System Overview Component Description Operator Controls and Displays SINUMERIK 802D sl Interfaces Instruction Manual Dimensional Drawings and Drill Patterns Installation Connection Technical Data Start-Up Creating a Drive Project Starting Up the PLC Valid for Control system Software version Data Backup and...
Page 4
Siemens. It is assumed that this product be transported, stored and installed as intended and maintained and operated with care to ensure that the product functions correctly and properly.
Page 5
SINUMERIK control systems (e.g., Universal Interface, Measuring Cycles, etc.) can be obtained from your local Siemens branch office. A list of documents, updated on a monthly basis, is available on the Internet for the available languages at: http://www.siemens.com/motioncontrol...
PROFIBUS interface for the drives and for the I/O modules with the slimline operator panel into a ready-to-install unit (Panel Control Unit). The SINUMERIK 802D sl can control up to 5 axes digitally. Up to 2 of these 5 axes can be configured as a spindle.
Page 12
Mains supply Feed motor 3 conductor Feed motor 4 when using a Main spindle motor machine control panel Fig. 1-1 System overview: SINUMERIK 802D sl mit SINAMICS S120 (example) SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 1-10 6FC5 397-0CP10-1BA0...
Page 13
To supply the module and the digital outputs, an external voltage source (+24 V DC) is required. S Drive units – SINAMICS S120 The communication between the SINUMERIK 802D sl control system and the SINAMICS S 120 drive is provided via the DRIVECLiQ communication system (Drive Component Link with IQ). System software...
Page 14
S PLC user library S “Starter” – parameterization and commissioning tool for the SINAMICS drive Note The table of contents and notes for setup can be found in the siemense.txt file. SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 1-12 6FC5 397-0CP10-1BA0...
Page 16
DRIVE CLiQ interfaceX1 and X2 Handwheel connectionX30 Digital inputs/outputs X20, X21 Optional interface Grounding screw Fig. 2-1 Position of the interfaces and front elements on the CNC operator panel SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 2-14 6FC5 397-0CP10-1BA0...
Page 17
12-pin screw-type male connector for connecting the digital inputs Digital inputs/digital outputs and outputs X20 and X21 see Chapter 4.1.8 TB30 interface 48-pin female connector for connecting the MCPA module see Chapter 4.2 Siemens Automation Parts SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 2-15 6FC5 397-0CP10-1BA0...
Operator Controls and Displays Operator controls Use the horizontal and vertical softkeys to select defined functions. For a description of the individual softkeys, please refer to the SINUMERIK 802D sl Programming and Operator’s Guide. References: /BP/, Programming and Operator’s Guide...
Sign-of-life monitoring CF (yellow) Reading from / writing to CF card Note For error descriptions, see SINUMERIK 802D sl Diagnostics Guide. References: /DG/, Diagnostics Guide LEDs on the PP 72/48 I/O module The following LEDs are installed on the I/O module (see Fig. 4-3): The individual LEDs and their functions are described in the table below.
S for NC programs S to carry out software updates S to store user data S to save parameters which have been set by the user. Siemens Automation Parts SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 4-19 6FC5 397-0CP10-1BA0...
Received data – not assigned – not assigned – You can obtain additional information about the different cable systems for Ethernet from your SIEMENS contact person. 4.1.3 USB port (available soon) SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 4-20 6FC5 397-0CP10-1BA0...
The CNC operator panel has a fixed PROFIBUS DP address. The addresses of the PP 72/48 I/O modules must be set using the DIL switches S1 (see Section 7.12). SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 4-22 6FC5 397-0CP10-1BA0...
– Received data – not assigned – not assigned – not assigned – not assigned – Blanking plate for DRIVE-CLiQ interface: Molex corp., order no. 85999-3255 Siemens Automation Parts SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 4-23 6FC5 397-0CP10-1BA0...
Page 27
24 V DC ext. power supply + 24 V PROFIBUS operator P24_1 DI/DO0 panel (PCU) DI/DO1 DI/DO2 DI/DO3 P24_2 DI/DO4 DI/DO5 DI/DO6 DI/DO7 Grounding Fig. 4-1 Connection example Siemens Automation Parts SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 4-25 6FC5 397-0CP10-1BA0...
Page 28
0 → 1 signal: 15 ms (typ. 6) DI/DO6 Digital I/O 1 → 0 signal: 150 ms (typically 40) 1 → 0 signal: 150 ms (typically 40) DI/DO7 Digital I/O Ground for DI/DO4...DI/ SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 4-26 6FC5 397-0CP10-1BA0...
Page 29
2 (24 V-P-switching). Switches or proximity encoders (2 or 3-wire encoders) can be connected. Digital outputs (PCU) These fast outputs (onboard) correspond to Standard IEC 1131-2/DIN EN 61131-2 (24 V-P-switching). Siemens Automation Parts SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 4-27 6FC5 397-0CP10-1BA0...
Page 30
Interface to the PCU 48-pin plug connectors for connecting the MCPA module to the PCU X110 Assignment of the interface to the MCP Designation: X1, X2 Type: 40-pin ribbon-cable connector SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 4-28 6FC5 397-0CP10-1BA0...
Page 31
– not assigned – not assigned – not assigned – not assigned – not assigned – not assigned – not assigned – not assigned – Siemens Automation Parts SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 4-29 6FC5 397-0CP10-1BA0...
Page 32
24 V DC supply voltage Digital output 0 Digital output 1 Digital output 2 Digital output 3 Digital output 4 Digital output 5 Digital output 6 X1021 Digital output 7 Ground (GND) SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 4-30 6FC5 397-0CP10-1BA0...
Page 33
Analog drive enable (contact: electrically isolated n.o. contact) Analog Analog output 0 V Reference signal – assigned – assigned Enable 2 Analog drive enable (contact: electrically isolated n.o. contact) Siemens Automation Parts SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 4-31 6FC5 397-0CP10-1BA0...
Page 34
X111 X222 X333 I/O module interfaces X111, X222 and X333 Fig. 4-4 Position of the interfaces and status displays on the I/O module when connecting 3 terminal strip converters SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 4-32 6FC5 397-0CP10-1BA0...
