hit counter script
Download Print this page
Honeywell CentraLine LYNX BACnet CLLYUB1012S Product Data

Honeywell CentraLine LYNX BACnet CLLYUB1012S Product Data

Programmable vav/unitary controllers

Advertisement

Quick Links

LYNX BACnet® Programmable
VAV/Unitary Controllers
model
type
CLLYUB1012S
unitary
CLLYUB4024S
unitary
CLLYUB6438S
unitary
CLLYVB0000AS
VAV
CLLYVB4022AS
VAV
CLLYVB4024NS
VAV
CLLYVB6436AS
VAV
CLLYVB6438NS
VAV
(A
One Universal Input (UI-1*) is selectable as a fast digital pulse meter.
All of the LYNX controllers communicate via an EIA-485 BACnet MS/TP communication network, capable of baud rates of
between 9.6 and 115.2 kbits/sec.
The LYNX controllers are field-mountable to either a panel or a DIN rail.
Copyright © 2015 Honeywell GmbH ● All Rights Reserved
Product Data
Table 1. Controller configurations
Universal
Digital
Inputs (UI)
Inputs (DI)
(A
1
0
(A
4
0
6
4
0
0
(A
4
0
(A
4
0
6
4
6
4
GENERAL
The BACnet MS/TP LYNX controllers are designed to control
HVAC equipment.
LYNX controllers provide many options and advanced system
features that allow state-of-the-art commercial building
control. Each LYNX controller is programmable and con-
figurable using the COACH
LYNX BACnet controllers require the LYNX BACnet Pro-
grammable Feature to be licensed in COACH
LYNX controllers are designed for use in VAV (Variable Air
Volume) and Unitary HVAC control applications. Each con-
troller contains a host microcontroller to run the main HVAC
application and a second microcontroller for BACnet MS/TP
network communications. Each controller has flexible,
universal inputs for wall modules, digital inputs, and a mix of
analog and digital triac outputs (see Table 1). The models
CLLYVB6436AS, CLLYVB0000AS, and CLLYVB4022AS
include an actuator.
Analog Out-
Digital Out-
puts (AO)
puts (DO)
1
2
2
4
3
8
0
0
2
2
2
4
3
6
3
8
AX
software.
AX
.
velocity pressure
floating
sensor
actuator
(Microbridge)
NO
NO
NO
NO
NO
NO
YES
YES
YES
YES
YES
NO
YES
YES
YES
NO
EN0Z-0959GE51 R0615

Advertisement

loading

Summary of Contents for Honeywell CentraLine LYNX BACnet CLLYUB1012S

  • Page 1 All of the LYNX controllers communicate via an EIA-485 BACnet MS/TP communication network, capable of baud rates of between 9.6 and 115.2 kbits/sec. The LYNX controllers are field-mountable to either a panel or a DIN rail. Copyright © 2015 Honeywell GmbH ● All Rights Reserved EN0Z-0959GE51 R0615...
  • Page 2: Technical Data

    LYNX BACNET PROGRAMMABLE, VAV/UNITARY CONTROLLERS – PRODUCT DATA TECHNICAL DATA Table 2. Universal input circuit specifications GENERAL SPECIFICATIONS input type sensor type operating range Rated voltage: 20 … 30 Vac; 50/60 Hz Power consumption: 100 VA for controller and all connected Room/Zone Discharge NTC 20kOhm -40 ...
  • Page 3 LYNX BACnet PROGRAMMABLE, VAV/UNITARY CONTROLLERS – PRODUCT DATA In the case of the AS-models, first the actuator and then the DAMPER controller is mounted. For the other models, see section “Mount Controller” on page 4 to begin the installation. Mounting Actuator onto Damper Shaft (AS- Models) The AS-models include the direct-coupled actuator with DECLUTCH button, which is shipped hard-wired to the...
  • Page 4: Mount Controller

