U-ENM00043, REV 0 UNINTERRUPTIBLE POWER SUPPLY SYSTEM MODEL 9900CX SERIES OWNER’S / TECHNICAL MANUAL (Inclusive Parallel Operation System Application) ® UNINTERRUPTED Peace of Mind...
3.3 PROCEDURE FOR CABLE CONNECTIONS ............3-2 3.4 OPERATING PROCEDURES ................... 3-8 4.0 RESPONSE TO UPS FAILURE ................4-1 5.0 PARTS REPLACEMENT ..................5-1 6.0 FAULT CODES ......................6-1 7.0 WARRANTY & OUT OF WARRANTY SERVICE ............ 7-1 MITSUBISHI ELECTRIC 9900CX SERIES UPS...
Recommended Cable Sizes ................ 3-4 Table 3.5 Recommended Hardware ................3-4 Table 3.6 Crimp Type Compression Lug ..............3-5 Table 6.1 Bypass Module Fault Code List ..............6-2 Table 6.2 UPS Module Fault Code List ............... 6-6 MITSUBISHI ELECTRIC 9900CX SERIES UPS...
Page 5
Figure 3.1 UPS Terminal Designation ..............3-5 Figure 3.2 Diagram of Input/Output Bus Bars and Terminal Blocks ....... 3-6 Figure 3.3 Diagram of Power Wire and Control Wire Interconnection between UPS and Battery ..................3-7 MITSUBISHI ELECTRIC 9900CX SERIES UPS...
UPS operation, load status and display status. Such information is essential if Mitsubishi field service group assistance and correspondence is required. Safety Recommendations: If any problems are encountered while following this manual, Mitsubishi field service group assistance and correspondence is recommended. MITSUBISHI ELECTRIC 9900CX SERIES UPS...
IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important instructions for the 9900CX SERIES Uninterruptible Power Supply System that should be followed during installation and maintenance of the UPS and batteries. WARNING 1 Lethal voltages exist within the equipment during operation.
Since the UPS contain special industrial waste, such as capacitors, insulators or batteries, they cannot be disposed of like other general waste. Please check the disposal guideline of your district, contact the specialized contractor for disposal. MITSUBISHI ELECTRIC 9900CX SERIES UPS...
Page 9
If the UPS System is to be applied to support equipment that could affect human safety, the following steps must be adhered to: 1. Consult with Mitsubishi Electric Power Products Inc. UPS Division. 2. Special consideration of the overall back up power system configuration is required so that the Mitsubishi UPS System is not the sole support required for operation, maintenance and management of power availability.
No more than 0.01 PPM IEC654-4 Chlorine gas (Cl No more than 0.002 PPM Part 4 Ammonia gas (NH No more than 1 PPM Nitrous oxides (NO No more than 0.05 PPM Ozone (O No more than 0.002 PPM MITSUBISHI ELECTRIC 9900CX SERIES UPS...
AC input and AC output overcurrent protection and disconnect devices shall be field supplied and installed. The DC circuit breaker (MCCB) shall be field supplied and installed. The overcurrent protection device should be installed in the Battery cabinet and rated as indicated in Table 1.6. MITSUBISHI ELECTRIC 9900CX SERIES UPS...
UPS. The UPS is simple to start-up, operate and maintain. The 9900CX SERIES UPS is available in 1050, 1400, 1750, and 2100 kVA. Specifications are shown in Section 1.5. This manual provides an overview of the 9900CX SERIES components and their functions. The appearance and purpose of operator controls and indicators is described with procedures for operation, start-up, shutdown and basic maintenance included.
UPS for supplying the critical load. BATTERY - The rechargeable battery strings which supply DC power to the inverter to maintain continuous AC power to the load during AC input power failure conditions. MITSUBISHI ELECTRIC 9900CX SERIES UPS...
UPS battery and to provide power to the Inverter. The Inverter converts the DC power to clean AC power to supply the critical load. The conversion - inversion process eliminates any voltage transients or fluctuations existing in the input power before it reaches the critical load. MITSUBISHI ELECTRIC 9900CX SERIES UPS...
