Page 1
Preface, Contents Product Overview and Installation SIMATIC Configuring the TD 200 TD 200 Operating the TD 200 Operator Interface Creating Sample Programs User Manual Specifications and Reference This manual has the order number: 6ES7272-0AA20-8BA0 Multiple CPU Configurations Troubleshooting TD 200 Parameters and Messages Modifying a TD 200 Configuration Index...
SIMATIC , SIMATIC HMI und SIMATIC NET Siemens AG. Copyright Siemens AG 2000 All rights reserved Disclaimer of Liability The reproduction, transmission or use of this document or its We have checked the contents of this manual for agreement with the contents is not permitted without express written authority.
Page 3
Preface Purpose The SIMATIC TD 200 Operator Interface User Manual is a combination user and reference manual that describes the operation of the TD 200 Operator Interface Module with an S7-200 programmable logic controller. Audience This manual is designed for engineers, programmers, and maintenance personnel who have a general knowledge of programmable logic controllers and operator interfaces.
Page 4
CPU scan cycle, password-protection, and network communication This manual also includes descriptions and examples for the programming instructions, typical execution times for the instructions, and the data sheets for the S7-200 equipment. SIMATIC TD 200 Operator Interface C79000-G7076-C272-01...
Page 5
+49 (911) 895-7777 nbgm.siemens.de Fax: +49 (911) 895-7001 GMT: +1:00 GMT: +01:00 The languages of the SIMATIC Hotlines are generally German and English, in addition, French, Italian and Spanish are spoken on the authorization hotline. SIMATIC TD 200 Operator Interface C79000-G7076-C272-01...
Page 6
– the Internet under http://www.ad.siemens.de/simatic Current product informations and downloads which you may find useful are available: – On the Internet at: http://www.ad.siemens.de/simatic-cs – On the Bulletin Board System (BBS) in Nuremberg ( SIMATIC Customer Support Mailbox) at the number +49 (911) 895-7100.
This manual uses the terms programmable logic controller and S7-200 CPU (or CPU) interchangeably. Chapter Overview Section Description Page Hardware Features Installing the TD 200 Connecting the Communication Cable Connecting a Power Cable Cleaning the Device 1-11 SIMATIC TD 200 Operator Interface C79000-G7076-C272-01...
The TD/CPU cable provides communication and power to your TD 200. It is a 9-pin, straight-through cable that is supplied with your TD 200. User Label The user label is a pull-out label that you can use to customize the function key labels for your applications. SIMATIC TD 200 Operator Interface C79000-G7076-C272-01...
If you press the SHIFT key along with, or prior to, pressing the F3 key, F3 sets the Mx.6 bit. Function key F4 sets the Mx.3 bit. If you press the SHIFT key along with, or prior to, pressing the F4 key, F4 sets the Mx.7 bit. SIMATIC TD 200 Operator Interface C79000-G7076-C272-01...
Tab of Label Insert SIEMENS TD 200 SIEMENS TD 200 Use tweezers to grasp tab of the label insert. Pull the label insert from the TD 200. Figure 1-2 TD 200 Keyboard Label Insert SIMATIC TD 200 Operator Interface C79000-G7076-C272-01...
Page 15
TD 200 SIEMENS TD 200 Label Insert Insert corner of label insert into Lift front panel. semi-circular cutout. Slide label insert Rotate label downward. into TD 200 front panel Figure 1-4 Inserting Customized Label SIMATIC TD 200 Operator Interface C79000-G7076-C272-01...
1. Remove the three screws from the rear of the TD 200 using a flat-head screwdriver or a T8 Torx screwdriver. See Figure 1-6. 2. Remove the backplate of the TD 200. Mounting Screws Figure 1-6 Removing the Three Mounting Screws SIMATIC TD 200 Operator Interface C79000-G7076-C272-01...
Carefully tighten the screws until snug. Spacers Gasket É É É É Gasket Backplate Frontplate É É É É Mounting Cabinet Door Screws or Control Panel Figure 1-7 Positioning Spacers SIMATIC TD 200 Operator Interface C79000-G7076-C272-01...
