metal counter nut M20 x 1.5 (accessories).
  • Page 49 Manual call point Manual call point FDM225/226 (direct alarm activation) Function of manual call points FDM225-RG and FDM226-RG ● Direct alarm activation by pushing in the glass insert ● Manual call point reset by replacing the glass insert ● Protective cover FDMC295 (accessory) protects the manual call point against the glass being broken and the alarm activated accidentally Figure 3: Installing the protective cover FDMC295 1 Manual call point FDM225...
  • Page 50 Manual call point Manual call point FDM225/226 (direct alarm activation) 5.3.2 Type Overview Type Designation Order no. Weight [kg] FDM225-RG Manual call point with glass insert A5Q00013434 0.102 FDM225-RP Manual call point with plastic element A5Q00012020 0.100 FDM225-RG (F) Manual call point with glass insert for A5Q00020274 0.102 France...
  • Page 51 Manual call point Manual call point FDM225/226 (direct alarm activation) 5.3.3 Technical data FDnet operating voltage DC 12…33 V Operating current (quiescent) 180 µA Operating temperature -25…+70°C Storage temperature -30…+75°C Air humidity ≤95 % rel. Communication protocol FDnet Connection terminals 0.28…1.5 mm Color ~RAL 3000, flame red...
  • Page 52: Manual Call Point Fdm231 (Direct Alarm Activation)

    Manual call point Manual call point FDM231 (direct alarm activation) 5.4 Manual call point FDM231 (direct alarm activation) 5.4.1 Use ● For indoor applications only ● For surface mounting ● For surface-mounted and recess-mounted cable entries in easily accessible locations 5.4.2 Type Overview Type Designation...
  • Page 53 Manual call point Manual call point FDM231 (direct alarm activation) 5.4.3 Technical data FDM231-RP FDM231-RP(F) Operating voltage DC 12…33 V Operating current (quiescent) Max. 180 µA Ext. alarm indicator (AI) Connection terminals 0.28…1.5 mm Operating temperature -25…+65 °C Storage temperature -30…+65 °C Air humidity, non-condensing ≤95 % rel.
  • Page 54: Manual Call Point Fdm233/234 (Direct/Indirect Alarm Activation)

    Manual call point Manual call point FDM233/234 (direct/indirect alarm activation) 5.5 Manual call point FDM233/234 (direct/indirect alarm activation) 5.5.1 Use ● For indoor and outdoor applications ● Also for humid, wet, and dusty areas ● For surface-mounted and recess-mounted feed lines in easily accessible locations 5.5.2 Type Overview FDM233...
  • Page 55 Manual call point Manual call point FDM233/234 (direct/indirect alarm activation) 5.5.3 Technical data FDM233 FDM234 Operating voltage DC 12…33 V Operating current (quiescent) Max. 200 µA Ext. alarm indicator (AI) Connection terminals 0.28…1.5 mm Operating temperature -25…+70 °C Storage temperature -30…+75 °C Air humidity ≤95 % rel.
  • Page 56: Manual Call Point Fdm243H 'Heavy Duty' (Indirect Alarm Activation)

    Manual call point Manual call point FDM243H 'Heavy Duty' (indirect alarm activation) 5.6 Manual call point FDM243H 'Heavy Duty' (indirect alarm activation) 5.6.1 Use ● For indoor and outdoor applications ● Also for humid, wet, and dusty areas ● For surface-mounted feed lines in easily accessible locations only ●...
  • Page 57 Manual call point Manual call point FDM243H 'Heavy Duty' (indirect alarm activation) 5.6.3 Technical data FDM243H Operating voltage DC 12…33 V Operating current (quiescent) Max. 200 µA Ext. alarm indicator (AI) Connection terminals 0.2…2.5 mm Operating temperature -35…+70 °C Storage temperature -40…+70 °C Air humidity, non-condensing ≤95 % rel.
  • Page 58: Alarm Indicators

    Alarm indicators Alarm indicators FDAI91, FDAI92, FDAI93 6 Alarm indicators 6.1 Alarm indicators FDAI91, FDAI92, FDAI93 6.1.1 Use Alarm indicators FDAI91, FDAI92 ● Alarm indicator is mounted on a door frame or wall. Alarm indicator FDAI93 ● Alarm indicator is mounted in a door frame, switchboard, false ceiling or special housing.
  • Page 59 Alarm indicators Alarm indicators FDAI91, FDAI92, FDAI93 6.1.1.2 Accessories for FDAI93 Indicator housing DJZ1193 ● For mounting in wet rooms ● Includes a hole for installing alarm indicator FDAI93 Housing DCA1191 ● For mounting in wet rooms ● Installation of a maximum of four alarm indicators FDAI93 ●...
  • Page 60 Alarm indicators Alarm indicators FDAI91, FDAI92, FDAI93 6.1.3 Technical data FDAI91 / FDAI92 FDAI93 Operating voltage DC 5…8 V DC 6…8 V Operating current (quiescent) Max. 35 mA Max. 35 mA Connection terminals Max. 1.5 mm Max. 1.5 mm Operating temperature -25…+80 °C -25…+80 °C Storage temperature...
  • Page 61: Addressable Alarm Indicator Fdcai221

