Using the DTM:
The error can be identified from the Monitor, Device Status & Alarms screen. The error is
identified as Model Number Mismatch (see Figure 5-11)
To clear this error, navigate to the Advanced Configuration, Services tab and select Reconcile
Model Numbers. In most cases, it will be appropriate to select Use Comm Module Model
Number to clear the error. After selection, the transmitter will restart.
Revision 8
Figure 5-11- Model Number Mismatch Critical Error
Figure 5-12 - Reconcile Model Numbers feature
SLG 700 SmartLine Level Transmitter User's Manual
Page 141