CPU communication, refer to Appendix B. The TD 200 defaults to address 1 and attempts to communicate to a CPU at address 2. If you use other addresses, see Section 3.8 to change the network address. SIMATIC TD 200 Operator Interface C79000-G7076-C272-01...
See “Making a Cable That Does Not Supply Power to the TD 200” on page B-4 for more information. To CPU TD 200 SIEMENS TD 200 +24 VDC Figure 1-9 Supplying Power Using an External Power Supply SIMATIC TD 200 Operator Interface C79000-G7076-C272-01...
É É É É É É É É É É É É É É É É É É É É É É É É É É É Figure 1-11 Removing the Protective Film SIMATIC TD 200 Operator Interface 1-10 C79000-G7076-C272-01...
Product Overview and Installation Cleaning the Device To clean the TD 200, use a soft cotton cloth and a neutral cleaning agent. Ensure that the cleaning agent liquid does not get into the TD 200 device. SIMATIC TD 200 Operator Interface 1-11 C79000-G7076-C272-01...
The software described in this chapter is the STEP 7–Micro/WIN Rel 3.1. Previous versions of this software may appear and operate differently. Chapter Overview Section Description Page Starting the STEP 7-Micro/WIN TD 200 Configuration Wizard Creating a Sample Program 2-19 Using the Chinese Character Set 2-21 SIMATIC TD 200 Operator Interface C79000-G7076-C272-01...
When completed, the wizard generates the supporting data block code. To begin configuring TD 200 messages, click Next. TD200 < Prev Next > Cancel 1, 1 Figure 2-1 Accessing the TD 200 Configuration Wizard SIMATIC TD 200 Operator Interface C79000-G7076-C272-01...
For example, the Latin 1 character set is the character set used by U.S. and Western European versions of Windows. PCs running this version of Windows will see the same characters in the TD 200 Configuration Wizard as on the TD 200 display. SIMATIC TD 200 Operator Interface C79000-G7076-C272-01...
Page 26
TD 200 Configuration Wizard and the data block, but they will be correct on the TD 200 display. It also happens if the font does not support all of the characters. SIMATIC TD 200 Operator Interface C79000-G7076-C272-01...
Would you like to enable the force menu on your TD 200? TD200 Would you like to enable password protection? Password (0000 - 9999): 1111 < Prev Cancel Next > Figure 2-3 Wizard: Time-of-Day Clock, Force I/O, and Password Protection SIMATIC TD 200 Operator Interface C79000-G7076-C272-01...
The update rate selection determines how often the TD 200 polls the S7-200 CPU for messages to display. The actual update time may be slower than the time that you select because of the size of the message, the processing required, or network traffic. SIMATIC TD 200 Operator Interface C79000-G7076-C272-01...
The TD 200 allows you to configure up to 80 messages. How many messages do you wish to configure? message(s) TD200 < Prev Cancel Next > Figure 2-6 Wizard: Message Size and Number of Messages SIMATIC TD 200 Operator Interface C79000-G7076-C272-01...
You must define where the message information is to reside in the data block. Starting byte for message information: < Prev Cancel Next > Figure 2-7 Wizard: Block Address, Enable Flags, and Message Location SIMATIC TD 200 Operator Interface C79000-G7076-C272-01...
Embedded Data... <Previous Message Next Message > message. VB40 is the address of MSG1, VB80 would be displayed for MSG2, and so on. < Prev Cancel Finish Figure 2-8 Wizard: 40-Character Message SIMATIC TD 200 Operator Interface C79000-G7076-C272-01...
Unsigned values are displayed without a sign. A leading zero is used for all fractional numbers (for example, 0.5). Real numbers are displayed with the number of decimal places you specify. The value is rounded to the specified decimal place. SIMATIC TD 200 Operator Interface 2-10 C79000-G7076-C272-01...
Page 33
Message enabled bit: V14.6 Embedded Data... <Previous Message Next Message > Place cursor at the correct position and click “Embedded Data...” < Prev Finish Cancel Figure 2-9 Wizard: Embedding Variable Data Value in a Message SIMATIC TD 200 Operator Interface 2-11 C79000-G7076-C272-01...
If the box is not checked, the data cannot be edited. The Embedded Data dialog box also lists the address of the data value within the message. The user program uses this address to write the data value in the message. SIMATIC TD 200 Operator Interface 2-12 C79000-G7076-C272-01...