    Alarm indicators Addressable alarm indicator FDCAI221 6.2 Addressable alarm indicator FDCAI221 6.2.1 Use FDCAI221 addressable alarm indicator ● Optical repeat signal for fire detectors on the same detector line: Enables the rapid identification of alarm-transmitting detectors which are difficult to access or are not immediately/easily visible.
  • Page 62 Alarm indicators Addressable alarm indicator FDCAI221 6.2.2 Type Overview Type Designation Order number Weight [kg] FDCAI221 Addressable alarm indicator S54370-F10-A1 0.049 Accessories AI330 Adapter frame BPZ:3169430001 0.018 DBZ1190-AA 0.5 mm , 4-pin micro terminal BPZ:4677080001 0.001 DBZ1190-AB 2.5 mm , 3-pin connection terminal BPZ:4942340001 0.001 6.2.3 Technical data...
  • Page 63: Alarm Devices In The Fdnet

    Alarm devices in the FDnet Sounder base FDSB29x 7 Alarm devices in the FDnet 7.1 Sounder base FDSB29x 7.1.1 Use Sounder base FDSB291, FDSB292 applications ● Hotel rooms ● Sick rooms ● Care homes, living rooms, and lounges Alarm sounders FDS221-R, FDS221-W applications ●...
  • Page 64 Alarm devices in the FDnet Sounder base FDSB29x Alarm sounder accessories Accessories FDB221 Detector base, A5Q00001664 0.026 addressable Flat, addressable FDB222 S54319-F1-A1 0.024 detector base FDBZ295 Sealing element S54319-F10-A1 0.062 FDB291 Base attachment A5Q00001603 0.035 FDBZ291 Designation plate A5Q00002621 0.002 FDB293 Base attachment humid A5Q00003945...
  • Page 65 Alarm devices in the FDnet Sounder base FDSB29x Alarm sounder accessories Addressable detector base FDB221 / FDB221-AA Function: ● Detector base with stilts for fire detectors with addressable signal processing ● 'Orange' connection terminals, 0.2…1.5 mm conductor cross-section ● FDB221-AA also contains micro terminal DBZ1190-AA Use: ●...
  • Page 66 Alarm devices in the FDnet Sounder base FDSB29x Base attachment humid FDB293 ● For achieving a higher protection category ● For mounting in wet or humid environments ● Required when using detector heating unit FDBH291 ● Required when using protective cage DBZ1194 or EMC-protective cage FDBZ294 ●...
  • Page 67 Alarm devices in the FDnet Sounder base FDSB29x 7.1.3 Technical data Supply FDS221-R, FDS221-W FDSB291 FDSB292 Operating voltage DC 12...33 V DC 12...33 V Operating current (quiescent) Max. 250 µA Max. 150 µA ● Sound activated 3.5 mA 1.2 mA Sounds 2 alarm levels 2 alarm levels...
  • Page 68: Sounder Beacon Fds224, Fds225, Fds226, Fds227

    Alarm devices in the FDnet Sounder beacon FDS224, FDS225, FDS226, FDS227 7.2 Sounder beacon FDS224, FDS225, FDS226, FDS227 7.2.1 Use ● Public buildings ● Office buildings ● Hotels ● Schools and kindergartens 7.2.2 Type Overview Type Designation Order number Weight [kg] FDS224-R Sounder S54364-F1-A1...
  • Page 69 Alarm devices in the FDnet Sounder beacon FDS224, FDS225, FDS226, FDS227 7.2.2.1 Accessories Type Designation Order number Weight [kg] FDB226-R Base (wall mounting) S54364-B1-A1 0.045 FDB226-W Base (wall mounting) S54364-B2-A1 0.045 FDB227-R Base deep (wall mounting) S54364-B3-A1 0.073 FDB227-W Base deep (wall mounting) S54364-B4-A1 0.073 –...
  • Page 70 Alarm devices in the FDnet Sounder beacon FDS224, FDS225, FDS226, FDS227 7.2.3 Technical data Supply Operating voltage ● DC 12...33 V for FDS224-x, FDS225-x ● DC 16...33 V for FDS226-xx, FDS227-xx, FDS227-xx-C Operating current (quiescent) ● 250 µA for FDS224-x, FDS225-x ●...
  • Page 71 Alarm devices in the FDnet Sounder beacon FDS224, FDS225, FDS226, FDS227 Functional data Tones ● 16 tones (including school bell) ● 2 alarm levels ('Warning' and 'Evacuation') ● 3 sound levels (maximum / medium / minimum) Voice messages ● 5 standard voice messages in 15 languages ●...
  • Page 72 Alarm devices in the FDnet Sounder beacon FDS224, FDS225, FDS226, FDS227 Standards, directives, and approvals Standards EN 54-3 type B, EN 54-17 EN 54-23, type B Approvals: ● FDS224-x G219001 FDS225-x G219002 FDS226-xW G219003 FDS227-xW G219004 FDS226-xR G219003 FDS227-xR G219004 ●...
  • Page 73: Sounder Bases Fdsb226, Fdsb227