Page 35
– assigned Data input/output (RS485) Transmission request 5 V reference potential 5 V power supply 90 mA, short-circuit-proof – assigned Data input/output (RS485) – assigned Siemens Automation Parts SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 4-33 6FC5 397-0CP10-1BA0...
Page 36
= 0 for connector X111; m = 3 for connector X222; m = 6 for connector X333 n = 0 for connector X111; n = 2 for connector X222; n = 4 for connector X333 SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 4-34...
Page 37
The connection cable between the voltage source and the load current supply connector and the associated reference potential M should exceed a maximum length of 10 m. Siemens Automation Parts SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 4-35 6FC5 397-0CP10-1BA0...
If an external power supply is used for the digital inputs, their reference ground must be con- nected to X111, X222, X333: pin 1 (M). In this case, X111, X222, X333: Pin 1 (P24OUT ) remains open. SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 4-36 6FC5 397-0CP10-1BA0...
Page 39
The 24 V power supply is to be designed as functional extra-low voltage with protective separation in accordance with EN60204-1, Section 6.4, PELV (with M ground). Siemens Automation Parts SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 4-37 6FC5 397-0CP10-1BA0...
Dimension drawing and drilling pattern for the machine control panel (MCP) Dimension drawing of the machine control panel (MCP) 90° ∅ 4.5 (6x) 159.8 152.2 Fig. 5-3 Dimension drawing of the machine control panel SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 5-42 6FC5 397-0CP10-1BA0...
Page 45
Drilling pattern for the machine control panel (MCP) 1) M4 rivet-down, insert nut or M4 extruded hole Fig. 5-4 Drilling pattern for the machine control panel Siemens Automation Parts SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 5-43 6FC5 397-0CP10-1BA0...
(24 + 15) = 39 mm 2) Pin for fixing the position (2∅4.7) 172.2 158.8 13.4 Fig. 5-5 Dimension drawing for the NC full keyboard (installed next to the PCU) SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 5-44 6FC5 397-0CP10-1BA0...
Page 47
2) Drill holes for fixing the position ∅ 5 mm (2x) 3) Please observe the cutting direction. Fig. 5-6 Drilling pattern for the NC full keyboard (installed next to the PCU) Siemens Automation Parts SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 5-45 6FC5 397-0CP10-1BA0...
Page 48
(24 + 15) = 39 mm 2) Pin for fixing the position (2∅4.7) 309.4 295.6 154.7 13.8 Fig. 5-7 Dimension drawing for the NC full keyboard (installed beneath the PCU) SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 5-46 6FC5 397-0CP10-1BA0...
Page 49
1) M4 rivet-down, insert nut or M4 extruded hole (8x) 2) Drill holes for fixing the position ∅ 5 mm (2x) Fig. 5-8 Drilling pattern for the NC full keyboard (installed beneath the PCU) Siemens Automation Parts SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 5-47 6FC5 397-0CP10-1BA0...
Installation Overview To install SINUMERIK 802D sl, first secure the individual components on the site of installa- tion and then connect them with each other. When doing so, observe the Section “Configu- ring the electrical design” (see Chapter 7, “Connecting”).
General rules for operation of a SINUMERIK 802D sl General rules for operation of a SINUMERIK 802D sl When integrating a SINUMERIK 802D sl into a plant, you must observe the following general rules. Starting the plant after certain events In case of ...
For the current consumption and the power loss of the individual modules, please refer to Chapter 8, “Technical Specifications”. Siemens Automation Parts SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 7-53 6FC5 397-0CP10-1BA0...
Connecting Overall design of the SINUMERIK 802D sl Overall design of the SINUMERIK 802D sl The following section provides information on the overall design of the SINUMERIK 802D sl connected to a grounded power supply. Low voltage distribution e.g. TNS system (3 x 400 V)
(installation acc. to EN 60204). If no grounding can be provided via the mounting plate, it must be connected to the central grounding point via an additional line (cross-section > 10 mm Siemens Automation Parts SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 7-55 6FC5 397-0CP10-1BA0...
Terminal strip X333 converter X200 SINAMICS S120 (max. 5 axes) Delivered length: 50 m Preassembled cable standard yard ware Single wiring Fig. 7-2 Connection overview without MCPA SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 7-56 6FC5 397-0CP10-1BA0...
Page 59
Machine control panel X333 (MCP) X200 Terminal strip converter SINAMICS S120 (max. 5 axes) Delivery length: 50 m Preassembled cable Single wiring Fig. 7-3 Connection overview with MCPA Siemens Automation Parts SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 7-57 6FC5 397-0CP10-1BA0...
Page 60
Connection overview for the SINUMERIK 802D sl Note Connect the lines as shown in Fig. 7-2 or 7-3. The preassembled cable sets from Siemens provide optimum interference immunity. For information regarding the cables (cable designations, connector types, etc.) shown in the illustrations, see:...
The variable assignment of the machine control panel is described in the PLC user interface (please refer to: Description of Functions 802Dsl). See also: PLC subroutine library V01.07.00 of SINUMERIK 802D sl. Siemens Automation Parts SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition...
Inverted incremental signal A Incremental signal A Caution The sensor power supply can be parameterized to 5 V or 24 V. The sensor may be destroyed if you enter the wrong parameters. SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 7-60 6FC5 397-0CP10-1BA0...
Make sure that the interconnecting cable between the power supply and the load power supply connection does not exceed a maximum length of 10 m (with PP72/48 I/O module only). Siemens Automation Parts SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 7-61 6FC5 397-0CP10-1BA0...
Page 64
In case of a defect in the control system, an internally installed fuse protects the electronics from collateral damage (e.g. fire). In this case, the entire control system must be replaced. SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 7-62...
Connect the female connector X9 on the CNC operator panel to the PS/2 socket on the rear of the NC full keyboard. For more information, please refer to: References: /BU/, Catalog Siemens Automation Parts SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 7-63 6FC5 397-0CP10-1BA0...
Connecting the Ethernet interface 7.10 Connecting the Ethernet interface Connect the Ethernet connection cable to the CNC operator panel, female connector X5. Make sure that the connector locks into position when connecting. SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 7-64 6FC5 397-0CP10-1BA0...
The PROFIBUS cable is a two-core, stranded and shielded cable which must not be twisted, stretched or squeezed. For more information regarding the bus connector, the bus cable and the cable length, please refer to: References: /BU/, Catalog SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 7-66 6FC5 397-0CP10-1BA0...
