Honeywell Stryker VAV Operating Manual
Honeywell Stryker VAV Operating Manual

Honeywell Stryker VAV Operating Manual

Zio configuration

Advertisement

Stryker VAV Zio Configuration
OPERATING GUIDE

TABLE OF CONTENTS

Zio Configuration Scope ..................................................................................................................................2
Home Screen Options ..................................................................................................................................2
Tenant View More ..................................................................................................................................3
Contractor View - Parameter Groups ..................................................................................................................................3
Sensors ..................................................................................................................................7
Equipment Status ..................................................................................................................................9
Temperature Setpoints ..................................................................................................................................10
Override ..................................................................................................................................12
Alarms ..................................................................................................................................13
Airflow Balance ..................................................................................................................................14
Air Flow Configuration ..................................................................................................................................16
Airflow Setpoints ..................................................................................................................................16
Damper Configuration ..................................................................................................................................17
Sensor Calibration ..................................................................................................................................18
Wall Module Configuration ..................................................................................................................................19
Control Configuration ..................................................................................................................................22
Configure Universal Inputs ..................................................................................................................................24
Configure Sbus ..................................................................................................................................25
Configure Logical Inputs ..................................................................................................................................25
Configure Floating Ouput1 ..................................................................................................................................26
Configure Logical Outputs ..................................................................................................................................28
Standard Zio Configuration Functions ..................................................................................................................................31
Put Bar Code Here
63-2730-01

Advertisement

Table of Contents
loading

Summary of Contents for Honeywell Stryker VAV

  • Page 1: Table Of Contents

    Stryker VAV Zio Configuration OPERATING GUIDE TABLE OF CONTENTS Zio Configuration Scope ..........................2 Home Screen Options ..........................2 Tenant View More ..........................3 Contractor View - Parameter Groups ..........................3 Sensors ..........................7 Equipment Status ..........................9 Temperature Setpoints ..........................10 Override ..........................12 Alarms ..........................13 Airflow Balance ..........................14 Air Flow Configuration ..........................16...
  • Page 2: Zio Configuration Scope

    HOME SCREEN OPTIONS This document serves as a technical users guide for an installer who is configuring a Stryker VAV controller via a TR71 or TR75 wall module. Parameters are grouped into logical categories rather than on large list. To access the “Contractor”...
  • Page 3: Tenant View More

    STRYKER VAV ZIO CONFIGURATION TENANT VIEW MORE NOTE: To add or remove items from the Tenant View More sequence use Contractor Mode by holding the up, down and center buttons for 5 seconds. During this time the display will show the model, firmware version and Sylk bus address of the TR71/75.
  • Page 4 STRYKER VAV ZIO CONFIGURATION View equipment status data View alarm conditions Edit balancing parameters Edit Temperature Setpoints Edit Flow Configuration parameters Set overrides for the controller Edit Flow Setpoints 63-2730—01...
  • Page 5 STRYKER VAV ZIO CONFIGURATION Universal input configuration Damper Config for pressure dependent control Configure C7400S sensor Calibration of dP, Zio and C7400S sensors Wall module configuration Configure logical inputs Configuration of control parameters Configure floating output 1 63-2730—01...
  • Page 6 STRYKER VAV ZIO CONFIGURATION Configure floating output 2 View controller time Configure analog output 1 Set controller time Configure analog output 2 Set controller date Configure logical outputs Set controller schedule 63-2730—01...
  • Page 7: Sensors

    STRYKER VAV ZIO CONFIGURATION SENSORS View room temperature Parameter Group Name View room RH View Zio temperature View room CO2 View Zio relative humidity View supply air temperature 63-2730—01...
  • Page 8 STRYKER VAV ZIO CONFIGURATION View discharge air temperature View calibrated pressure (inWC only) View outdoor air temperature View Occ Sensor status View box airflow (cfm only) View Window switch View Flow Pressure un-calibrated in Pascals 63-2730—01...
  • Page 9: Equipment Status

    STRYKER VAV ZIO CONFIGURATION EQUIPMENT STATUS View reheat valve position Parameter Group Name View number of reheat stages on View damper position View periph heat valve position View airflow setpoint View number of periph stages on 63-2730—01...
  • Page 10: Temperature Setpoints

    STRYKER VAV ZIO CONFIGURATION TEMPERATURE SETPOINTS View demand limit setpoint shift Parameter Group Name View auxiliary output status Set occupied cooling setpoint [nciTempSetpoints, occupiedCool] View fan status Set occupied heating setpoint [nciTempSetpoints, occupiedHeat] View modulating fan status 63-2730—01...
  • Page 11 STRYKER VAV ZIO CONFIGURATION Set unoccupied cooling setpoint [nciTempSetpoints, View center or set Setpoint Temperature unoccupiedCool] Value range limited by WM_CONFG: CNTSP_HI, & CNTSP_LO Set unoccupied heating setpoint [nciTempSetpoints, unoccupiedHeat] Set freeze protection setpoint (heating setpoints is changed to this value when window sensor is open) [nciSpSpcFrz] Set standby cooling setpoint [nciTempSetpoints,standbyCool] View effective setpoint which displays in F or C.
  • Page 12: Override