    Alarm devices in the FDnet Sounder bases FDSB226, FDSB227 7.3 Sounder bases FDSB226, FDSB227 7.3.1 Use ● Public buildings ● Office buildings ● Hotels ● Schools and kindergartens 7.3.2 Type Overview Type Designation Order number Weight [kg] FDSB226-WR Sounder beacon base S54364-F13-A1 0.253 FDSB226-WW...
  • Page 74 Alarm devices in the FDnet Sounder bases FDSB226, FDSB227 7.3.2.1 Accessories Type Designation Order number Weight [kg] FDB228 Base (ceiling mounting) S54364-B5-A1 0.067 FDB229 Base deep (ceiling mounting) S54364-B6-A1 0.092 FDBZ221 Ring attachment S54364-B7-A1 0.015 FDBZ298 Blanking plate S54364-B8-A1 0.030 FDBZ291 Designation plate A5Q00002621...
  • Page 75 Alarm devices in the FDnet Sounder bases FDSB226, FDSB227 7.3.3 Technical data Supply Operating voltage DC 16...33 V Operating current (quiescent) 400 µA ● Tone/voice activated Max. 5 mA (140 mW) ● Beacon activated LED white High (O-4-15): 26 mA (416 mW) Medium (C-3-12): 17 mA (272 mW) Low (O-2.5-6.5): 9 mA (144 mW) Indicator: 3 mA (48 mW)
  • Page 76 Alarm devices in the FDnet Sounder bases FDSB226, FDSB227 Functional data Tones ● 16 tones (including school bell) ● 2 events ('Warning' and 'Evacuation') ● 3 sound levels (maximum / medium / minimum) Voice messages ● 5 standard voice messages in 15 languages ●...
  • Page 77 Alarm devices in the FDnet Sounder bases FDSB226, FDSB227 Standards, directives, and approvals Standards EN 54-3 type A, EN 54-17 EN 54-23 type A Approvals: ● FDSB226-Wx G219017 FDSB227-Wx, FDSB227-Wx-C G219018 ● LPCB Pending 008164_y_en_-- 77 | 152...
  • Page 78: Line Separator

    Line separator Line separator FDCL221 8 Line separator 8.1 Line separator FDCL221 8.1.1 Functions ● Disconnects the affected bus area in the event of a short-circuit in the FDnet so that the area unaffected by the short-circuit continues to function. ●...
  • Page 79 Line separator Line separator FDCL221 8.1.2 Type Overview Type Designation Order number Weight [kg] FDCL221 Input module incl. 8 resistors, A5Q00004011 0.038 2 mounting feet Accessories for the line separator FDCL221 Type Designation Order number Weight [kg] TS35 (L = 122 mm) U-rail TS35/7.5/122 BPZ:5644780001 0.041...
  • Page 80: Multi Line Separator Module Fdcl221-M

    Line separator Multi line separator module FDCL221-M 8.2 Multi line separator module FDCL221-M 8.2.1 Functions FDCL221-M multi line separator module ● Nine electronic switches (line separators) ● Connections for the detector lines (FDnet) ● Connections for the stub lines (T-branches) ●...
  • Page 81 Line separator Multi line separator module FDCL221-M Screw terminal for FDnet loop 1 Jumpers Screw terminal for FDnet loop 2 FDnet loop 2 FDnet stub lines FDnet loop 1 Connector (20-pin) for sub-stub lines 8.2.2 Type Overview Type Designation Order number Weight [kg] FDCL221-M Multi line separator module...
  • Page 82 Line separator Multi line separator module FDCL221-M Replacement material for the multi line separator module FDCL221-M Type Designation Order number Weight [kg] FDCM291 Mounting foot A5Q00003855 0.001 8.2.3 Technical data FDCL221-M Operating voltage DC 12…33 V Operating current (quiescent) ● 1-loop operation 2.25 mA (9x 250 µA) ●...
  • Page 83: Input/Output Modules

    Input/output modules FDCI221, FDCIO221 9 Input/output modules 9.1 FDCI221, FDCIO221 9.1.1 Functions FDCI221 input module ● Input for potential-free detector contact ● Monitoring the input line for open line and short-circuit with terminating resistors ● The input for status or alarm messages can be configured using the fire control panel.
  • Page 84 Input/output modules FDCI221, FDCIO221 FDCIO221 input/output module ● Input for potential-free detector contact ● Monitoring the input line for open line and short-circuit with terminating resistors ● The input for status or alarm messages can be configured using the fire control panel.
  • Page 85 Input/output modules FDCI221, FDCIO221 9.1.2 Type Overview Type Designation Order number Weight [kg] FDCI221 Input module incl. 2 resistors, S54312-F1-A1 0.060 2 mounting feet Input/output module incl. 2 resistors, FDCIO221 S54312-F2-A1 0.066 2 mounting feet Accessories for input module FDCI221, input/output module FDCIO221 Type Designation...
  • Page 86 Input/output modules FDCI221, FDCIO221 9.1.3 Technical data FDCI221 FDCIO221 Operating voltage DC 12…33 V Operating current (quiescent) Max. 0.3 mA Max. 0.4 mA AC 22 V, 2 A, max. 44 VA Relay output (ohmic) ‑ DC 30 V, 2 A, max. 60 W Line resistance (input) Max.
  • Page 87: Fdci222, Fdcio222, Fdcio224