Page 35
Message enabled bit: V14.6 Embedded Data... <Previous Message Next Message > Note: Grayed fields are place holders for embedded data values. < Prev Finish Cancel Figure 2-11 Wizard: Embedded Data Value Place Holder in Message SIMATIC TD 200 Operator Interface 2-13 C79000-G7076-C272-01...
Page 36
Should the user edit of data be Password-protected? Edit Notification Bit: V114.2 Password for Edit: 1111 Address of Data Value: VD116 Delete Cancel Figure 2-12 Embedded Data: Making the Data Editable and Password Protected. SIMATIC TD 200 Operator Interface 2-14 C79000-G7076-C272-01...
Since there is no data associated with this format word, the format word can be placed anywhere in your message (not just at the end). The format characters appear as blank spaces on the TD 200 display. SIMATIC TD 200 Operator Interface 2-15 C79000-G7076-C272-01...
Page 38
The TD 200 ignores the acknowledge bit in all subsequent data values of the message. For this example, make the selections shown in Figure 2-15 and click on the “OK” button to return to the message configuration dialog box. SIMATIC TD 200 Operator Interface 2-16 C79000-G7076-C272-01...
Page 39
Message enabled bit: V14.6 Acknowledgement notification bit: V158.1 Embedded Data... <Previous Message Next Message > Note: The address of the acknowledge- notification bit is displayed. < Prev Finish Cancel Figure 2-16 Wizard: Message Requires Acknowledgement SIMATIC TD 200 Operator Interface 2-17 C79000-G7076-C272-01...
// No Edit; Acknowledgement Notification V158.1; No Password VB159 16#00 // No Data; 0 Digits to the right of the decimal; // END TD200_BLOCK 0 Figure 2-17 Data Block Editor Showing a Sample TD 200 Parameter Block SIMATIC TD 200 Operator Interface 2-18 C79000-G7076-C272-01...
Press ENTER to edit the setpoint. Press ENTER again to go to the acknowledge message. Press ENTER to acknowledge the third message. Press F2 to enable all three messages at once. Press F3 to disable all the messages. SIMATIC TD 200 Operator Interface 2-19 C79000-G7076-C272-01...
Page 42
16#20 VB14 Network 4 V158.1 V158.1 MOV_B 16#80 VB14 Network 5 M0.1 MOV_B 16#E0 VB14 M0.1 Network 6 M0.2 MOV_B VB14 M0.2 Figure 2-18 Sample Program in the Ladder and Statement List Editors SIMATIC TD 200 Operator Interface 2-20 C79000-G7076-C272-01...
Press F1 for more information on how this might be useful. Which character set would you like your TD 200 messages to support? TD200 Simplified Chinese Chinese character set. < Prev Cancel Next > Figure 2-19 Wizard: Chinese Language and Character Set SIMATIC TD 200 Operator Interface 2-21 C79000-G7076-C272-01...
Page 44
Note: This field shows the Embedded Data... <Previous Message Next Message > address of the particular message. VB32 is the address of MSG1. < Prev Cancel Finish Figure 2-20 Wizard: Chinese Character Message SIMATIC TD 200 Operator Interface 2-22 C79000-G7076-C272-01...
Using the Display Message Mode Using the Menu Mode Viewing Messages Viewing CPU Status Menu Forcing I/O Setting Time and Date in the CPU 3-13 Releasing the Password 3-15 Using the TD 200 Setup Menu Option 3-16 SIMATIC TD 200 Operator Interface C79000-G7076-C272-01...
1. Press the DOWN arrow. The TD 200 displays the next lower priority message(s). 2. Press the UP arrow. The TD 200 displays the next higher priority message(s). 3. Press any key (except the UP or DOWN arrows). The TD 200 exits the scrolling mode. SIMATIC TD 200 Operator Interface C79000-G7076-C272-01...
“9” in “1234.56789”, the value of the variable does not change. Changing the most significant (left-most) digit of a real-number variable with more than six digits may cause other (less significant) digits in the variable to change. SIMATIC TD 200 Operator Interface C79000-G7076-C272-01...