Page 15
In the event of a UPS module failure during Parallel Operation, the critical load power will be continually supplied and shared by all other UPS. The Bypass Input circuit breaker (MCCB) for protection of the UPS and cables are field supplied and field installed. (See WARNING 4 on page 1-4). MITSUBISHI ELECTRIC 9900CX SERIES UPS...
Parallel Operation if a cable length of bypass line is equal each other. For a MMS unable to equalize the cable length, additional rectors should be installed to compensate the difference in cable impedance. MITSUBISHI ELECTRIC 9900CX SERIES UPS...
Referring to Figure 1.3: In the event of AC input source failure or interruption, the UPS Converter(s)* will de-energize and the UPS battery(s)* will immediately discharge and supply DC power to the Inverter to maintain continuous AC power to the load. This operation will continue until: MITSUBISHI ELECTRIC 9900CX SERIES UPS...
Page 18
The power drawn by the load is equally shared between all UPS regardless of the presence or absence of the UPS that is (are) in battery operation or not whenever the system is in the Parallel Operation. . MITSUBISHI ELECTRIC 9900CX SERIES UPS...
Recommended : 68゚F to 86゚F ( 20゚C to 30゚C) Relative Humidity 5% ~ 95% Non Condensing Altitude 0 to 6500 feet No Derating at 40゚C Location Indoor (free from corrosive gases and dust) Paint Color Munsell 5Y7/1 (Beige) MITSUBISHI ELECTRIC 9900CX SERIES UPS...
Page Number: 9900CX SERIES UPS OWNERS / TECHNICAL MANUAL 2.0 OPERATOR CONTROLS AND INDICATORS The 9900CX Series operator controls and indicators are located as follows (Bypass Module door exterior) : Figure 2.1 Operation/Display Panel (Front panel) MITSUBISHI ELECTRIC 9900CX SERIES UPS...
2.2 EPO BUTTON (Emergency Power Off button) (7) When activated, the Emergency Power Off (EPO) function shuts down the UPS module. The critical load will lose power and also shutdown. The EPO function can be performed both locally or remotely. MITSUBISHI ELECTRIC 9900CX SERIES UPS...
- Start: When the bypass voltage is abnormal, the LCD asks the operator if an interrupted transfer is acceptable (Load may be lost). - Stop: When the bypass voltage is abnormal, the user cannot transfer from inverter to bypass line. MITSUBISHI ELECTRIC 9900CX SERIES UPS...
MEASUREMENT MENU (Figure 2.4) This screen shows details of measured values. Input and Output values are displayed. During Battery operation, Remaining battery power and Run time are also displayed. Figure 2.4(a) Input Values Figure 2.4(b) Output Values MITSUBISHI ELECTRIC 9900CX SERIES UPS...
Pressing the EVENT LOG icon, up to 100 condition/operation records will be displayed. Press button for page turning. Pressing the BATTERY LOG icon, Number of battery operations and Summed battery operation time are displayed. Figure 2.6(a) Log Menu Figure 2.6(b) Event Log Figure 2.6(c) Battery Log MITSUBISHI ELECTRIC 9900CX SERIES UPS...
When the input power is restored, the inverter will automatically restart to power the load, and the batteries will be simultaneously recharged. The End of Battery announcement is shown at the bottom of the screen. MITSUBISHI ELECTRIC 9900CX SERIES UPS...
5 second intervals. Figure 2.9 Message screen SILENCE ALARM This icon will appear when a failure occurs. The audible alarm (announcing the failure) can be silenced by pressing this icon. MITSUBISHI ELECTRIC 9900CX SERIES UPS...
Terminals 15 to 16 "Spare" contact (OUT7) Terminals 17 to 18 "Total Alarm" contact (OUT8) Activated during major fault, minor fault and alarm events. Terminals 19 to 20 "52C Close" contact Activated when the inverter output contactor 52C has closed. MITSUBISHI ELECTRIC 9900CX SERIES UPS...
CONVERTER OPERATION OUT4 INVERTER OPERATION CB1 CLOSE CB2 CLOSE 52S CLOSE POWER DEMAND ON EQUALIZING CHARGE ANOTHER BUS SYNC.OK SPARE 29 SPARE 30 SPARE 31 NOTE: Contact MITSUBISHI ELECTRIC POWER PRODUCTS, INC for Detailed information. MITSUBISHI ELECTRIC 9900CX SERIES UPS...