    Input/output modules FDCI222, FDCIO222, FDCIO224 9.2 FDCI222, FDCIO222, FDCIO224 9.2.1 Functions FDCI222 input module ● Four inputs for potential-free detector contacts ● Monitoring the input lines for open line and short-circuit with terminating resistors ● Inputs can be configured independently for status or alarm messages using the fire control panel Fields of application: To activate four independent, potential-free, normally open or normally closed...
  • Page 88 Input/output modules FDCI222, FDCIO222, FDCIO224 FDCIO222, FDCIO224 input/output modules ● Four inputs for potential-free detector contacts ● Monitoring the input lines for open line and short-circuit with terminating resistors ● Inputs can be configured independently for status or alarm messages using the fire control panel ●...
  • Page 89 Input/output modules FDCI222, FDCIO222, FDCIO224 9.2.2 Type Overview Type Designation Order no. Weight [kg] FDCI222 Input module incl. 8 resistors, A5Q00001984 0.098 2 mounting feet Input/output module incl. 8 resistors, FDCIO222 A5Q00002369 0.127 2 mounting feet Input/output module incl. 8 resistors, FDCIO224 A5Q00018689 0.127...
  • Page 90 Input/output modules FDCI222, FDCIO222, FDCIO224 9.2.3 Technical data FDCI222 FDCIO222 / FDCIO224 Operating voltage DC 12…33 V Operating current (quiescent) Max. 0.35 mA Max. 0.75 mA Relay output — AC 250 V / 4 A, max. 1000 VA DC 30 V / 4 A, max. 120 W Operating temperature -25…+60 °C Storage temperature...
  • Page 91: Fdci223

    Input/output modules FDCI223 9.3 FDCI223 9.3.1 Use For connecting to collective or conventional fire detectors (with safety barrier SB3 for areas at risk of explosion). 1 Connections for the FDnet detector 4 Detector line input connections line Max. 32 detectors per line 2 FDnet detector line 5 Contact input 3 External supply DC 24 V...
  • Page 92 Input/output modules FDCI223 NOTICE Country-specific safety regulations Failure to observe country-specific safety regulations can cause injury to persons and damage to property. ● Observe country-specific regulations and comply with the corresponding safety directives. 9.3.2 Type Overview Type Designation Order no. Weight [kg] FDCI223 Zone module, external powered...
  • Page 93 Input/output modules FDCI223 9.3.3 Technical data FDCI223 FDnet operating voltage DC 12…33 V External power supply Tested to EN 54-4 ● Operating voltage DC 18...32 V Collective detector line ● Collective line code (KLK) ● End-of-line (EOL) 20 V voltage reference diode or EOL22 (Ex) Operating temperature -20...+55 °C Storage temperature...
  • Page 94: Fdcio223

    Input/output modules FDCIO223 9.4 FDCIO223 9.4.1 Use The input/output module (transponder) FDCIO223 has the following application areas: ● Connection of collective fire detectors. If safety barrier SB3 is used, intrinsically safe collective fire detectors can be connected in potentially explosive atmospheres ●...
  • Page 95 Input/output modules FDCIO223 FDnet/C-NET FDnet/C-NET 1 Connections for input/output, 4 External supply DC 24 V collective/conventional detector line (2x) 2 Connection for the FDnet detector 5 Contact input line 3 Connection for the detector 6 Jumper for internal fuses exchanger and tester (MC link) max.
  • Page 96 Input/output modules FDCIO223 9.4.2 Type Overview Type Designation Order no. Weight [kg] FDCIO223 (ES ≥50) Input/output module (transponder) S24218-B102-A1 0.126 incl. 2 20 V voltage reference diodes, 4 sets of terminating resistors, 2 mounting feet, 2 jumpers Accessories for the input/output module (transponder) FDCIO223 Type Designation Order no.
  • Page 97 Input/output modules FDCIO223 General (irrespective of the device) Storage temperature -30…+65 °C Air humidity ≤85 % rel. (no freezing or condensing at low temperature) Communication protocol FDnet Connections: ● Pluggable connection terminals 0.2…1.5 mm² (with 2.5 mm² connection terminal DBZ1190-AB) Plug-type connection, 3.5 mm jack socket ●...
  • Page 98: Special Detectors