    STRYKER VAV ZIO CONFIGURATION OVERRIDE Set modulating Fan Speed [nviFan, value] Parameter Group Name Reheat override as a percent number of stages or modulation [nviValveOvrd, reheatPos] Set damper open/closed [nviFlowOverride, state] Peripheral Heat override as a percent number of stages or...
  • Page 13: Alarms

    STRYKER VAV ZIO CONFIGURATION ALARMS [nvoApAlarm, EmergOvrd] Parameter Group Name [nvoApAlarm, HtgOvrd] All alarms have the following views [nvoApAlarm, LowFlow] Display Description FALS False trUE True [nvoApAlarm, FanOvrd] [nvoApAlarm, AirflowOvrd] [nvoApAlarm, Frost] 63-2730—01...
  • Page 14: Airflow Balance

    STRYKER VAV ZIO CONFIGURATION 4. Obtain the factory zone terminal K factor from the man- ufacturer data sheet. If the K factor is unknown, use the value 1400. 5. Navigate to PARAMETERS, FLO_CNFG, K 6. Set the factory K factor.
  • Page 15 STRYKER VAV ZIO CONFIGURATION 25. Monitor AIRFLOW value for stability at the maximum airflow setpoint value. 26. Navigate to PARAMETERS, BALANCE, MAXFLOSP 27. Set the maximum measured flow setpoint: MAXFLOSP = Avg(AIRFLOW) 28. After the airflow has settled to a stable value, measure the actual airflow with a calibrated instrument.
  • Page 16: Air Flow Configuration

    STRYKER VAV ZIO CONFIGURATION AIR FLOW CONFIGURATION K Factor listed on side of VAV box [nciKFactor] Parameter Group Name AIRFLOW SETPOINTS Pressure Dependend Flow [nciFlowLoop.PressDependent] Display Description Parameter Group Name FALS False trUE True Unoccupied flow setpoint in CFM [nciMinFlowSetpt] Area of duct in square feet [nciDuctArea] 63-2730—01...
  • Page 17: Damper Configuration

    STRYKER VAV ZIO CONFIGURATION DAMPER CONFIGURATION Pressure Dependent damper configuration Standby flow setpoint in CFM [nciStbyMinFlowSetpt] Parameter Group Name Minimum flow occupied setpoint in CFM [nciMinFlowSetpt] Unoccupied minimum damper position [nciFlowSP, UnOcMinFlowPos] Maximum occupied flow setpoint in CFM [nciMaxFlowSetpt] Standby minimum damper position [nciFlowSP,...
  • Page 18: Sensor Calibration

    STRYKER VAV ZIO CONFIGURATION SENSOR CALIBRATION Occupied minimum damper position [nciFlowSP, MinFlowPos] Parameter Group Name Maximum occupied damper position [nciFlowSP, MaxFlowPos] Pressure sensor offset in pascals Reheat damper position [nciFlowSP, ReheatFlowPos] Zio temperature offset [nciWallModZio.TempOffset] Zio humidity offset [nciWallModZio.RhOffset] 63-2730—01...
  • Page 19: Wall Module Configuration

    STRYKER VAV ZIO CONFIGURATION C7400S temperature offset [nciSbusSnsr.TempOffset] Display Home screen temp in F or C [nciWallModZio.TempUnits] C7400S humidity offset [nciSbusSnsr.RhOffset] Choose wall module type [nciWallModCom.type] Display Description WALL MODULE nOnE No Wall Module tr20 Conventional Wall Module CONFIGURATION Zio Wall Module...
  • Page 20 STRYKER VAV ZIO CONFIGURATION Center setpoint high limit [nciWallModCom, HightSetPt] Minimum heating setpoint [nciWallModCom, MinHtgSetPt] Center setpoint low limit [nciWallModCom, LowSetPt] Maximum cooling setpoint [nciWallModCom, MaxClgSetPt] Bypass time in minutes [nciWallModCom, BypassTime] Minimum cooling setpoint [nciWallModCom, MinClgSetPt] Maximum heating setpoint [nciWallModCom, MaxHtgSetPt] Effective heating high limit 63-2730—01...
  • Page 21 STRYKER VAV ZIO CONFIGURATION Display Description Stnd Standard Bypass bYPS Bypass Only dSbl Override disabled Effective heating low limit Conventional Wall Module Override Button [nciLogicalInVav, WallModOvrdBut] Display Description dI 1 digital input 1 (UI 1) None Effective cooling high limit...
  • Page 22: Control Configuration

