Speed control of a startdrive with tia portal via profibus dp with safety integrated (via terminal) and hmi (62 pages)
Summary of Contents for Siemens SINAMICS G120D
Page 3
___________________ Converter with control units CU240D-2 Changes in this manual Fundamental safety ___________________ instructions ___________________ Introduction SINAMICS ___________________ Description SINAMICS G120D ___________________ Converter with control units Installation CU240D-2 ___________________ Commissioning Operating Instructions ___________________ Adapt inputs and outputs ___________________ Configuring the fieldbus...
Page 4
Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
Important changes with respect to the Manual, 01/2013 Edition New hardware In Chapter New CU240D-2 PN-F FO Control Units with SINAMICS G120D CU240D-2 Inverter fieldbus via fiber-optic cable (Page 23) Connections and cables (Page 37) New Firmware Functions for V4.7...
Page 6
Changes in this manual Converter with control units CU240D-2 Operating Instructions, 04/2014, FW V4.7, A5E34262100B AA...
Residual risks of power drive systems ..................19 Introduction ............................21 About this manual ........................21 Guide through this manual ......................22 Description ............................23 SINAMICS G120D CU240D-2 Inverter ..................23 Commissioning tools ........................25 Motors ............................27 Installation ............................29 Mechanical Installation ......................... 29 Electrical Installation ........................
Page 8
Table of contents Restoring the factory setting ....................... 62 Basic commissioning with IOP ....................64 Basic commissioning with STARTER ..................68 5.5.1 Generating a STARTER project ....................68 5.5.2 Transfer inverters connected via USB into the project ............... 69 5.5.3 Go online and start wizard for basic commissioning ..............
Page 9
Table of contents 8.3.3 Specifying the setpoint via the fieldbus ..................115 8.3.4 Motorized potentiometer as setpoint source ................116 8.3.5 Fixed speed as setpoint source ....................118 Setpoint calculation ........................121 8.4.1 Overview of setpoint processing ....................121 8.4.2 Invert setpoint ..........................
Page 10
Table of contents 8.8.1 Function description ........................177 8.8.2 Prerequisite for STO use ......................179 8.8.3 Commissioning STO ......................... 179 8.8.3.1 Commissioning tools ......................... 179 8.8.3.2 Protection of the settings from unauthorized changes .............. 180 8.8.3.3 Resetting the safety function parameters to the factory setting ..........180 8.8.3.4 Changing settings ........................
Page 11
Technical data ............................ 253 12.1 Performance ratings Control Unit ....................253 12.2 Performance ratings Power Module................... 255 12.3 SINAMICS G120D specifications ....................256 12.4 Ambient operating conditions ..................... 257 12.5 Derating as a function of the installation altitude ............... 258 12.6 Pulse frequency and current reduction ..................
Page 12
Table of contents A.10.3 Product Support ........................293 A.10.4 Mistakes and improvements ..................... 294 Index ..............................295 Converter with control units CU240D-2 Operating Instructions, 04/2014, FW V4.7, A5E34262100B AA...
Fundamental safety instructions General safety instructions DANGER Danger to life due to live parts and other energy sources Death or serious injury can result when live parts are touched. • Only work on electrical devices when you are qualified for this job. •...
Page 14
Fundamental safety instructions 1.1 General safety instructions WARNING Danger to life when live parts are touched on damaged devices Improper handling of devices can cause damage. For damaged devices, hazardous voltages can be present at the enclosure or at exposed components;...
Page 15
Fundamental safety instructions 1.1 General safety instructions WARNING Danger to life through unexpected movement of machines when using mobile wireless devices or mobile phones Using mobile wireless devices or mobile phones with a transmit power > 1 W closer than approx.
Page 16
Fundamental safety instructions 1.1 General safety instructions NOTICE Device damage caused by incorrect voltage/insulation tests Incorrect voltage/insulation tests can damage the device. • Before carrying out a voltage/insulation check of the system/machine, disconnect the devices as all converters and motors have been subject to a high voltage test by the manufacturer, and therefore it is not necessary to perform an additional test within the system/machine.
Fundamental safety instructions 1.2 Safety instructions for electromagnetic fields (EMF) Safety instructions for electromagnetic fields (EMF) WARNING Danger to life from electromagnetic fields Electromagnetic fields (EMF) are generated by the operation of electrical power equipment such as transformers, converters or motors. People with pacemakers or implants are at a special risk in the immediate vicinity of these devices/systems.
Siemens recommends strongly that you regularly check for product updates. For the secure operation of Siemens products and solutions, it is necessary to take suitable preventive action (e.g. cell protection concept) and integrate each component into a holistic, state-of-the-art industrial security concept.
Fundamental safety instructions 1.5 Residual risks of power drive systems Residual risks of power drive systems The control and drive components of a drive system are approved for industrial and commercial use in industrial line supplies. Their use in public line supplies requires a different configuration and/or additional measures.
Page 20
Fundamental safety instructions 1.5 Residual risks of power drive systems 3. Hazardous shock voltages caused by, for example, – Component failure – Influence during electrostatic charging – Induction of voltages in moving motors – Operation and/or environmental conditions outside the specification –...
Introduction About this manual Who requires the operating instructions and what for? These operating instructions primarily address fitters, commissioning engineers and machine operators. The operating instructions describe the devices and device components and enable the target groups being addressed to install, connect-up, set, and commission the converters safely and in the correct manner.
Introduction 2.2 Guide through this manual Guide through this manual ① Inverter components and accessories. Permissible motors. Tools for commissioning. ② Install and wire the inverter and its components. Install the inverter in accordance with EMC. ③ Prepare for commissioning. Restore the inverter to factory settings.
