Parameter
RESET_IN
STOTAL
RTOTAL
SRTOTAL
SSP
INTEG_TYPE
INTEG_OPTIONS
CLOCK_PER
PRE_TRIP
N_RESET
PCT_INC
GOOD_LIMIT
UNCERTAIN_LIMIT
OP_CMD_INT
OUTAGE_LIMIT
RESET_CONFIRM
UPDATE_EVT
BLOCK_ALM
Rev.5
Resets the totalizers
Indicates the snapshot of OUT just before a reset
Indicates the totalization of "Bad" or "Bad" and "Uncertain" inputs,
according to INTEG_OPTIONS.
The snapshot of RTOTAL just before a reset
The snapshot of TOTAL_SP.
Defines the type of counting (up or down) and the type of resetting
(demand or periodic)
A bit string to configure the type of input (rate or accumulative) used in
each input, the flow direction to be considered in the totalization, the
status to be considered in TOTAL and if the totalization residue must be
used in the next batch (only when INTEG_TYPE=UP_AUTO or
DN_AUTO).
Establishes the period for periodic reset, in hours.
Adjusts the amount of mass, volume or energy that should set
OUT_PTRIP when the integration reaches (TOTAL_SP-PRE_TRIP)
when counting up of PRE_TRIP when counting down.
Counts the number of resets. It cannot be written or reset.
Indicates the percentage of inputs with Good status compared to the
ones with Bad or Uncertain and Bad status.
Sets the limit for PCT_INC. Below this limit OUT receives the status
Good
Sets the limit for PCT_INC. Below this limit OUT receives the status
Uncertain
Operator command RESET Resets the totalizer
The maximum tolerated duration for power failure
Momentary discrete value with can be written by a host to enable
further resets, if the option "Confirm reset" in INTEG_OPTIONS is
chosen.
This alert is generated by any changes to the static data.
Used for all configuration, hardware, connection failure, or system
problems in the block. The cause of the alert is entered in the subcode
field. The first alert to become active sets the active status in the status
parameter. As soon as the unreported status is cleared by the alert
reporting task other block alerts may be reported without clearing the
Active status, if the subcode has changed.
FOUNDATION Fieldbus Option User's Manual
Description
Page 97