    LYNX BACNET PROGRAMMABLE, VAV/UNITARY CONTROLLERS – PRODUCT DATA Mounting Actuator Onto Damper Shaft (AS- g) When the actuator closes, the damper rotates CW either 45 or 60° to fully close. Models) The unit is shipped with the actuator set to rotate open in the IMPORTANT clockwise (CW) direction to a full 95°.
  • Page 5 LYNX BACnet PROGRAMMABLE, VAV/UNITARY CONTROLLERS – PRODUCT DATA The controller can be mounted in any orientation. Ventilation openings are designed into the cover to allow proper heat dissipation, regardless of the mounting orientation. 13 14 15 16 17 18 19 20 21 22 23 24 13 14 15 16 17 18 19 20 21 22 23 24 DIN Rail Mounting (S- and NS-models) DEPTH = 57...
  • Page 6 LYNX BACNET PROGRAMMABLE, VAV/UNITARY CONTROLLERS – PRODUCT DATA It is important to understand these interrelationships early in NOTE 1: If controllers are mounted in unusually dusty or the job engineering process, to ensure proper implementation dirty environments, an inline, 5-micron disposable when configuring the controllers.
  • Page 7 200 pF per meter. Foil or braided shields are acceptable. The Honeywell tested and recommended MS/TP cable is Honeywell Cable 3322 (18 AWG, 1-Pair, Shielded, Plenum cable), alternatively Honeywell Cable 3251 (22 AWG, 1-Pair, Shielded, Plenum...
  • Page 8 LYNX BACNET PROGRAMMABLE, VAV/UNITARY CONTROLLERS – PRODUCT DATA 1. Find an unused MAC address on the MS/TP network to grounded on only one end of the MS/TP segment (typically, which the LYNX controller connects. on the router end). Tie the shield through using the SHLD (terminal 4) on the LYNX Controller.
  • Page 9 20 VDC 20 VDC POWER work must have a unique MAC address in the range of 0-127 UNIVERSAL INPUTS (address 0 should be avoided as it is the Honeywell factory UI-1* UNIVERSAL INPUT default MAC address for all MS/TP devices).
  • Page 10 LYNX BACNET PROGRAMMABLE, VAV/UNITARY CONTROLLERS – PRODUCT DATA CLCM4T111 WINDOW CONTACTS OCCUPANCY SENSOR BYPASS (CONTACTS CLOSED (CONTACTS CLOSED = WINDOW CLOSED) = OCCUPIED) SET-POINT 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 SENSOR AIR FLOW PICK-UP...
  • Page 11 LYNX BACnet PROGRAMMABLE, VAV/UNITARY CONTROLLERS – PRODUCT DATA CLCM4T111 WINDOW CONTACTS OCCUPANCY SENSOR BYPASS (CONTACTS CLOSED (CONTACTS CLOSED SET-POINT = WINDOW CLOSED) = OCCUPIED) SENSOR AIR FLOW PICK-UP 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 C770A AIR TEMP.
  • Page 12 LYNX BACNET PROGRAMMABLE, VAV/UNITARY CONTROLLERS – PRODUCT DATA CLCM4T111 OUTDOOR ENTHALPY OUTDOOR ENTHALPY WALL MODULE CLCM4T111 WALL MODULE BYPASS SET-POINT BYPASS SENSOR RETURN ENTHALPY RETURN ENTHALPY SET-POINT WINDOW CONTACTS (CONTACTS CLOSED SENSOR = WINDOW CLOSED) OCCUPANCY SENSOR (CONTACTS CLOSED = OCCUPIED) DISCHARGE DISCHARGE AIR TEMP.
  • Page 13 LYNX BACnet PROGRAMMABLE, VAV/UNITARY CONTROLLERS – PRODUCT DATA CLCM4T111 2- OR 3-WAY CHILLER 2- OR 3-WAY HOTWATER/ WATER VALVE STEAM VALVE WALL MODULE BYPASS SERIES 70 SERIES 70 VALVE ACTUATOR VALVE ACTUATOR SET-POINT 2 2 2 2 2 2 2 2 2 2 3 3 3 3 3 3 3 3 3 4 SENSOR 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 CLLYUB6438S...
  • Page 14 (see network must have a unique MAC address in the range of 0- Fig. 11). 127 (address 0 should be avoided as it is the Honeywell  Verify that triac wiring of the digital outputs to external factory default MAC address for all MS/TP devices).
  • Page 15: Controller Replacement

    LYNX BACnet PROGRAMMABLE, VAV/UNITARY CONTROLLERS – PRODUCT DATA visual indication of the BACnet MS/TP communication status. Terminal Block Removal When the controller receives power, the LED appears in one To simplify controller replacement, all terminal blocks are of the following allowable states, as described in Table 7. designed to be removed with the wiring connections intact and then re-installed on the new controller.
  • Page 16 (see Fig. 7). Mount the new controller (see section “Installation” on page 2). Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl, Rolle, Z.A. La Pièce 16, Switzerland by its Authorized Representative: CentraLine Honeywell GmbH Böblinger Strasse 17...

This manual is also suitable for:

Centraline lynx bacnet cllyub6438sCentraline lynx bacnet cllyvb0000asCentraline lynx bacnet cllyub4024sCentraline lynx bacnet cllyvb4024nsCentraline lynx bacnet cllyvb4022asCentraline lynx bacnet cllyvb6436as ... Show all