Figure 2.12 Remote "Start" Contact Connections External to UPS Cabinet UPS Cabinet Relay Start Coil Start Switch Common 0.5s – 4s 12 VDC Use Momentary Relay Coil current : 16.7 mA Switches Only User supplied MITSUBISHI ELECTRIC 9900CX SERIES UPS...
Page 36
OFF when the contact is open. Terminals 33 to 34 "Remote EPO" contact input Used to perform a remote UPS Emergency Power Off (EPO). The load will be dropped. MITSUBISHI ELECTRIC 9900CX SERIES UPS...
SPARE 28 SPARE 29 SPARE 30 TRACE TRIGGER NOTE: Contact MITSUBISHI ELECTRIC POWER PRODUCTS, INC for Detailed information. CAUTION : In all cases, a switch having a protective cover is recommended in order to reduce the possibility of accidental operation.
: Not used Pin 7. : Not used Pin 8. : Not used Pin 9. : Not used PCB IOAU-19 * Consult MITSUBISHI ELECTRIC POWER PRODUCTS, INC for details on“DiamondLink” monitoring software and its capabilities. MITSUBISHI ELECTRIC 9900CX SERIES UPS...
C) Space requirement for routine maintenance Allow for the following space at the time of installation. Front 1000 mm (39 inches) Sides 0.0 mm (0 inch) Back side 0.0 mm (0 inch) Top side 500 mm (20 inches) MITSUBISHI ELECTRIC 9900CX SERIES UPS...
With a phase rotation meter, check that the phase rotation of the AC Input power terminals A, B and C as well as the Bypass Input power terminals A40, B40 and C40 are correct. The proper phase rotation is clockwise MITSUBISHI ELECTRIC 9900CX SERIES UPS...
Page 41
2.10 for functional description. 2mm , or less, shielded conductor is recommended. CAUTION : UPS power terminals are supplied with stud type fittings. It is recommended that compression lugs be used to fasten all input/output power cables. MITSUBISHI ELECTRIC 9900CX SERIES UPS...
*4 - Allowable ampere-capacities based on copper conductors with 75 degree C. insulation at ambient temperature of 40 degree C. Recommended Hardware Table 3.5 Split Nut size Flat washer UPS Capacity Bolt size lockwasher size size 1050kVA M12 x 40mm 1400kVA M12 x 40mm 1750kVA M12 x 40mm 2100kVA M12 x 40mm MITSUBISHI ELECTRIC 9900CX SERIES UPS...
※1. Signal lines should be separated to the main circuit cables with more than 100mm insulating distance. The wiring also should fix to the frame to ensure the insulating distance satisfied the condition. ※2. 3x 2-holes bases ※3. 4x 4-holse bases MITSUBISHI ELECTRIC 9900CX SERIES UPS...
Figure 3.3 Diagram of Power Wire & Control Wire Interconnections between UPS and Battery DC circuit breaker External signal User supplied terminal IOAU-19 - [TN1] Auxiliary “-” Negative “+” Positive Power terminal User supplied UPS module Wall mounted DC breaker for Battery MITSUBISHI ELECTRIC 9900CX SERIES UPS...
NOTE : When "REMOTE OPERATION MODE" is displayed on the LCD panel, the inverter start operation can only be performed remotely. If local inverter start operation is required (at the UPS), select "LOCAL ONLY" or “REMOTE & LOCAL” in the OPERATION MENU. MITSUBISHI ELECTRIC 9900CX SERIES UPS...
Page 47
De-energize all external sources of AC and DC power. Before removing the covers, wait 5 minutes after de-energizing. Check no-voltage before handling UPS. Be careful for the devices even when the UPS has been de-energized, still internal devices may hot. MITSUBISHI ELECTRIC 9900CX SERIES UPS...
Page 48
NOTE : When "REMOTE OPERATION MODE" is displayed on the LCD panel, the inverter start operation can only be performed remotely. If local inverter start operation is required (at the UPS), select "LOCAL ONLY" or “REMOTE & LOCAL” in the OPERATION MENU. MITSUBISHI ELECTRIC 9900CX SERIES UPS...