Messages that do not require acknowledgement or editing are replaced on the display if a higher priority message is enabled by the S7-200 CPU. For more information on acknowledging a message, see Section D.5. SIMATIC TD 200 Operator Interface C79000-G7076-C272-01...
The TD 200 exits the Menu mode when you press ESC during the display of one of the menu items. Also, the TD 200 exits the Menu mode automatically after one minute and returns to the Display Message mode if you have not pressed any keys. SIMATIC TD 200 Operator Interface C79000-G7076-C272-01...
Pressing ESC at any time when you are viewing messages aborts the message display and returns you to the Display Message mode. The TD 200 automatically returns to the Display mode after one minute if no keys are pressed. SIMATIC TD 200 Operator Interface C79000-G7076-C272-01...
If fatal and/or non-fatal errors are present, use the following process to view the fatal and non-fatal errors. Action Display The TD 200 scrolls down the list of errors that are present. ERRORS PRESENT SIMATIC TD 200 Operator Interface C79000-G7076-C272-01...
Pressing ESC at any time while you are forcing I/O returns you to the Display Message mode. The TD 200 automatically returns to the Display Message mode after one minute if no keys are pressed. SIMATIC TD 200 Operator Interface C79000-G7076-C272-01...
Such a failure could result in the CPU going into fatal error mode upon next power-up. To clear the fatal error, rewrite the force information to the CPU or unforce all I/O points, then power cycle the CPU to clear the fatal error. SIMATIC TD 200 Operator Interface 3-11 C79000-G7076-C272-01...
If you wish to change the force status, press ESC to return the cursor to the I/O address. With the cursor on the I/O address, press ESC to return to the Force I/O menu. SIMATIC TD 200 Operator Interface 3-12 C79000-G7076-C272-01...
The TD 200 reads the current date and time from the CPU and displays it. The first line of the display contains the date and time. The second line of the display contains the day of the week. SIMATIC TD 200 Operator Interface 3-13 C79000-G7076-C272-01...
If you have selected Chinese for the language, the date is displayed as year-month-day. Pressing ENTER when the cursor is on the seconds field writes the new time and date to the CPU. SIMATIC TD 200 Operator Interface 3-14 C79000-G7076-C272-01...
The TD 200 enters the Menu mode. MENU MODE: VIEW MESSAGES The TD 200 scrolls down the menu MENU MODE: options four times. RELEASE PASSWORD The TD 200 returns to the ENTER password-protected operations. SIMATIC TD 200 Operator Interface 3-15 C79000-G7076-C272-01...
Use the up or down arrow keys to display the correct TD 200 ADDRESS address. Press to store the new address ENTER ENTER SETUP MENU: for the TD 200. TD 200 ADDRESS SIMATIC TD 200 Operator Interface 3-16 C79000-G7076-C272-01...
CPU. CPU ADDRESS Note Pressing ESC at any time while you are setting the network address of the CPU aborts the edit and restores the previous value of the CPU address. SIMATIC TD 200 Operator Interface 3-17 C79000-G7076-C272-01...
PARM ADDRESS Note Pressing ESC at any time while you are entering the address of the parameter block aborts the edit and restores the previous address for the parameter block. SIMATIC TD 200 Operator Interface 3-18 C79000-G7076-C272-01...
ENTER ENTER SETUP MENU: rate. BAUD RATE 19.2K Note Pressing ESC at any time while you are setting the baud rate aborts the edit and restores the previous baud rate. SIMATIC TD 200 Operator Interface 3-19 C79000-G7076-C272-01...
TD 200. HIGHEST STATION Note Pressing ESC at any time while you are setting the highest station address for the TD 200 aborts the edit and restores the previous highest station address. SIMATIC TD 200 Operator Interface 3-20 C79000-G7076-C272-01...
Factor for the TD 200. GAP FACTOR Note Pressing ESC at any time while you are selecting the GAP Factor for the TD 200 aborts the edit and restores the previous GAP Factor. SIMATIC TD 200 Operator Interface 3-21 C79000-G7076-C272-01...
SETUP MENU: value for the TD 200. CONTRAST Note Pressing ESC at any time while you are changing the Display Contrast for the TD 200 aborts the edit and restores the previous value. SIMATIC TD 200 Operator Interface 3-22 C79000-G7076-C272-01...
