3 Technical datas
3.1 Hardware features
Mechanical design
Housing
Dimensions
Weight
Degree of protection
Housing
Terminals
Auxiliary voltage U
Rated input voltage
- DC voltage
- AC voltage
Fuse internal
Class of protection (depends on
input voltage)
Power consumption
- DC voltage
- AC voltage
Alarm relay
1 Relay
Connector
Test voltage
Switching voltage (nominal value)
Switching capability
Switching current
Fault indicator
RS232-interface
Connector
Baudrate
Test voltage
12.10.2006
H
RS232-FO Converter
Plastic, EG90
see dimensional drawings
approx. 250g
according EN60529, IEC60529
IP 20
IP 20
24 V - 250 V DC ± 20 %
24 V - 230 V AC ± 20 % / 45-65 Hz
1,25 A slow blow (not changeable)
III
With U
= U
; typical value
H
HN
3 W
2.5 W; 3.5 VA
MSR-Relay, 1 NC (open) contact,
potential free
2-pol. Phönix terminal
3,7 kV
eff
250 V DC
20 W/VA
1 A permanent
LED green: 5 V o.k,
9-pol. SUB-D, socket
DC - 115200 bauds
2 kV AC towards other connections
Page 11 of 28