Page 69
Fig. 4-3). Use a screw driver to set the PROFIBUS DP address. It results from the addition of the switches to be found on the right (ON position). Siemens Automation Parts SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 7-67 6FC5 397-0CP10-1BA0...
Page 70
You can change the PROFIBUS DP address once set at any time. However, the control system will accept the newly set PROFIBUS DP address only after turning off/turning on the 24 V DC power supply. SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 7-68 6FC5 397-0CP10-1BA0...
Page 71
Connecting 7.12 Connecting the PP72/48 I/O module and the drive Networking example The diagram below shows a networking example for SINUMERIK 802D sl with two PP72/48 I/O modules. SINUMERIK 802D sl CNC operator À panel (PCU) Á 12 MBaud 1. PP72/48 2.
SMCxx module (xx depends on the type of the measuring system you are using: e.g. SMC20 with incremental encoder or SMC30 with TTL encoder). SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 7-70 6FC5 397-0CP10-1BA0...
Note To ensure optimim interference immunity when connecting sensing probes or BEROs, it is imperative to use shielded lines. The max. line length is 30 m. Siemens Automation Parts SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 7-71 6FC5 397-0CP10-1BA0...
I/O module to the terminal strip converter. The individual wiring can be performed on the ter- minal strip connectors. Remove the insulation from the cable end, insert the cable end (with end sleeve) into the screw terminal connection and tighten the fastening screw. SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 7-72 6FC5 397-0CP10-1BA0...
More information regarding the machine control panel and the pin assignment of the connectors X1201 and X1202 is to be found on the installed toolbox at: Start > Programs > Toolbox802sl > PLC802slLibrary > Description. Siemens Automation Parts SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 7-73 6FC5 397-0CP10-1BA0...
NC full keyboard (upright design) Dimensions W D [mm] Weight [g] approx. 1,700 NC full keyboard (broad format) Dimensions W D [mm] Weight [g] approx. 1,700 Siemens Automation Parts SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 8-75 6FC5 397-0CP10-1BA0...
Page 78
In addition, take into account the PROFIBUS DP communication time and the application cycle time. A polarity reversal does not cause a high signal level nor does it destroy the inputs. SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 8-76...
Page 79
S Galvanic isolation through opto-couplers S Current limited to max. 0.25 A S Protection from: – short-circuit – overtemperature – loss of grounding S automatic shutdown in case of undervoltage Siemens Automation Parts SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 8-77 6FC5 397-0CP10-1BA0...
Adobe Acrobat Reader S The mechanical and electrical installation of the system must be completed. Commissioning sequence To commission the SINUMERIK 802D sl, proceed as follows: 1. Check that the PCU boots. 2. Set the language. 3. Setting the technology 4.
Access levels Protection levels The SINUMERIK 802D sl provides a concept of protection levels for enabling data areas. There are the protection levels 0 to 7 whereby 0 is the highest and 7 the lowest level. The protection levels can be set for certain function areas (e.g. program editor) using the display machine data (USER_CLASS...).
The activation stages are listed according to their priority. If any data is changed, it comes into effect after: S POWER ON (po) Turning off/turning on the SINUMERIK 802D sl S NEW_CONF (cf) With RESET at the PLC interface (V3000 0000.7) S RESET (re) With RESET at the PLC interface (V3000 0000.7) or at the end of the...
Use the right mouse button to open the context menu dis- playing the “Properties” window. It displays the file size, the creation date and the DLL version. SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 9-82 6FC5 397-0CP10-1BA0...
CF card with a software update is inserted in the slot for the CF card. S PLC stop Select PLC Stop while the control system is booting if PLC Stop can not be triggered via the user interface any more. Siemens Automation Parts SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 9-83 6FC5 397-0CP10-1BA0...
S Use Settings > Toolbox > Select Project to select a project (1), insert front and back- ground languages (2) and create the project (3) (see Fig. 9-1). Fig. 9-1 Creating a project SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 9-84 6FC5 397-0CP10-1BA0...
(see Fig. 9-3); change if necessary. S Use Connection on to establish the connection. Siemens Automation Parts SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 9-85 6FC5 397-0CP10-1BA0...
Page 88
Tools > Toolbox Manager, using Write Data to NC. See Fig. 9-4 and Fig. 9-5. S Click OK to transfer your selection to the 802D sl. S Restart the NC. S The required language files are now active. SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 9-86 6FC5 397-0CP10-1BA0...
Page 89
Commissioning Language setting and file management Fig. 9-4 Transmitting user alarms to the control system Fig. 9-5 Transmitting the language to the control system Siemens Automation Parts SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 9-87 6FC5 397-0CP10-1BA0...
Setting the technology Note The SINUMERIK 802D sl is delivered with default machine data. In the next step, the appropriate setup file must be loaded from the toolbox into the control system. The following setup files are offered to choose from: setup_M.arc...
If you forget to save the data, the old data is effective again after the next drive reset. The machine data is activated depending on the machine data property “Activated”, Section 9.1.2. SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 9-90 6FC5 397-0CP10-1BA0...
Setting the Profibus address Setting the Profibus address Certain bus configurations have already been prepared for SINUMERIK 802D sl. The required configuration can be set via MD 11240[2]: PROFIBUS_SDB_NUMBER. Depending on the physical plant configuration, set the relevant setting data bit (SDB) accor- dingly to select the machine data 11240[2] Profibus_SDB_NUMBER.
After starting up the Profibus, the prepared PLC user program is ready to run and can be used for further start-up. To load the PLC user program, use the Programming Tool. For a description, please refer to Section 11.5. SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 9-92 6FC5 397-0CP10-1BA0...
STARTER tool. In any case, the macro must be started BEFORE commissioning the drives! Procedure: S Turn on the Sinumerik 802D sl and wait until the booting sequence is completed. S Use the System > Set Password softkeys to set the manufacturer password or higher.
Page 96
S Assign p15 a macro number. Note With SINUMERIK 802D sl, version v 01.00, up to 5 axes can be initialized. Macro 150111 – initialization of up to 6 axes + Active Line Module (ALM) + one/no BERO as zero mark equivalent Macro 150112 –...