TD 200 display using ASCII text. A TD 200 and a CPU 224 are used to create a clock. The second program illustrates the bar graph character set. Chapter Overview Section Description Page Using a Text Message to Create a Clock for a CPU 214 Using the Bar Graph Character Set SIMATIC TD 200 Operator Interface C79000-G7076-C272-01...
When completed, the wizard will generate the supporting data block code. To begin configuring TD 200 messages, click Next. TD200 < Prev Next > Cancel 1, 1 Figure 4-1 Accessing the TD 200 Configuration Wizard SIMATIC TD 200 Operator Interface C79000-G7076-C272-01...
Page 69
// Set the starting address for message enable bits to VW12 // MESSAGE 1 // Message Enable Bit V12.7 VB20 ’ – – : : ’ // END TD200_BLOCK 0 Figure 4-2 Data Block of the Clock Message SIMATIC TD 200 Operator Interface C79000-G7076-C272-01...
Page 70
// ...convert the second VB101 MOVB 16#80, VB12 // ...enable the message VB20 VB102 VB23 VB100 VB26 VB103 VB32 VB104 VB35 VB105 VB38 MOV_B 16#80 VB12 Figure 4-3 Sample Program for Creating a Clock SIMATIC TD 200 Operator Interface C79000-G7076-C272-01...
Figure 4-5, download the data block and the program to a CPU, and place the CPU in RUN mode. Adjust potentiometer 0 to display the bar graph. Note This example does not produce an exact representation of the analog potentiometer value. The partial bars are approximate. SIMATIC TD 200 Operator Interface C79000-G7076-C272-01...
Page 72
MOVB AC1, *AC2 // store partial block to buffer MOV_B SMB28 MOV_B 16#FF VB19 BLKMOV_B VB19 VB20 SHR_DW ADD_I 16#FA MOV_DW &VB20 ADD_I MOV_B *AC2 Figure 4-5 Sample Program for Creating a Bar Graph SIMATIC TD 200 Operator Interface C79000-G7076-C272-01...
Page 73
TD 200 Original Character Set ALT Key Combinations for International and Special Characters for the TD 200 Original Character Set TD 200 Latin 1 Character Set TD 200 Cyrillic Character Set TD 200 Simplified Chinese Character Set A-10 SIMATIC TD 200 Operator Interface C79000-G7076-C272-01...
Postfach 1963 D-92209 Amberg Tel.: 09621 80 3283 Fax: 09621 80 3278 Observing the Setup Guidelines The setup guidelines and notes on safety given in the manual must be observed on startup and during operation. SIMATIC TD 200 Operator Interface C79000-G7076-C272-01...
(e.g. plug-in connections, fuses, switches). Do not close or disconnect any live circuits unless explosion hazards can be definitely excluded. Warning WARNING - DO NOT DISCONNECT WHILE CIRCUIT IS LIVE UNLESS LOCATION IS KNOWN TO BE NON-HAZARDOUS SIMATIC TD 200 Operator Interface C79000-G7076-C272-01...
Power supplies with the same voltage can only be used with additional means of protection. For example, a surge voltage protector available from the Dehn company, type RZ/E 24 V-, order No. 917 204 SIMATIC TD 200 Operator Interface C79000-G7076-C272-01...
Page 77
Semisinusoidal: 150 m/s (15g), 11 ms Transport (packaged) Semisinusoidal: 250 m/s (25g), 6 ms Special features Quality assurance In accordance with ISO 9001 Servicing Maintenance-free (no battery) Panel mounting Accessories for panel mounting are enclosed SIMATIC TD 200 Operator Interface C79000-G7076-C272-01...
The other ASCII codes other ASCII codes & are not changed. are not changed. ’ See Section D.2 for information about selecting about selecting the bar graph characters. α Ω Σ Π < SIMATIC TD 200 Operator Interface C79000-G7076-C272-01...
Specifications and Reference TD 200 Latin1 Character Set Table A-4 Latin 1 Characters for the TD 200 SIMATIC TD 200 Operator Interface C79000-G7076-C272-01...