    Special detectors Linear smoke detector FDL241-9 10 Special detectors 10.1 Linear smoke detector FDL241-9 10.1.1 Use ● Buildings with historically valuable ceilings ● Atriums, detection on multiple levels ● Large rooms and high halls ● Churches ● Long corridors, cable and energy ducts with a room height of more than 3 m ●...
  • Page 99 Special detectors Linear smoke detector FDL241-9 Type Designation Order number Weight [kg] DLR1193 Reflector for short distance (foil) BPZ:4787840001 0.025 FDLU291 Adjustment kit for linear smoke A5Q00004905 0.840 detector Detector tester for linear smoke RE10 BPZ:3685190001 0.345 detectors TF04 Alarm test filter (absorption 77 %) BPZ:4931090001 0.005 10.1.3 Technical data...
  • Page 100: Flame Detector Fdf241-9

    Special detectors Flame detector FDF241-9 10.2 Flame detector FDF241-9 10.2.1 Functions The flame detector measures infrared radiation and can therefore detect liquid and gas fires without smoke and organic material fires with smoke. It has three sensors technology with ASA and can distinguish between deceptive phenomena and real fires.
  • Page 101 Special detectors Flame detector FDF241-9 Fields of application The flame detector is suited to use in environments with deceptive phenomena, such as solar radiation or hot motors. ● Large industrial storage rooms ● Power plants ● Chemical production facilities ● Transformer stations ●...
  • Page 102 Special detectors Flame detector FDF241-9 Rain hood DFZ1190 ● Rain hood made of stainless steel ● For protecting the flame detector during outdoor applications Test lamp LE3 ● For testing the function of all flame detectors at distances up to 10 m 10.2.2 Type Overview Flame detector FDF241-9 Type...
  • Page 103 Special detectors Flame detector FDF241-9 10.2.3 Technical data Flame detector FDF241-9 Operating voltage (quiet) addressed / collective DC 12…33 V / DC 14…28 V Operating current (quiet) addressed / collective 0.7 mA / 0.5 mA External alarm indicator (AI) can be connected and configured externally Operating temperature -35…+70°C Storage temperature...
  • Page 104: Swing Radio Fire Detection System

    Special detectors SWING radio fire detection system 10.3 SWING radio fire detection system ● Radio gateway FDCW241 ● Radio fire detector FDOOT271 ● Radio manual call point FDM273, FDM275 10.3.1 Use The radio fire detection system is primarily used in places where there are restrictions on the laying of cables and pipelines for reasons of building technology, aesthetics, or for the protection of landmarked buildings.
  • Page 105 Housing base for radio gateway S54370-N45-A1 0.054 FDCH272 Housing cover for radio gateway S54370-N46-A1 0.042 1) You can download the software from the Siemens Intranet. Radio fire detector FDOOT271 and detector base FDB271 Type Designation Order no. Weight [kg] FDOOT271...
  • Page 106 Special detectors SWING radio fire detection system Accessories and spare parts for radio manual call points FDM273 Type Designation Order no. Weight [kg] DMZ1197-AC Protective cover BPZ:5223550001 0.012 DMZ1196-AC Glass insert BPZ:4942050001 0.011 DMZ1195 BPZ:4851910001 0.001 Radio manual call point FDM275 Type Designation Order no.
  • Page 107 Special detectors SWING radio fire detection system Description of the devices Radio gateway FDCW241 ● The radio gateway FDCW241 has an integrated line separator. The gateway has a complete send and receive unit and a microcontroller control unit for all functions that are required for radio transmission.
  • Page 108 Special detectors SWING radio fire detection system Neural radio fire detector FDOOT271 ● Consistent response to a wide range of different fires ● Dynamic analysis of the sensor signal in the detector itself ● Built-in diagnosis algorithms with automatic selftest ●...
  • Page 109 Special detectors SWING radio fire detection system Radio manual call point FDM273 ● Radio manual call point can be mounted anywhere in a radio cell ● The radio manual call point consists of a housing and a switching unit including radio electronics and dual-band antenna ●...
  • Page 110 Special detectors SWING radio fire detection system Battery pack BAT3.6-10 ● For supplying radio devices and the radio gateway with power FDCW241. ● Lithium batteries BAT3.6-10 LI-SOCI2 battery pack 3.6 V, 10 Ah. ● Batteries with cable and connector with protection against polarity reversal ●...
  • Page 111 Special detectors SWING radio fire detection system FDCW241 FDOOT271 Communication protocol FDnet – (detector line) Electromagnetic 100 kHz…2.5 GHz: 30 V/m 100 kHz…2.5 GHz: 30 V/m compatibility Permissible wind speed – Max. 5 m/s Compatible conductor 0.2…1.5 mm – cross-sections at the connection terminals Battery service life >6 years...
  • Page 112: Air Sampling Smoke Detection Kit Fdbz290