Page 97
24 P 150111 150112 Bidir. I/O, Bero 1 – zero mark substitute” p945 = 1 1µs, smoothed 150101 150102 Ground for pins 7, 8, 10, 11 Siemens Automation Parts SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 9-95 6FC5 397-0CP10-1BA0...
Page 98
(to this end, load additonal SDB from the toolbox into the control system) P977 = Data backup of the selected SERVO components SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 9-96 6FC5 397-0CP10-1BA0...
Commissioning Configuring SINAMICS S120 with 802D sl Note For the meanings of the contents of the individual warning codes and warning values, please refer to the Manual /DG/ SINUMERIK 802D sl “Diagnostics Guide”, Chapter “Sinamics Alarms”. 9.8.4 Setpoint/actual-value assignment The axis machine data MD 30130: CTRLOUT_TYPE can be used to switch the setpoint out- put, and MD 30240: ENC_TYPE can be used to switch the actual-value input between simu- lation and PROFIBUS drive.
Note to the reader /FB/ SINUMERIK 802D sl “Description of Functions” Siemens Automation Parts SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 9-99 6FC5 397-0CP10-1BA0...
Page 102
The axis can now be traversed. The direction of movement can be reversed using MD 32100: AX_MOTION_DIR = 1 or –1 (without influencing the control direction of the position control). SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 9-100 6FC5 397-0CP10-1BA0...
Default settings of the axis machine data for the spindle With SINUMERIK 802D sl, the spindle is a subfunction of the entire axis functionality. The machine data of the spindle are therefore to be found amongst the axis machine data (MD 35xxx).
Page 104
In SINAMICS_I, the message frame type must also be set in P922 = 103. For the actual-value assignment, the following machine data must be set: SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 9-102 6FC5 397-0CP10-1BA0...
Page 105
To be able to transfer the encoder actual value, an SDB must be reloaded which reflects the hardware configuration (see Toolbox 802D_SL\V0100xx00\Special\DMSforSpindle). Thereafter, set the following machine data: Siemens Automation Parts SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 9-103 6FC5 397-0CP10-1BA0...
– If you switch to the Expert list, a list of all parameters is displayed which you can view or change. S Detailed view: This area provides detailed information, for example, on faults and warnings. Siemens Automation Parts SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 9-105 6FC5 397-0CP10-1BA0...
The appropriate drive consists, for example, of a motor (power section) and of a motor with encoder. Fig. 9-10 shows the STARTER project navigator. You can see that a project (Project_Philo- sophy) and a drive unit (Drive_Unit_One_Motor) have been configured for a drive. SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 9-106 6FC5 397-0CP10-1BA0...
Page 109
Fig. 9-11 shows the STARTER project navigator. In the same project (Project_Philosophy), a second drive unit (Device_Unit_Two_Motors), which is designed for two drives, has been configured. Siemens Automation Parts SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 9-107 6FC5 397-0CP10-1BA0...
Page 110
Commissioning STARTER start-up tool Fig. 9-11 Drive unit with two motors SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 9-108 6FC5 397-0CP10-1BA0...
10.1.2 drive properties, drive with power section, motor, encoder, and so on. Save your project. 10.1.2 Continue with “Operating the STARTER control panel (motor rotating)”. 10.2 Siemens Automation Parts SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 9-109 6FC5 397-0CP10-1BA0...
Configure and acquire the topology and configuration of the drive unit 10.3.2 automatically. Configure the motor and check the acquired topology. 10.3.3 Save your project. 10.3.3 Continue with “Operating the STARTER control panel (motor rotating)”. 10.2 SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 9-110 6FC5 397-0CP10-1BA0...
S Analysis of the control behavior using the measuring function (see Section 9.11.3) S Output of voltage signals for external measuring instruments via measuring sockets (see Section 9.11.4) Siemens Automation Parts SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 9-111 6FC5 397-0CP10-1BA0...
Any influence of overlaid closed-loop control circuits is suppressed automatically. Parameterizing and operating the function generator The function generator is parameterized and operated via the STARTER parameterization and commissioning tool. Fig. 9-12 The “Function generator” start screen SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 9-112 6FC5 397-0CP10-1BA0...
Page 115
Current Setpoint Speed Setpoint Controlled filter controller filter controller system from – – interpolator Disturbing torque funk_gen_ueber.vsd Fig. 9-13 Switching points of the function generator Siemens Automation Parts SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 9-113 6FC5 397-0CP10-1BA0...
Page 116
5. Load the settings to the target system (“Download parameters” pushbutton) 6. Start the ramp-function generator (“Start FctGen” pushbutton) To stop the function generator, proceed as follows: “Stop FctGen” pushbutton SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 9-114 6FC5 397-0CP10-1BA0...
Parameterizing and operating the trace function The trace function is parameterized and operated via the STARTER parameterization and commissioning tool. Fig. 9-16 The “Trace function” start screen Siemens Automation Parts SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 9-115 6FC5 397-0CP10-1BA0...
The “trace function” parameter screen is selected via the following icon in the toolbar of the STARTER commissioning tool: Fig. 9-17 STARTER icon for “trace function/ramp-function generator” 9.11.3 Measuring function (SERVO) (available soon) Note This functionality is available soon. SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 9-116 6FC5 397-0CP10-1BA0...
Page 119
Fig. 9-18 “Measuring function” initial screen Note Please refer to the online help for more information about parameterizing and using the measuring sockets. Siemens Automation Parts SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 9-117 6FC5 397-0CP10-1BA0...
Page 120
4. Load the settings to the target system (“Download parameters” pushbutton) 5. Start the measuring function (“Start Measuring Function” pushbutton) To stop the function generator, proceed as follows: “Stop Measuring Function” pushbutton SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 9-118 6FC5 397-0CP10-1BA0...
The “measuring function” parameter screen is selected via the following icon in the toolbar of the STARTER commissioning tool: Fig. 9-19 STARTER icon for “measuring function” 9.11.4 Measuring sockets (available soon) Note This functionality is available soon. Siemens Automation Parts SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 9-119 6FC5 397-0CP10-1BA0...
– Select the Save data softkey in the System operating area. – To save the drive mmachine data, set parameter p977=1 in the CU (SINAMICS_I). 2. Resetting the access level: – Select the Delete passw. softkey. SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 9-120 6FC5 397-0CP10-1BA0...