Specifications and Reference TD 200 Cyrillic Character Set Table A-5 TD 200 Cyrillic Character Set SIMATIC TD 200 Operator Interface C79000-G7076-C272-01...
Chinese character. The alternate character set must be set to Simplified Chinese to allow the TD 200 to display Chinese characters. SIMATIC TD 200 Operator Interface A-10 C79000-G7076-C272-01...
Page 83
//Signed Word; 0 Digits to the right of the decimal; VW52 16#0 //Embedded Data Value: Move data for display here. // END TD200_BLOCK 0 Figure A-2 Data Block with Message Containing Digits for Chinese Character SIMATIC TD 200 Operator Interface A-11 C79000-G7076-C272-01...
The CPUs can be either masters or slaves on the network. Chapter Overview Section Description Page Configuring for Multiple CPU Communication Building a TD/CPU Cable CPU Grounding and Circuit Reference Point Guidelines for Using Isolated Circuits SIMATIC TD 200 Operator Interface C79000-G7076-C272-01...
TD 200 (Number 1) CPU 224 (Number 1) Address 1 Address 2 CPU 212 (Number 2) TD 200 (Number 2) Address 3 Address 4 To additional CPUs Figure B-1 A Typical Multiple CPU Network SIMATIC TD 200 Operator Interface C79000-G7076-C272-01...
Page 87
Multiple CPU Configurations Network connectors are available from Siemens. Using these connectors allows you to isolate the CPUs from one another (the 24 VDC), but still allows you to power the TD 200 from the CPU. See the SIMATIC S7-200 Programmable Controller System Manual for more information on using network connectors.
The maximum length for the cable is 1200 meters. TD 200 Side S7-200 Side Transmit/Receive Data + Transmit/Receive Data + Logic Ground Logic Ground Shield Transmit/Receive Data – Transmit/Receive Data – Figure B-3 TD/CPU Cable without Power Connections SIMATIC TD 200 Operator Interface C79000-G7076-C272-01...
Multiple CPU Configurations Network Connectors Siemens offers two types of networking connectors that you can use to connect multiple devices to a network easily. Both connectors have two sets of terminal screws to allow you to attach the incoming and outgoing network cables. Both connectors also have switches to bias and terminate the network selectively.
Table B-2 Maximum Cable Length of a Segment in a PROFIBUS Network Transmission Rate Maximum Cable Length of a Segment 9.6 kbaud to 19.2 kbaud 1,200 m (3,936 ft.) 187.5 kbaud 1,000 m (3,280 ft.) SIMATIC TD 200 Operator Interface C79000-G7076-C272-01...
Multiple CPU Configurations Network Repeaters Siemens provides network repeaters to connect PROFIBUS network segments. See Figure B-5. The use of repeaters extends the overall network length, allows you to add devices to a network, and/or provides a way to isolate different network segments.
When locating grounds, you must also consider safety grounding requirements and the proper operation of protective interrupting devices. In most installations, you will have the best noise immunity if you connect the CPU sensor supply M terminal to ground. SIMATIC TD 200 Operator Interface C79000-G7076-C272-01...
Page 93
Relay outputs are isolated from logic circuit to 1,500 VAC. Relay output groups are isolated from each other by 1,500 VAC. AC power supply line and neutral are isolated from ground, the logic circuit, and all I/O to 1,500 VAC. SIMATIC TD 200 Operator Interface C79000-G7076-C272-01...
Refer to Section B.2. Network too long or too many Refer to Section B.2. devices on network. HARDWARE ERROR TD 200 is inoperable. The TD 200 module could be defective. Replace with a new module. SIMATIC TD 200 Operator Interface C79000-G7076-C272-01...
Page 96
Use the TD 200 wizard to select selected is not supported. a valid character set. Display backlight blinks on and Software checksums are TD 200 hardware is defective. incorrect. Replace with a new TD 200. SIMATIC TD 200 Operator Interface C79000-G7076-C272-01...
TD 200 Unit 1 Parameter block at VW0 VW40 Parameter block for unit 2 SIEMENS TD 200 TD 200 Unit 2 Parameter block at VW40 Figure D-1 Displaying Different Messages on Two TD 200 Units SIMATIC TD 200 Operator Interface C79000-G7076-C272-01...
