VR8245 and VR8345 Universal
Electronic Ignition Gas Controls
APPLICATION
The universal electronic ignition gas controls are used in
gas-fired appliances with capacities up to 300 cu ft/hour
at 1 inch wc pressure drop [8.5 cu m/hour at 0.25 kPa] for
natural gas. These gas controls will operate with a direct
spark (DSI), hot surface (HSI) or intermittent pilot ignition.
The control includes a manual valve, two automatic
operators, a pressure regulator, pilot adjustment, pilot
plug, conduit cover and ignition adapter. Refer to the
following list for the specifications.
Size (Inlet x Outlet)
3/4 x 3/4
1/2 x 1/2
a
Capacity based on 1000 Btu/cu ft, 0.64 specific gravity natural gas at 1 in. wc pressure drop [37.3 MJ/cu m, 0.64 spe-
cific gravity natural gas at 0.25 kPa pressure drop].
Use conversion factors in Table 2 to convert capacities
for other gases.
Table 2. Gas Capacity Conversion Factors.
Gas
Specific Gravity
Manufactured
0.60
Mixed
0.70
Propane
1.53
APPROVALS:
American Gas Association Design Certificate:
L2025007.
Canadian Gas Association Design Certificate:
L2025007.
Table 1. Gas Capacity.
Capacity (at 1 in. wc
a
pressure drop)
300 cu ft/hour
[8.5 cu m/hour]
150 cu ft/hour
[4.25 cu m/hour]
Multiply Listed
Capacity By
0.516
0.765
1.62
INSTALLATION INSTRUCTIONS
SPECIFICATIONS
AMBIENT TEMPERATURE RANGE: -40° to 175°F
[-40° to 79°C].
BODY PATTERN: Straight-through.
IGNITION ADAPTER: Configures device to operate with
direct spark or hot surface ignition.
ELECTRICAL RATINGS:
Voltage and Frequency: 24 Vac, 60 Hz.
Current Draw: See Table 3.
CAPACITY: See Table 1.
Minimum Regulated
Capacity
30 cu ft/hour
[0.8 cu m/hour]
20 cu ft/hour
[0.6 cu m/hour]
PIPE ADAPTERS: Includes two 3/4 to 1/2 inch NPT
bushings and one 1/2 to 3/8 inch NPT bushing.
CROSS REFERENCE: See Table 4 for cross reference
information.
INSTALLATION
WHEN INSTALLING THIS PRODUCT...
1. Read these instructions carefully. Failure to follow
them could damage the product or cause a hazard-
ous condition.
2. Check the ratings given in the instructions and on
the product to make sure the product is suitable for
your application.
3. The installer must be a trained, experienced ser-
vice technician.
4. After installation is complete, use these instructions
to check out product operation.
Maximum Regulated
Capacity
415 cu ft/hour
[11.8 cu m/hour]
200 cu ft/hour
[5.7 cu m/hour]
69-2013