The trace function is selected in the System\Service display\SERVO Trace operating area. Note to the reader /BH/ SINUMERIK 802D sl “Operation and Programming”, Chapter 7 Siemens Automation Parts SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition...
Page 124
Commissioning 9.13 Service display of the axis drive behavior Notes SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 9-122 6FC5 397-0CP10-1BA0...
Project Wizard will not appear any more when the STARTER is started next time. Fig. 10-1 Main screen of the STARTER parameterization and commissioning tool Siemens Automation Parts SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 10-123 6FC5 397-0CP10-1BA0...
Page 126
3. Select the Configure drive units offline button, as shown in Fig. 10-2. Fig. 10-2 Project Wizard Starter The wizard will guide you when creating a new project. 4. Enter the project name and, if required, a comment (see Fig. 10-3). SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 10-124 6FC5 397-0CP10-1BA0...
Page 127
5. Click Continue > to set up a PPI interface in the PC/PG. Fig. 10-4 Setting up the interface 6. In this example, you need a PPI interface in the PC/PG. Choose Change and test..Siemens Automation Parts SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 10-125 6FC5 397-0CP10-1BA0...
Page 128
– For corporate networks with DHCP server, the password for protection level 1 must be entered via HMI. Use System > Service display > Service control system > Service network to change the DHCP entry to yes. SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 10-126 6FC5 397-0CP10-1BA0...
Page 129
Creating a Drive Project 10.1 Creating a drive project OFFLINE 169.254.11.22 Fig. 10-6 Features of SINAMICS Fig. 10-7 Connection properties Siemens Automation Parts SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 10-127 6FC5 397-0CP10-1BA0...
Page 130
To add the components and data listed above, use the relevant list boxes for selection and click on Insert button. Note Section 10.1.2 shows you how to configure the drive unit and its components. SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 10-128 6FC5 397-0CP10-1BA0...
Page 131
SINAMICS S120 drive unit (see Fig. 10-10). Fig. 10-10 Introduction 9. Work your way through the introduction by choosing >, or exit by choosing X. Siemens Automation Parts SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 10-129 6FC5 397-0CP10-1BA0...
Page 132
STARTER project navigator (see Fig. 10-11). Fig. 10-11 “Machine Tool V1_2” preview 10.Click Continue >. Fig. 10-12 Summary 11. To complete the process of creating a new project for a drive unit, choose Complete. SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 10-130 6FC5 397-0CP10-1BA0...
As you can see in Fig. 10-14, the STARTER opens a wizard for configuring the drive unit components. Note The graphical representation corresponds to the SINAMICS CU 320, there is no special illustration for the CU 320 integrated into the 802D sl. Siemens Automation Parts SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 10-131 6FC5 397-0CP10-1BA0...
Page 134
Fig. 10-15 Configuration – Introduction to SINAMICS CU320 3. In this example, you are using a controlled SINAMICS infeed with DRIVE-CLiQ connection, an Active Line Module. Confirm the default setting Yes by choosing Continue >. SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 10-132 6FC5 397-0CP10-1BA0...
Page 135
(order no.) (see rating plate), assign a name (Supply_1), and click the Line filter available field. 5. Click Continue > to select further data for the Active Line Module (infeed) (see Fig. 10-17). Siemens Automation Parts SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 10-133 6FC5 397-0CP10-1BA0...
Page 136
7. For the supply in your example, you want to program a free message frame configuration with BICO interconnection. Confirm the default setting Free telegram configuration with BICO by choosing Continue >. SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 10-134 6FC5 397-0CP10-1BA0...
Page 137
10.Choose Servo from the “Type of operation” listbox. 11. Assign a name for the first drive, Drive_1, and enter some general comments. Click Continue >. Siemens Automation Parts SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 10-135 6FC5 397-0CP10-1BA0...
Page 138
Fig. 10-22 Configuring the motor module 13.Select the appropriate motor module from the Motor module selection list box accor- ding to type (order no.) (see rating plate) and assign a name (Power unit). SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 10-136 6FC5 397-0CP10-1BA0...
Page 139
18. Choose “Without holding brake”. Fig. 10-23 Configuring the motor 18.Choose Without holding brake and click Continue > to select the encoder fitted to the motor (see Fig. 10-24). Siemens Automation Parts SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 10-137 6FC5 397-0CP10-1BA0...
Page 140
Select Siemens message frame 102. Fig. 10-25 Control mode/setpoints 21.For your example with the drives, you want to select the Siemens message frame 102. Select the message frame and click Continue >. Alternatively, you can select the Siemens message frame 103 if the axis possesses a direct measuring system.
Page 141
Chapter 10.2 “Starting the Drive Project (“Motor rotates)”. You will set the parameters of the interface with the drive and rotate the motor. Siemens Automation Parts SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 10-139 6FC5 397-0CP10-1BA0...
2. To use the “control panel” function, you have to switch to ONLINE mode. To switch to the ONLINE mode, click the function key Connect to target system (as shown in Fig. 10-28). SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 10-140 6FC5 397-0CP10-1BA0...
Page 143
– When the system informs you that the data was successfully loaded to the target system, click OK. – Click OK for “Load from RAM to ROM”. Siemens Automation Parts SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 10-141 6FC5 397-0CP10-1BA0...
Page 144
When loading, observe the LEDs on the control unit. The control unit is ready for operation when the LED RDY is continuously lit (green). The hardware configuration of the drive unit is completed. To operate the control panel in STARTER, proceed as follows: SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 10-142 6FC5 397-0CP10-1BA0...
(see Fig. 10-32). The control panel is displayed in STARTER (see Fig. 10-33). You can use the control panel to control the drive directly from the PC/PG. Siemens Automation Parts SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 10-143 6FC5 397-0CP10-1BA0...
Page 146
(e.g. BICO interconnection). Once control priority has been transferred to the PC, the BICO interconnections on bit 1 to bit 6 of the control word are no longer active. SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 10-144 6FC5 397-0CP10-1BA0...
Page 147
Table 4-14 lists the most important digital input signals of the control word for sequence control, which are required to set a motor to motion and which are issued via the control panel for the control unit (CU320 in 802D). Siemens Automation Parts SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 10-145 6FC5 397-0CP10-1BA0...