5 - Spanish 2 - German 6 - Chinese 3 - French 7 - Not defined * Values given as hexadecimal values Figure D-3 Information Contained in Byte 2 of the TD 200 Parameter Block SIMATIC TD 200 Operator Interface C79000-G7076-C272-01...
Page 101
If your program uses these bits, the program must reset these bits after they are used. Figure D-4 shows the information contained in Byte 3. SIMATIC TD 200 Operator Interface C79000-G7076-C272-01...
The highest priority message is message 1 and the lowest priority message is message 80. See Section D.5 for more information on message priorities and the display of messages. Figure D-5 shows the prioritization scheme and the correspondence between message-enable bits and messages. SIMATIC TD 200 Operator Interface C79000-G7076-C272-01...
Inadvertent changes to M bits could cause your program to behave unexpectedly. Unpredictable controller operation could cause death or serious injury to personnel, and/or damage to equipment. Always reserve an M area address, even when your program does not utilize function keys. SIMATIC TD 200 Operator Interface C79000-G7076-C272-01...
Note You can set or clear the message-enable bits from within your program. The TD 200 may also clear the message-enable bit following an acknowledge or an edit. See Section D.6 for more information. SIMATIC TD 200 Operator Interface C79000-G7076-C272-01...
The character set selection does not affect the language selection. The character set selection only affects how the character codes that STEP 7–Micro/WIN stores in the CPU data block are interpreted by the TD 200. SIMATIC TD 200 Operator Interface C79000-G7076-C272-01...
TD 200. How the Message Looks in V Memory Value Text 1 Text 2 Format Variable Word Data (word) How the Message Is Displayed on the TD 200 Figure D-7 Twenty-Character Message Format SIMATIC TD 200 Operator Interface D-10 C79000-G7076-C272-01...
Value Value Value Text 3 Format Variable Text 4 Format Variable Text 5 Word Data Word Data (word) (word) How the Message Is Displayed on the TD 200 Figure D-8 Forty-Character Message Format SIMATIC TD 200 Operator Interface D-11 C79000-G7076-C272-01...
Format Word with an Optional Double Word Value or Real (Floating-Point) Value Byte 0 Byte 1 Byte 2 Byte 3 Byte 4 Byte 5 MSB of LSB of MSB of LSB of Format Format DWord DWord Figure D-9 Format Word Usage SIMATIC TD 200 Operator Interface D-12 C79000-G7076-C272-01...
MSB of LSB of Format Format Data Data E P EN A - Acknowledgement 0 - No acknowledgement 1 - Acknowledgement required Figure D-11 Acknowledgement Bit of Byte 0 of the Format Word SIMATIC TD 200 Operator Interface D-13 C79000-G7076-C272-01...
MSB of LSB of Format Format Data Data A N - Acknowledge-Notification E P EN 0 - Not acknowledged 1 - Message Acknowledged Figure D-12 Acknowledge-Notification Bit of Byte 0 of the Format Word SIMATIC TD 200 Operator Interface D-14 C79000-G7076-C272-01...
LSB of MSB of LSB of Format Format Data Data EN- Edit-Notification 0 - Not edited E P EN 1 - Message edited Figure D-14 Edit-Notification Bit of Byte 0 of the Format Word SIMATIC TD 200 Operator Interface D-15 C79000-G7076-C272-01...
Page 112
// On each scan ... VW23 VW250 MOVWVW250,VW23 // copy the variable to the location of the Network # // embedded value. SM 0.0 MOV_W VW250 VW23 Figure D-15 Sample Program for Using the Edit-Notification Bit SIMATIC TD 200 Operator Interface D-16 C79000-G7076-C272-01...
MSB of LSB of Format Format Data Data E - Edit-Allowed 0 - Edit not allowed E P EN 1 - Edit allowed Figure D-17 Edit-Allowed Bit of Byte 0 of the Format Word SIMATIC TD 200 Operator Interface D-17 C79000-G7076-C272-01...
6 - Six digits to the right of the decimal point 7 - Seven digits to the right of the decimal point Figure D-18 Bit Values of Byte 1 of the Format Word SIMATIC TD 200 Operator Interface D-18 C79000-G7076-C272-01...