    Special detectors Air sampling smoke detection kit FDBZ290 10.4 Air sampling smoke detection kit FDBZ290 10.4.1 Functions ● The air sampling smoke detection kit is a passive monitoring system without a fan of its own. It uses the pressure differences within the ventilation system to continuously take air samples from the ventilation duct via the air flow tube and supply them to the air sampling smoke detection kit.
  • Page 113 Special detectors Air sampling smoke detection kit FDBZ290 10.4.2 Type overview Type Designation Order number Weight [kg] FDBZ290 Air sampling smoke detection kit S54319-S32-A1 0.664 Accessories for air sampling smoke detection kit FDBZ290 Type Designation Order number Weight [kg] DB110 Detector base (collective) S54319-F5-A1 0.052...
  • Page 114: Aspirating Smoke Detector Fda221, Fda241

    Special detectors Aspirating smoke detector FDA221, FDA241 10.5 Aspirating smoke detector FDA221, FDA241 10.5.1 Use Aspirating smoke detectors are used for early detection of smoke-generating fires in rooms and equipment. They are especially suited to applications in which point detectors are pushed to their limits, cannot be used or can only be used with restrictions.
  • Page 115 Special detectors Aspirating smoke detector FDA221, FDA241 Applications with a filter box ● Rooms with polluted air, in which the pollution has impaired the performance of optical point detectors ● Mounting lines ● Recycling facilities ● Cement factories ● Mining industry ●...
  • Page 116 Monitoring area (dependent on local Up to 800 m² Up to 500 m² provisions and standards) System compatibility Compatible with all Siemens FC20/FC720 (FS20/FS720 systems) Relay alarm outputs Can be selected with/without lock Nominal current 2.0 A at DC 30 V. Contact: NO/NC...
  • Page 117 Special detectors Aspirating smoke detector FDA221, FDA241 FDA241 FDA221 Indication ● 4x alarm status indicators (FDA241) ● 3x alarm status indicators (FDA221) ● Faults ● Blowing out (FDA241) ● Dust (FDA241) ● Smoke density and flow indicator Service area ● LED 'Status OK' ●...
  • Page 118: Multi-Sensor Fire Detector Fdoot241-A9-Ex

    Can be set as a multi-sensor smoke detector, smoke detector, or heat detector by the software ● Selectable detection behavior thanks to application-specific ASA parameter sets ● Multi-protocol: Collective / GMT (Cerberus / Siemens), SynoLINE300 and FDnet-Ex Observe national guidelines and regulations. ● Fields of application: –...
  • Page 119 Special detectors Multi-sensor fire detector FDOOT241-A9-Ex 10.6.2 Type Overview Type Designation Order number Weight [kg] FDOOT241-A9-Ex Multi-sensor fire detector (Ex) S54329-F7-A1 0.106 Accessories for the multi-sensor fire detector (Ex) FDOOT241-A9-Ex Type Designation Order number Weight [kg] DBZ1190-AB Connection terminal BPZ:4942340001 0.001 FDB201 Detector base collective...
  • Page 120 Special detectors Multi-sensor fire detector FDOOT241-A9-Ex FDOOT241-A9-Ex Standards for explosion-hazard areas IEC 60079-0, IEC 60079-11 Ex approvals ● EC-type examination certificate BVS 12 ATEX E 087 X ● IECEx IECEx BVS 12.0076 X Approvals ● G213106 ● DNV GL (marine) MEDB00003UK System compatibility ●...
  • Page 121: Manual Call Point Fdm223-Ex

    Special detectors Manual call point FDM223-Ex 10.7 Manual call point FDM223-Ex Device for zone 0, 1 and 2 areas at risk of explosion 10.7.1 Functions 1 Manual call point FDM223-Ex 2 Metal cable gland 3 Cable gripper (2-hole) 4 Protective cover DMZ1197-AC ●...
  • Page 122 Special detectors Manual call point FDM223-Ex Observe national guidelines and regulations. 10.7.2 Type Overview Type Designation Order number Weight [kg] FDM223-Ex Manual call point S54329-F5-A1 0.356 Accessories for FDM223-Ex Type Designation Order number Weight [kg] DMZ1197-AC Protective cover BPZ:5223550001 0.012 –...
  • Page 123 Special detectors Manual call point FDM223-Ex 10.7.3 Technical data FDM223-Ex Operating voltage DC 13…28 V Operating current (quiescent) 200 μA Operating temperature -25…+70 °C Storage temperature -35…+75 °C Air humidity ≤95 % rel. Communication protocol FDnet-Ex Conductor cross section 1…1.5 mm Color ~RAL 3000 flame red Protection category (IEC/EN 60529)
  • Page 124 Special detectors Manual call point FDM223-Ex Ex-related connection 28 V data, intrinsically safe 92 mA 650 mW Negligible 0,2 nF Line to external alarm 14.2 V indicator 480 mA 195 mW 100 µH 38 nF Only for connecting passive, external alarm indicators with negligibly low inductance and capacitance levels.
  • Page 125: Infrared Flame Detector Df1101-Ex