The error code indicated on the LCD display panel when an UPS alarms is very important. In order to reduce repair time, please include this information, along with the operation and load status for all correspondence to Mitsubishi Electric field service group. MITSUBISHI ELECTRIC 9900CX SERIES UPS...
9900CX SERIES UPS OWNERS / TECHNICAL MANUAL 5.0 PARTS REPLACEMENT Contact Mitsubishi Electric Power Products, Inc.or its authorized service representatives on all issues regarding the replacement of parts. A) Battery Battery lifetime may vary according to the frequency of use and the average ambient operating temperature.
A) Verify and record the occurrence of the alarm. Note details of alarm message displayed on the LCD display panel. Contact Mitsubishi Electric Power Products, Inc. at 1-800-887-7830. B) If a circuit breaker (MCCB) has tripped, depress the toggle to reset the breaker before closing it again.
CHECK A power converter module has INPUT Intermittent UA863 MOD.IN.VOLT. detected input voltage abnormal. POWER sound SOURCE WARNING : A power converter module has Intermittent UA864 MODULE OVERLOAD DECREASE Overload detected output overload. sound LOAD MITSUBISHI ELECTRIC 9900CX SERIES UPS...
Page 53
Detection of an external CALL Continuous UF302 CTRL.CIRCUIT ERR. interruption during the software SERVICE Major sound execution. ENGINEER CALL Timer does not reset in the Continuous UF303 CTRL.CIRCUIT ERR. SERVICE Major specified period (WDT settings) sound ENGINEER MITSUBISHI ELECTRIC 9900CX SERIES UPS...
Page 54
ENGINEER CALL Cable disconnection in the Intermittent UF374 CTRL.CIRCUIT ERR. SERVICE Minor parallel interface board. sound ENGINEER Unable to achieve CALL Intermittent UF375 CTRL.CIRCUIT ERR. synchronization for parallel SERVICE Minor sound operation. ENGINEER MITSUBISHI ELECTRIC 9900CX SERIES UPS...
Page 55
ENGINEER CALL Contactor 52S failed during load Intermittent UF451 52S ABNORMAL SERVICE Minor transfer from inverter to bypass. sound ENGINEER CALL Contactor CB3 is not working Intermittent UF452 CB3 ABNORMAL SERVICE Minor properly. sound ENGINEER MITSUBISHI ELECTRIC 9900CX SERIES UPS...
Major unbalance of the neutral point voltage. Major MF110 ZERO PHASE OC. Major unbalance of the neutral point voltage. Major MF111 CTRL.CIRCUIT ERR. Battery current unbalance. Major MF112 DC CIRCUIT ABNL. Sudden change of the DC voltage level. Major MITSUBISHI ELECTRIC 9900CX SERIES UPS...
Page 57
MF254 COOLING FAN ABNL. Thermal relay of cooling fan worked. Minor MF256 O/P VOLTAGE ABNL. Output voltage is out of the specified range. Minor MF301 CTRL.CIRCUIT ERR. AD reference has an abnormal value. Major MITSUBISHI ELECTRIC 9900CX SERIES UPS...
Page 58
#%2++ --------------------- Inverter circuit failure #%3++ --------------------- Control circuit failure #%4++ --------------------- Bypass system failure #%8++ --------------------- Alarm “#” Bypass Module “U”, UPS Module “M” “+” denotes any numeral from 0 to 9 “%” denotes either “A” or “F” MITSUBISHI ELECTRIC 9900CX SERIES UPS...
Mitsubishi Electric Power Products, Inc. at (724) 772-2555. To register your UPS for warranty purposes, please complete the warranty registration form and fax it to the Mitsubishi Electric UPS Division Service Department fax line shown on the registration form. (Next page) For warranty purposes, it is essential that any and all service work that may be required on your Mitsubishi brand UPS equipment is performed by a Mitsubishi Electric Authorized Service Center.
Page 60
Would you like to receive future product updates __ Electrical Contractor __ Distributors/Reps and news? __ Healthcare __ Other __________________ __Yes __ No __ Internet After Start-Up has been done Fax completed Form to: (724) 778-3146 MITSUBISHI ELECTRIC 9900CX SERIES UPS...