Page 148
6. Click Infeed control priority. The supply (Active Line Module) is turned on. 7. Before starting the motor by choosing Motor on (see Fig. 10-38), you have to make the following settings: SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 10-146 6FC5 397-0CP10-1BA0...
Page 149
10.When you click Stop, the motor stops. You can also trigger a fast stop by pressing the space bar. In the following steps, reset the master controls to disconnect the drive: – Supply – Control unit Siemens Automation Parts SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 10-147 6FC5 397-0CP10-1BA0...
Page 150
Fig. 10-42 Returning the control priority 13.Confirm the query Return control priority? with Yes (see Fig. 10-42) Now you are in the STARTER commissioning tool project, as shown in Fig. 10-43 below. SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 10-148 6FC5 397-0CP10-1BA0...
Page 151
Operating the control panel in STARTER (with the motor rotating) Fig. 10-43 Commissioning completed Congratulations! You have now successfully completed your first start-up of a drive with the SINAMICS S120 drive system. Siemens Automation Parts SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 10-149 6FC5 397-0CP10-1BA0...
Fig. 10-44 The STARTER project wizard 2. Click on the Find drive units online ..button (see Fig. 10-44). The wizard will guide you when creating a new project. SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 10-150 6FC5 397-0CP10-1BA0...
Page 153
Once the search process is completed, the Project Wizard will display the drive unit with its PPI address Drive_unit_Addr5 in the preview (see Fig. 10-47) (for alternative PC/PG interface settings, see Figs. 10-6 to 10-8). Siemens Automation Parts SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 10-151 6FC5 397-0CP10-1BA0...
Page 154
“Load drive configuration into PG/PC”. Fig. 10-47 Inserted drive unit 6. Click Continue >. The Project Wizard will list a project summary (see Fig. 10-48) Fig. 10-48 Summary SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 10-152 6FC5 397-0CP10-1BA0...
3. Select the drive unit Drive_unit_Addr5 in the Project Navigator. 4. Choose the Restore factory settings function key (see screenshot below). 4. Select Restore default settings. Fig. 10-50 Restoring the default settings Siemens Automation Parts SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 10-153 6FC5 397-0CP10-1BA0...
Page 156
7. Click on the Start automatic configuration button. STARTER will automatically search for all drive unit components connected correctly and will load them automatically into STARTER. In our case, it has detected a drive. SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 10-154 6FC5 397-0CP10-1BA0...
Page 157
The drives are listed with standard motors. If a drive is equipped with a motor with a DRIVE-CLiQ interface, the motor does not need to be configured in OFFLINE mode. Siemens Automation Parts SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 10-155 6FC5 397-0CP10-1BA0...
Page 158
The drive unit, all components and the drives are now integrated in the STARTER project. Now you must merely configure the motors of the drives and check the topology (see Section 10.3.3). SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 10-156 6FC5 397-0CP10-1BA0...
1. In the project navigator, choose the Drives folder and double-click Drive navigator under the drive. The Drive Navigator dialog box provides an overview in which you can configure the main drive functions. Siemens Automation Parts SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 10-157 6FC5 397-0CP10-1BA0...
Page 160
Click on Carry out drive configuration. Fig. 10-59 Device configuration 3. Click on Carry out drive configuration. The Project Wizard for configuring the drive is displayed (see Fig. 10-60). SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 10-158 6FC5 397-0CP10-1BA0...
Page 161
4. Work through the wizard by choosing Continue> until you reach the point at which you configure the motor (see Fig. 10-61). Note Change only the configuration of the motor. The supply etc. must not be changed! Siemens Automation Parts SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 10-159 6FC5 397-0CP10-1BA0...
Page 162
7. Click on Continue > and Continue> again to proceed with the wizard until you have come to the dialog with the summary (see Fig. 10-62 below). Note Change only the configuration of the motor. The supply etc. must not be changed! SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 10-160 6FC5 397-0CP10-1BA0...
Page 163
Before you save the project, use STARTER to check the topology you have created. Click on Check topology. Fig. 10-63 Device configuration 9. Click on Check topology. Siemens Automation Parts SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 10-161 6FC5 397-0CP10-1BA0...
Page 164
(see Fig. 10-64). 11. Choose Project > Save and save the project under the name “Project_1”. To start the motor, continue with the steps described in Section 10.2. SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 10-162 6FC5 397-0CP10-1BA0...
Monitoring can be performed using software solutions, as shown in the example MCP_802D (SBR 34) from the subroutine library. Siemens Automation Parts SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 11-163 6FC5 397-0CP10-1BA0...
Cold restart User pro- Stop unchanged Acceptance of gram *** the active and debug mode PLC MD Overall reset User pro- deleted Acceptance of gram *** the active PLC MD SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 11-164 6FC5 397-0CP10-1BA0...
Page 167
Only in the “Stop” mode can the user load a corrected or new project into the control system. The user program only becomes effective when the control system is booted the next time or if the “Run” mode is selected. Siemens Automation Parts SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 11-165 6FC5 397-0CP10-1BA0...
NCK via the user interface. S Read-in disable: Once the user program is executed, the PLC transmits the read-in disa- ble signal to the NCK via the user interface. SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 11-166 6FC5 397-0CP10-1BA0...
Other user alarms are canceled by the PLC after detecting the relevant cancel condition for the appropriate user alarms. If the bit of the user alarm, however, is still present, the alarm recurs. Siemens Automation Parts SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 11-167 6FC5 397-0CP10-1BA0...
Page 170
The % character in the alarm text denotes an additional variable. The variable type is the form of representation of the variable. The following variable types are possible: S %D integer decimal number S %I integer decimal number S %U decimal number without sign SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 11-168 6FC5 397-0CP10-1BA0...
Page 171
S 700004 ‘’ %U Alarm number with variable and fixed alarm text ‘’ S 700005 ‘’Axis monitoring active : %U’’ Display: 700005 Axis monitoring active : 1 700005 Axis monitoring active : 3 Siemens Automation Parts SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 11-169 6FC5 397-0CP10-1BA0...
PLC data types permitted in the control system Data type Size Address Range for logical operations Range for arithmetic operations alignment BOOL 1 Bit – BYTE 1 byte 00 ... FF 0 ... +255 SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 11-170 6FC5 397-0CP10-1BA0...