    STRYKER VAV ZIO CONFIGURATION Display Description cooling only 1 rH 1 stage reheat 2 rH 2 stage reheat 3 rH 3 stage reheat A rH analog (mod) reheat Space Temp input [nciLogicalInVav, SpcTemp] Display Description UI_1 universal input 1 UI_2...
  • Page 23 STRYKER VAV ZIO CONFIGURATION Heating throttling range [nciHeat, TR] Configure fan type [nciFan, Type] Suggested: Display Description Type TR (F) nOnE no fan Modulating SErS Series fan 1 stage P tC Parallel fan temperature control 2 stage P AF Parallel fan airflow threshold...
  • Page 24: Configure Universal Inputs

    STRYKER VAV ZIO CONFIGURATION CONFIGURE UNIVERSAL INPUTS Configure UI 2 [nciUI2, type] Display Description Parameter Group Name 20 Kntc temperature sensor dGnO Digital Normally Open dGnC Digital Normally Closed tr_t TR20 Conventional Wall Module ntc temperature sensor Configure UI 3 [nciUI3, type]...
  • Page 25: Configure Sbus

    STRYKER VAV ZIO CONFIGURATION CONFIGURE SBUS Configure discharge air sensor [nciLogicalInVav, DschrgAirTemp] Parameter Group Name Display Description UI 1 universal input 1 UI 2 UI 3 UI 4 SbUS C7400s Sbus sensor None C7400S Temperature and humidity sylk bus sensor...
  • Page 26: Configure Floating Ouput1

    STRYKER VAV ZIO CONFIGURATION Configure outdoor air sensor [nciLogicalInVav, OdTemp] Configure window sensor [nciLogicalInVav, WindowOpen] Display Description Display Description UI 1 universal input 1 UI 1 universal input 1 UI 2 UI 2 UI 3 UI 3 UI 4 UI 4...
  • Page 27: Configure Analog Output 1 & 2

    STRYKER VAV ZIO CONFIGURATION Display Description Display Description FALS Direct Action FALS Direct Action trUE Reverse Action trUE Reverse Action Actuator travel time as a value in (seconds) [nciFloat2, Actuator travel time as a value in (seconds) [nciFloat1, travelTime] travelTime]...
  • Page 28: Configure Logical Outputs

    STRYKER VAV ZIO CONFIGURATION Display Description Display Description 0d10 0 to 10 volts (Wall Mod LED) AO_1 Analog output 1 10d0 10 to 0 volts AO_2 2d10 2 to 10 volts dO_1 Binary output 1 10d2 10 to 2 volts...
  • Page 29 STRYKER VAV ZIO CONFIGURATION Display Description Display Description AO_1 Analog output 1 AO_1 Analog output 1 AO_2 AO_2 FL_1 Floating output 1 (DO3, DO4) FL_1 Floating output 1 (DO3, DO4) FL_2 Floating output 2 (DO1, DO2) FL_2 Floating output 2 (DO1, DO2)
  • Page 30 STRYKER VAV ZIO CONFIGURATION Display Description AO_1 Analog output 1 AO_2 dO_1 Binary output 1 dO_2 dO_3 dO_4 None NOTES: If you select dO_1 or dO_2, verify that Configure Fan Binary control [nciLogicalOutVav, FanDig] Float_2_TRVL_SEC =0. This frees dO_1 & dO_2 from internal links to Float_2.
  • Page 31: Standard Zio Configuration Functions

    STRYKER VAV ZIO CONFIGURATION STANDARD ZIO CONFIGURATION FUNCTIONS Set Time Configure VAV cooling damper [nciLogicalOutVav, ClgDmpr] Display Description AO_1 Analog output 1 AO_2 Parameter Group Name FL_1 Floating output 1 (DO3, DO4) FL_2 Floating output 2 (DO1, DO2) Configure TR2X Wall Module LED [nciLogicalOutVav,...
  • Page 32 STRYKER VAV ZIO CONFIGURATION Set Date Set Schedule Parameter Group Name Parameter Group Name Select Day 63-2730—01...
  • Page 33 STRYKER VAV ZIO CONFIGURATION Edit Event Time & Occupancy State 63-2730—01...
  • Page 34 STRYKER VAV ZIO CONFIGURATION 63-2730—01...
  • Page 35 STRYKER VAV ZIO CONFIGURATION 63-2730—01...
  • Page 36 STRYKER VAV ZIO CONFIGURATION Automation and Control Solutions Honeywell International Inc. 1985 Douglas Drive North ® U.S. Registered Trademark Golden Valley, MN 55422 © 2012 Honeywell International Inc. 63-2730—01 M.S. 05-12 customer.honeywell.com Printed in United States...