Page 115
(This includes the number of decimal places that were specified in the format word. See Figure D-18.) If a number cannot be displayed within the number of digits available, the TD 200 displays “eeeeee” for that value. SIMATIC TD 200 Operator Interface D-19 C79000-G7076-C272-01...
Page 116
123456789.1 to 1 to 7 123.4567891 -1234567891 Signed DWord -123456789.1 to 1 to 7 -123.4567891 Up to 20 -1234567 Real Real DWord 12345.6 to (Floating Point) 1 to 7 Up to 20 0.0123456 SIMATIC TD 200 Operator Interface D-20 C79000-G7076-C272-01...
CPU enables a higher priority message, the flashing message shifts to the second line of the display. The operator cannot press the UP or the DOWN key to scroll through other enabled messages until s/he acknowledges the current message. SIMATIC TD 200 Operator Interface D-21 C79000-G7076-C272-01...
TD 200 then displays the message and causes the entire message to flash to notify the operator that the message is present and must be acknowledged. For more information about editing variables, see Section D.6. SIMATIC TD 200 Operator Interface D-22 C79000-G7076-C272-01...
– To reset the variable to 0, press the SHIFT ENTER keys. 5. Press ENTER to write the updated variable to the CPU. On the same program scan, the edit-notification bit is set in the format word corresponding to the variable being edited. SIMATIC TD 200 Operator Interface D-23 C79000-G7076-C272-01...
CPU.) If the message was configured for acknowledgement, the message starts to flash again, since the edit was not completed. Note An edit is automatically aborted if you do not press a key after one minute. SIMATIC TD 200 Operator Interface D-24 C79000-G7076-C272-01...
STEP 7–Micro/WIN version that you are currently using. Chapter Overview Section Description Page Types of TD 200 Wizard Configurations Using STEP 7–Micro/WIN (version prior to 3.1) Using STEP 7–Micro/WIN (version 3.1 or greater) SIMATIC TD 200 Operator Interface C79000-G7076-C272-01...
// Character Set = Latin1 Figure E-2 Data Block Showing a Sample TD 200 Configuration Table E-1 Values to Use for Each Language Language Value to Use English German French Italian Spanish Simplified Chinese SIMATIC TD 200 Operator Interface C79000-G7076-C272-01...
Page 124
TD 200. If you are using STEP 7–Micro/WIN version 3.02 (or earlier), and you re-edit the configuration using the TD 200 Wizard, the Data Block changes are overwritten by the TD 200 Wizard. SIMATIC TD 200 Operator Interface C79000-G7076-C272-01...
You must define where the message information is to reside in the data block. Starting byte for message information: < Prev Cancel Next > Figure E-3 Wizard: Block Address, Enable Flags, and Message Location SIMATIC TD 200 Operator Interface C79000-G7076-C272-01...
D-12 Chinese character set , 2-21 format word, D-12 Chinese character set, A-10 real numbers, D-18–D-21 Cleaning the TD 200, 1-11 Date, setting, 3-13 Clock, enabling, 2-5, D-5 Decimal bits, D-18–D-21 SIMATIC TD 200 Operator Interface Index-1 C79000-G7076-C272-01...
Page 128
D-12 M area address, parameter block, 2-6, D-7 password protection, D-17 Making, cable to supply power to TD 200, Function keys, 1-3 description, 1-3 Making a cable, no power to TD 200, B-4 SIMATIC TD 200 Operator Interface Index-2 C79000-G7076-C272-01...
Page 130
Selecting display contrast, 3-22 Variables, acknowledging and editing, Selecting GAP Factor, 3-21 3-3–3-5, D-23–D-24 Set time and date menu, 3-13 Viewing CPU status menu, 3-7 Setting network address, 3-16 Viewing messages menu, 3-6 SIMATIC TD 200 Operator Interface Index-4 C79000-G7076-C272-01...
Page 131
Please check any industry that applies to you: Automotive Pharmaceutical Chemical Plastic Electrical Machinery Pulp and Paper Food Textiles Instrument and Control Transportation Nonelectrical Machinery Other _ _ _ _ _ _ _ _ _ _ _ Petrochemical SIMATIC TD 200 Operator Interface 6ES7 272-0AA20-8BA0...