T16 to T39 (10 ms) Counter C0 to C31 Image of digital inputs I0.0 to I17.7 Image of digital outputs Q0.0 to Q11.7 Flags M0.0 to M383.7 Siemens Automation Parts SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 11-171 6FC5 397-0CP10-1BA0...
Page 175
The user can only view the statement list (STL) in PT802 under “View STL”. This type of representation (see Table : Mnemonic) shows the sequential processing. Siemens Automation Parts SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 11-173 6FC5 397-0CP10-1BA0...
And Byte . a t b open > =B Or Byte . Load Byte 3 a ≤ b close And Byte 3 a u b open < =B Or Byte 3 SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 11-174 6FC5 397-0CP10-1BA0...
Page 177
> =R Or RWord . Load RWord 3 a ≤ b close And RWord 3 a u b open < =R Or RWord 3 Siemens Automation Parts SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 11-175 6FC5 397-0CP10-1BA0...
Page 181
If EN = 1, exit the sub- Enable: EN from Subroutine routine. Return from Subrou- Exit subroutine. tine Conditional End If EN = 1, END termi- Enable: EN nates the main scan. Siemens Automation Parts SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 11-179 6FC5 397-0CP10-1BA0...
Page 182
VD, ID, QD, MD, AC, LD Swap Bytes If EN = 1, Enable: EN SWAP exchange MSB and VW, IW, QW, MW, T, C, AC, LW LSB of w. SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 11-180 6FC5 397-0CP10-1BA0...
(STEP7 connect active) to the control system can be checked in the “PLC/informa- tion” menu of the PLC 802 Programming Tool. If the interface is active, the active PLC mode, for example (Run/Stop) is displayed in this window. Siemens Automation Parts SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 11-181 6FC5 397-0CP10-1BA0...
S PLC program: Display and monitoring (status) of the whole user program including sym- bols and comments S PT PLC 802: It is possible to connect a PG/PC and to activate the PT connection via mo- SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 11-182 6FC5 397-0CP10-1BA0...
Export/Import user machine data alarm texts Series machine start-up application Toolbox application CF card RCS802 Series machine start-up Fig. 11-1 PLC applications in the control system Siemens Automation Parts SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 11-183 6FC5 397-0CP10-1BA0...
Page 186
The programmer can use the start of the first comment line in the comment of OB1 in the PLC 802 Programming Tool for his own supplementary information in the version display (see “View Properties”). SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 11-184 6FC5 397-0CP10-1BA0...
This interface comprises all signals exchanged between NCK/PLC and HMI/PLC. In addi- tion, the PLC decodes all auxiliary function commands for processing in the user program. Note to the reader /FB/ Sinumerik 802D sl Description of Functions, Chapter 20 Siemens Automation Parts SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition...
Page 188
Starting Up the PLC 11.6 User interface Notes SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 11-186 6FC5 397-0CP10-1BA0...
S In case of data loss of the buffered memory, the data saved in the permanent memory are automatically reloaded into the memory with POWER ON. Note Message “4062 Data backup copy has been loaded” is displayed on the screen. Siemens Automation Parts SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 12-187 6FC5 397-0CP10-1BA0...
– Start screen – Online help – HMI screens 3. Furthermore, the following data can be saved from the “Program Manager” operating area: – Manufacturer cycles – Standard cycles SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 12-188 6FC5 397-0CP10-1BA0...
On the PC, one single file will result which contains the data you have selected for backup. Note to the reader /BP/ SINUMERIK 802D sl “Operation and Programming”, Chapter 7 Data backup in the “Program Manager” operating area The data from the Program Manager > NC directory operating area are output to the RS232 in the text format.
The start-up archive (HMI) incorporates the following data: S User cycles S User directories S Language file SP1 S Language file SP2 S Start screen S Online help S HMI screens SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 12-190 6FC5 397-0CP10-1BA0...
Page 193
At the end of the series machine start-up, the whole control system will re- boot (warm start). After an error-free series machine start-up, the control system will be in a fully configured operating condition. Siemens Automation Parts SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 12-191 6FC5 397-0CP10-1BA0...
Page 194
Start-up archive (HMI) This data backup is created analogously to the start-up archive (NC/PLC). For creation and reading in, select System > 802D data > Start-up files > Start-up archive (HMI). SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 12-192 6FC5 397-0CP10-1BA0...
After turning on the control system, wait until the boot sequence is completed and press CTRL S. This will output the series machine start-up archives (NC/PLC and HMI) with the latest current data. Siemens Automation Parts SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 12-193 6FC5 397-0CP10-1BA0...
Page 196
Data Backup and Series Machine Start-Up 12.3 Data backup in case of backlight failure Notes SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition 12-194 6FC5 397-0CP10-1BA0...
Page 197
Range of values (minimum/maximum value) If no range of values is specified, the data type determines the input limits and the field is marked with “***”. Siemens Automation Parts SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition A-195 6FC5 397-0CP10-1BA0...
USER_CLASS_READ_PROGRAM decimal Protection level for “Read part program” immediately BYTE USER_CLASS_WRITE_PROGRAM decimal Protection level for “Enter part program” immediately BYTE USER_CLASS_SELECT_PROGRAM decimal Protection level for program selection immediately BYTE SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition A-196 6FC5 397-0CP10-1BA0...
Page 199
Diameter for “Transverse axis active” immediately BYTE CTM_G91_DIAMETER_ON 10 (K1) decimal Incremental feed immediately BYTE G_GROUP1 decimal User-oriented G group for position display immediately 1000 INTEGER Siemens Automation Parts SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition A-197 6FC5 397-0CP10-1BA0...
Page 200
The positions of the elements must be specified in position 4 (mathematic coordinate system). The simulation will then auto- matically convert the representation to the relevant system. CONTOUR_MASK decimal Activating the 802 contour definition programming immediately BYTE SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition A-198 6FC5 397-0CP10-1BA0...
Page 201
Activate utilization display for the spindle, limit value 2 immediately 9999999 Integer SPINDLE_LOAD_BAR_LIM3 decimal Activate utilization display for the spindle, limit value 3 immediately 9999999 Integer Siemens Automation Parts SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition A-199 6FC5 397-0CP10-1BA0...