    Special detectors Infrared flame detector DF1101-Ex 10.8 Infrared flame detector DF1101-Ex Device for zone 0, 1 and 2 areas at risk of explosion 10.8.1 Use ● Chemical production facilities, warehouses for chemicals ● Oil refineries ● Gas depots and pump stations ●...
  • Page 126 Special detectors Infrared flame detector DF1101-Ex 10.8.3 Technical data DF1101-Ex Operating voltage DC 16…28 V Operating current (quiescent) 0.5 mA Ext. alarm indicator (AI) Connection factor KMK Connection terminals 0.2…2.5 mm Operating temperature -35…+70°C Storage temperature -40…+75 °C Air humidity ≤95 % rel.
  • Page 127: Line Adapter (Ex) Fdcl221-Ex

    Special detectors Line adapter (Ex) FDCL221-Ex 10.9 Line adapter (Ex) FDCL221-Ex Device for zone 0, 1 and 2 areas at risk of explosion 10.9.1 Functions ● The line adapter (Ex) is used for electrical isolation purposes and for limiting the electrical energy between non-intrinsically safe and intrinsically safe circuits.
  • Page 128 Special detectors Line adapter (Ex) FDCL221-Ex Application in the C-NET Area not at risk Area at risk of explosion C-NET C-NET 1 Ex stub line 1 (C-NET-Ex) 2 Ex stub line 2 (C-NET-Ex) Application in the FDnet Area not at risk Area at risk of explosion FDnet FDnet...
  • Page 129 Special detectors Line adapter (Ex) FDCL221-Ex 10.9.2 Type Overview Type Designation Order number Weight [kg] FDCL221-Ex Line adapter (Ex) S54329-F4-A1 0.240 Accessories for the line adapter (Ex) FDCL221-Ex Type Designation Order number Weight [kg] TS35 (L = 122 mm) U-rail TS35/7.5/122 BPZ:5644780001 0.041 TS35 (L = 288 mm)
  • Page 130 Special detectors Line adapter (Ex) FDCL221-Ex FDCL221-Ex Standards for explosion-hazard areas EN 60079-0:2012 EN 60079-11:2012 EN 54-18 Ex approvals ● EC-type examination certificate BVS 12 ATEX E 094 ● IECEx IECEx BVS 12.0079 Approvals ● G213108 ● DNV GL (marine) MEDB00003UU System compatibility ●...
  • Page 131: Safety Barrier Sb3

    Special detectors Safety barrier SB3 10.10 Safety barrier SB3 Device for zone 0, 1 and 2 areas at risk of explosion 10.10.1 Functions If fire detectors are being installed and operated in potentially explosive atmospheres, the installations and apparatus must conform to country-specific safety regulations.
  • Page 132 Special detectors Safety barrier SB3 10.10.2 Type Overview Type Designation Order number Weight [kg] Safety barrier BPZ:4717230001 0.125 Type: Steel (9002/13-280-93-001) Safety barrier BPZ:4837400001 0.115 Type: Steel (9002/13-280-93-001) Accessories for safety barriers SB2, SB3 Type Designation Order number Weight [kg] DCA1191 Housing with cover, flat BPZ:4588560001...
  • Page 133: Test Units And Accessories

    Test units and accessories Detector exchanger FDUD291 11 Test units and accessories 11.1 Detector exchanger FDUD291 11.1.1 Function ● Efficient installation and removal of the point detectors FDO, FDOOT, FDT, FDOOTC 1 Point detectors FDO, FDOOT, Dimensioned drawing FDUD291 FDT, FDOOTC 2 Joint springs of the FDUD291 008164_y_en_-- 133 | 152...
  • Page 134 Test units and accessories Detector exchanger FDUD291 11.1.2 Properties ● Possible to exchange the detector without a ladder or scaffolding up to a room height of 8 m with the help of the telescope rods ● Joint springs enable the point detectors to be inserted or removed at an angle ●...
  • Page 135: Detector Exchanger And Tester Fdud292, Intelligent Detector Tester Fdud293

    Test units and accessories Detector exchanger and tester FDUD292, intelligent detector tester FDUD293 11.2 Detector exchanger and tester FDUD292, intelligent detector tester FDUD293 11.2.1 Function FDUD292 ● Efficient installation and removal of the point detectors FDO, FDOOT, FDT, FDOOTC ● Commissioning, maintenance, status checking, and testing of detectors with further diagnosis information directly on site ●...
  • Page 136: Scorp 8000

    Test units and accessories SCORP 8000 11.3 SCORP 8000 11.3.1 Properties The remote test system for aspirating smoke detectors (ASD) solves a number of longstanding problems, supports compliance with international regulations and standards, helps make considerable time and cost savings, and reduces interruption times.
  • Page 137 Test units and accessories SCORP 8000 Features ● Smoke generation tailored to functional testing of ASD systems and point smoke detectors ● Adjustable smoke supply time to suit characteristics of system being tested Test capacity ● More than 240 tests per Scorpion device 11.3.2 Type Overview Type Order number...
  • Page 138 Test units and accessories SCORP 8000 11.3.3 Technical data Environmental conditions and protection categories Solo770 battery SCORP 2001 SCORP 8000 Scorpion ASD Scorpion head unit controller Transport/storage temperature -25...+70 °C -20...+70 °C -10...+50 °C Operating temperature +5...+35 °C 0...+60 °C +5...+45 °C Storage humidity ≤90 % rel.
  • Page 139: Adjustment Kit Fdlu291

