Disassembling the thyristor blocks for size K

G K
G K
15
13
14
Front thyristor block, level A (weight of a thyristor block, approx. 25 kg)
Remove the 3 covers
Remove the copper plate
Remove the copper plate
Unplug the gate and cathode cables
Only on disassembling the central thyristor block, remove the two thermistors that are only located on the
central thyristor block by removing the screws
Loosen the two M10 hexagon-head screws
A
Loosen M10 nut
and pull the thyristor block out upwards at an angle.
Rear thyristor block, level B (weight of a thyristor block, approx. 25 kg)
Unplug gate and cathode cables (G, K)
Remove 2 M10 hexagon-head screws
Remove 2 M10 hexagon-head screws
Remove 2 M10 hexagon-head screws
H
Loosen M10 nut
angle.
The thyristor blocks are installed in the reverse order.
Siemens AG
6SE7087-6AK85-1AA0
Rectifier/Regenerating Unit
Operating instructions
AoteWell LTD
AoteWell Automation Sales Team
10
G K
G K
8
9
9
5
4
6
7
a
by removing 7 M4 hexagon-head bolts
f
by removing 6 M10 hexagon-head bolts
h
by removing 4 M10 hexagon-head bolts
k
(G, K).
;
S
.
D
.
F
.
G
.
, swing the thyristor block out forwards and pull the thyristor block out upwards at an
Buy Siemens PLC HMI Drives at AoteWell.com
G K
G K
s
and 3 M4 nuts
l
(Torx drive T25).
and swing the thyristor block out forwards.
Sales@aotewell.com
12
15
16
11
13
14
d
.
g
.
j
.
https://www.aotewell.com
Maintenance
2
1
3
10
8
1
3
5
5
7
4
6
5
7
3
1
2
8-13