Page 202
Protection level for “Write user cycles” immediately Byte USER_CLASS_WRITE_TO_MON_DAT decimal Protection level for “Tool monitoring” immediately Byte USER_CLASS_LADDER_VIEW decimal Protection level for “Select user ladder view” immediately Byte SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition A-200 6FC5 397-0CP10-1BA0...
Page 209
Time monitoring for the tool in the toolholder POWER ON C06, C09 – DWORD Default – – – 20360 TOOL_PARAMETER_DEF_MASK – Definition of the tool parameters POWER ON – DWORD Default – 0xFFFF Siemens Automation Parts SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition A-207 6FC5 397-0CP10-1BA0...
Page 210
Circle end point monitoring factor POWER ON – DOUBLE Default – 0.001 – – 21020 WORKAREA_WITH_TOOL_RADIUS – Tool radius with working area limitation RESET C03, C06 – BOOLEAN Default – FALSE – – SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition A-208 6FC5 397-0CP10-1BA0...
Page 211
– – – – 22254 AUXFU_ASSOC_M0_VALUE – Additional M functions for program stop POWER ON C01, C03, C10 – DWORD Default – –1 – – Siemens Automation Parts SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition A-209 6FC5 397-0CP10-1BA0...
Page 214
Sign of the rotary axis NEW CONF – BOOLEAN Default – TRUE – – 24961 TRANSMIT_POLE_SIDE_FIX_2 – Limitation of the working area in front of/after the pole NEW CONF – BYTE Default – SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition A-212 6FC5 397-0CP10-1BA0...
Machine and Setting Data 802D SINAMICS parameters SINAMICS parameters Note to the reader SINAMICS S parameter list SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition A-230 6FC5 397-0CP10-1BA0...
Page 233
SINUMERIK products are designed for use in industry. Range of application Requirements in respect of interference emission interference immunity Industry EN 50081-2: 1993 EN 61000-6-2: 1999 Siemens Automation Parts SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition B-231 6FC5 397-0CP10-1BA0...
S in plants which require special supervision, e.g. – lifts – electrical equipment in especially hazardous rooms. An additional measure for use of the control system may be, for example, the installation incabinets. SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition B-234 6FC5 397-0CP10-1BA0...
Page 237
If the control system is subjected to major impacts or vibration, appropriate measures must be taken to reduce the acceleration or the amplitude of the vibration. We recommend mounting the control system on shock-absorbing material (e.g. vibration- absorbing metal). Siemens Automation Parts SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition B-235 6FC5 397-0CP10-1BA0...
Additional measures (e.g. channel redundance, tests, checksums, etc.) must be implemented and cer- tified for the control system (DIN VDE 0801). Siemens Automation Parts SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition B-237 6FC5 397-0CP10-1BA0...
The damage resulting at a module due to an overvoltage is in most cases not detected immediately, but only noticed after a longer period of operation. Siemens Automation Parts SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition C-239 6FC5 397-0CP10-1BA0...
3 antistatic material such as wood or concrete 5 10 20 30 40 50 60 70 80 90 100 Relative humidity in % Fig. C-1 Electrostatic voltages to which an operator can be charged SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition C-240 6FC5 397-0CP10-1BA0...
If you must perform measurements at a module, discharge your body first before performing the work. To do so, touch a grounded metal object. To do so, touch grounded metal objects. Use only grounded measuring and test equipment. Siemens Automation Parts SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition C-241 6FC5 397-0CP10-1BA0...
Page 244
Directive for handling electrostatically sensitive devices (ESD) Basic protective measures against discharge of static electricity Notes SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition C-242 6FC5 397-0CP10-1BA0...
SINUMERIK 802D sl License Agreement License Agreement for the Sinumerik 802D sl Software – in the following referred to as “Software” General Terms and Conditions for the Use of Software for Sinumerik and Drive Technology This Software is protected by national and international copyright and treaties. Unauthorized...
– for the Previous Version (downgrading). If the Software is an upgrade or a PowerPack as mentioned in Point D.2.4 below, Point D.2.4 shall apply in addition. SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition D-244 6FC5 397-0CP10-1BA0...
14 days, commencing at the time when the Software was started first, unless another time of use is specified in the Order Data or in the CoL. Siemens Automation Parts SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition D-245 6FC5 397-0CP10-1BA0...
Licensee shall acquire a license in the Runtime Software according to the inten- ded type of use in accordance with the Siemens Catalog valid at this time each time when installing the Software or making copies, whichever is earlier. If the Licensee deli- vers the programs or data mentioned above for use by third parties, these must be bound in writing to the regulations of Point D.2.5 in respect of the embedded parts of the Run-...
Software. Otherwise, the provisions of the purchase contract shall apply, unless contrary provisions are specified expressly hereinafter for the Free Software. Siemens Automation Parts SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition D-247 6FC5 397-0CP10-1BA0...
License Provisions for Free Software Components License Provisions for Free Software Components In the “Sinumerik 802D sl” software, the following free software components (in the following referred to as “Free Software”) are used either in unmodified form or after modification by...
Toolbox CD under /licenses see bsd.txt on the Toolbox CD under /licenses see zlip.txt on the Toolbox CD under /licenses see lgpl.txt on the Toolbox CD under /licenses Siemens Automation Parts SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition D-249 6FC5 397-0CP10-1BA0...
Page 252
SINUMERIK 802D sl License Agreement see lgpl.txt on the Toolbox CD under /licenses Notes SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition D-250 6FC5 397-0CP10-1BA0...
Page 253
Interface standard; describes an 8-pin plug connection for twisted-pair Ethernet RS232 Serial interface RS485 Interface standard; describes the physical properties of a digital serial interface System data block Siemens Automation Parts SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition E-251 6FC5 397-0CP10-1BA0...
Page 254
Abbreviations TB 30 Terminal Board 30 Underwriters Laboratories Inc. Universal Serial Bus SINUMERIK 802D sl Instruction Manual (BA), 05/2005 Edition E-252 6FC5 397-0CP10-1BA0...
Page 262
Siemens AG Automation & Drives Motion Control Systems Postfach 3180, D–91050 Erlangen Federal Republic of Germany Siemens AG 2005 Subject to change without prior notice www.ad.siemens.com Order No. 6FC5397-0CP10-0BA0 Printed in the Federal Republic of Germany...