7.15.6
Current imbalance protection
This protection detects if there is imbalance in the
currents. Normally it should be same current amount in
all three phases. If the current amount is different in the
phases the engine can go bumpy.
This protection is only operational in the Top of ramp
state.
Current imbalance
protection is configured with the
following parameters:
Parameter
14.11 Curr imb level
14.12 Curr imb trip time
14.13 Curr imb delay time
14.14 Curr imb out
14.15 Curr imb operation
7.15.7
Over voltage protection
This proection detects if the main voltage is too high.
Check the main voltage.
This protection is not operational
in the Standby state.
Over voltage protection is configured with the
following parameters:
Parameter
15.01 Over voltage level
15.02 Over voltage trip time
15.03 Over voltage out
15.04 Over voltage op
7.15.8
Under voltage protection
This protection detects if the main voltage is too low.
Check the main voltage.
Under voltage protection is configured with the
following parameters:
Parameter
15.05 Under voltage level
15.06 Under voltage trip time
15.07 Under voltage op
15.08 Under voltage out
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Description
Sets the Current imbalance trip
level.
Sets the time that the Current
imbalance has to be below the trip
level to trip.
Sets the time after Top of ramp that
the protection is enabled.
Specifies the Event groups this
protection belongs to.
Sets the operation of this protection. Off, Stop manual,
Description
Sets the Over voltage trip level.
Sets the time that the voltage has to
be above the trip level to trip.
Specifies the Event groups this
protection belongs to.
Sets the operation of this protection. Off, Stop manual,
Description
Sets the Under voltage trip level.
Sets the time that the voltage has to
be below the trip level to trip.
Sets the operation of this protection. Off, Stop manual,
Specifies the Event groups this
protection belongs to.
Setting range
Default value
10 ... 80 %
80 %
1 ... 30 s

10 s

1 ... 30 s
30 s
Eventgroup 0 ...6
2
Off
Stop auto, Indication.
Setting range
Default value

170 ... 850 V

850 V
0.1 ... 100.0 s
1.0 s
Eventgroup 0 ... 6
2
Off
Stop auto, Indication.
Setting range
Default value
170 ... 850 V
208 V
0.1 ... 100.0 s
1.0 s
Off
Stop auto, Indication.
Eventgroup 0 ... 6
2
7