    Test units and accessories Adjustment kit FDLU291 11.4 Adjustment kit FDLU291 The adjustment kit is used for commissioning the linear smoke detector FDL241-9. The lens of the linear smoke detector can be efficiently aligned to the reflector by one man. Scope of delivery: ●...
  • Page 140: Detector Tester Re6

    Test units and accessories Detector tester RE6 11.5 Detector tester RE6 ● The detector tester RE6 is used together with a test gas can REF8, REF8-S, or REF8-C. It is designed to test optical smoke detectors, ionization detectors, and CO detectors. ●...
  • Page 141: Detector Tester Re7T - Solo461 Heat Detector Tester Kit

    Test units and accessories Detector tester RE7T – Solo461 heat detector tester kit 11.6 Detector tester RE7T – Solo461 heat detector tester kit The heat detector tester kit consists of ● 1x heat detector tester ● 2x rechargeable batteries ● 1x charger with 12 V connection cable ●...
  • Page 142: Detector Tester Re8St - Testifire 1001-101 Rt Test Kit

    Test units and accessories Detector tester RE8ST – Testifire 1001-101 RT test kit 11.7 Detector tester RE8ST – Testifire 1001-101 RT test The test kit RE8ST consists of ● 1x Testifire 1001-101 tester ● 1x RE8-S smoke capsule ● 2x rechargeable batteries ●...
  • Page 143: Detector Tester Re8Stco - Testifire 1001-101 St Test Kit

    Test units and accessories Detector tester RE8STCO – Testifire 1001-101 ST test kit 11.8 Detector tester RE8STCO – Testifire 1001-101 ST test kit Figure 5: The test kit RE8STCO consists of ● 1x Testifire 2001-101 tester ● 1x RE8-S smoke capsule ●...
  • Page 144: Accessories And Spare Parts For Re7T/Re8St/Re8Stco

    Test units and accessories Accessories and spare parts for RE7T/RE8ST/RE8STCO 11.9 Accessories and spare parts for RE7T/RE8ST/RE8STCO RE7T-A – Solo719 adapter for FDUM29x Mounting adapter for the detector testers RE7T, RE8ST, and RE8STCO on the telescope rods FDUM291 and FDUM292 RE7T-B1 –...
  • Page 145: Detector Tester Re10, Alarm Test Filter Tf04

    Test units and accessories Detector tester RE10, alarm test filter TF04 11.10 Detector tester RE10, alarm test filter TF04 ● For undertaking a function check on the linear smoke detectors. The alarm test filter TF04 is inserted into the detector tester in accordance with the type of detector to be tested.
  • Page 146: Line Tester Fdul221

    Test units and accessories Line tester FDUL221 11.11 Line tester FDUL221 11.11.1 Function Different functions can be called up, e.g.,: ● Number of devices found at A and B connection ● Line errors found, location of the line error ● Short-circuit, open line, ground fault with indication of which conductor/s ●...
  • Page 147 Test units and accessories Line tester FDUL221 Figure 6: Line tester software FXS2017 Figure 7: Line tester software FXS2017 008164_y_en_-- 147 | 152...
  • Page 148: Le3 Test Lamp

    Test units and accessories LE3 Test lamp 11.12 LE3 Test lamp The test lamp LE3 is used to test the function of all flame detectors over distances up to 10 m. It is housed in a transportable case together with the required accessories.
  • Page 149: Adapter For Fdnet Devices Fduz227

    Test units and accessories Adapter for FDnet devices FDUZ227 11.13 Adapter for FDnet devices FDUZ227 11.13.1 Use The MCL-USB adapter (radio) is an interface converter for USB to MC link. It connects FDnet devices to a PC using a serial protocol (MC link). The adapter is used for firmware updates or in live operation.
  • Page 150 A driver for devices based on TUSB3410 is a mandatory requirement to operate the MCL-USB adapter (radio) FDUZ227 with the 'FXS2061 SWING tool' software. Link to driver and installation instructions: www.siemens.com/fduz227-driver The 'SintesoWorks FXS2002' software or the 'Cerberus-Engineering-Tool FXS7212' is required to update the firmware on FDnet devices.
  • Page 151 Test units and accessories Adapter for FDnet devices FDUZ227 11.13.2 Type Overview Type Designation Order number Designation Weight MCL-USB FDUZ227 Adapter incl. adapter S54323-F106-A1 Adapter incl. adapter 0.077 kg adapter cable FDUD292-A for cable FDUD292-A for the (radio) the cable connection to cable connection to the the FDnet devices and FDnet devices and USB...
  • Page 152 Issued by Siemens Switzerland Ltd Smart Infrastructure Global Headquarters Theilerstrasse 1a CH-6300 Zug © Siemens Switzerland Ltd, 2004 +41 58 724 2424 www.siemens.com/buildingtechnologies Technical specifications and availability subject to change without notice. 008164_y_en_--...