SINAMICS G120D CU240D-2 Inverter Overview The SINAMICS G120D is a converter for controlling the speed of three-phase motors. The converter consists of two parts, the Control Unit (CU) and the Power Module (PM). Table 3- 1...
Page 24
Description 3.1 SINAMICS G120D CU240D-2 Inverter Table 3- 2 PM250D Power Modules Frame Rated output Rated output Order number size power current based on High Overload (HO) 0.75 kW 2.2 A 6SL3525-0PE17-5AA1 1.5 kW 4.1 A 6SL3525-0PE21-5AA1 3.0 kW 7.7 A 6SL3525-0PE23-0AA1 4.0 kW...
Description 3.2 Commissioning tools Commissioning tools Figure 3-1 Commissioning tools - PC or IOP Handheld Kit Converter with control units CU240D-2 Operating Instructions, 04/2014, FW V4.7, A5E34262100B AA...
Page 26
Description 3.2 Commissioning tools Table 3- 3 Components and tools for commissioning Component or tool Order number Operator Panel IOP Handheld 6SL3255-0AA00-4HA0 STARTER Commissioning tool (PC You obtain STARTER on a DVD software) (Order number: 6SL3072- 0AA00-0AG0) and it can be downloaded: STARTER (http://support.automation.sieme ns.com/WW/view/en/10804985/...
1LG6, 1LA7, 1LA9 and 1LE1 standard induction 1PH8 induction motors motors Multi-motor drive is permissible, i.e. multiple motors operated on one inverter. See also: Multi- motor drive (http://support.automation.siemens.com/WW/view/ en/84049346). SIMOTICS S 1FK7 encoderless permanent-field Motors from other manufacturers synchronous motors Standard induction motors...
Page 28
Description 3.3 Motors Table 3- 5 Constraints for operations using 1FK7 encoderless synchronous motors Property Constraint Revision level of inverter Revision level of power module ≥ B01 • Firmware version of the control unit: ≥ FW V4.7 • Applications Suitable for applications using stationary operation in the range of the rated speed of the motor : Conveyor belts •...
Installation Mechanical Installation Fitting the Control Unit to the Power Module The inverter is delivered as two separate components - the Power Module (PM) and the Control Unit (CU). The CU must be fitted to the PM prior to any further commissioning taking place.
Page 30
The inverter has an identical drill pattern for all frame sizes. The drill pattern, depth and tightening torques are shown in the diagram below. Figure 4-2 SINAMICS G120D drill pattern Converter with control units CU240D-2 Operating Instructions, 04/2014, FW V4.7, A5E34262100B AA...
Page 31
Installation 4.1 Mechanical Installation Mounting orientation Mount the converter on a table or on a wall. The minimum clearance distances are as follows: ● Side-by-side - no clearance distance is required ● Above and below the inverter 150 mm (5.9 inches). Figure 4-3 Mounting orientation: correct (✓), impermissible (X), permissible with restrictions (!) Restrictions due to vertical mounting...
Installation 4.2 Electrical Installation Electrical Installation NOTICE Material damage from inappropriate supply system V > 1% Operating the converter on an inappropriate supply system can cause damage to the converter and other loads. • Only operate the converter on supply systems with V ≤...
2.32 2.40 3.33 5.5 - 7.5 kW 3.05 3.15 4.40 For more comprehensive information on the standby current, please read the following FAQ: Standby currents for PM250D (http://support.automation.siemens.com/WW/view/en/31764702) Converter with control units CU240D-2 Operating Instructions, 04/2014, FW V4.7, A5E34262100B AA...
Installation 4.2 Electrical Installation Brake voltage The brake voltage of 180 V DC is suitable for brakes which require 400 V AC with rectifier. Remove the rectifier module and connect the brake output of the converter directly to the brake coil. The UL approved current rating for the brake output is 600 mA.
Page 35
Installation 4.2 Electrical Installation Cable shields ● Use shielded cables with finely stranded braided shields. Foil shields are not suitable since they are much less effective. ● Connect shields to the grounded housings at both ends with excellent electrical conductivity and a large contact area. ●...
Installation 4.2 Electrical Installation 4.2.4 Overview of the interfaces Intefaces of the converter ① ⑧ Digital inputs 0 … 5 with status LED HTL Encoder connection ② ⑨ Fieldbus IN and OUT (PROFINET or Analog inputs 0 and 1 PROFIBUS) ③...
Installation 4.2 Electrical Installation 4.2.5 Connections and cables DANGER Electrical shock by touching the pins in the motor terminal box The temperature sensor and motor holding brake connections are at DC link negative potential. Touching the pins in the motor terminal box can lead to death due electrical shock.
Installation 4.2 Electrical Installation Figure 4-5 CU240D-2 PROFIBUS connectors Converter with control units CU240D-2 Operating Instructions, 04/2014, FW V4.7, A5E34262100B AA...
Page 39
Installation 4.2 Electrical Installation Figure 4-6 CU240D-2 PROFINET connectors Converter with control units CU240D-2 Operating Instructions, 04/2014, FW V4.7, A5E34262100B AA...
Page 40
Installation 4.2 Electrical Installation Figure 4-7 CU240D-2 PROFINET Push-Pull connectors Converter with control units CU240D-2 Operating Instructions, 04/2014, FW V4.7, A5E34262100B AA...
Page 41
Installation 4.2 Electrical Installation Figure 4-8 CU240D-2 PROFINET FO connectors Converter with control units CU240D-2 Operating Instructions, 04/2014, FW V4.7, A5E34262100B AA...
Page 42
The detailed specifications for the cables, connectors and tools required to manufacture the necessary cables for the SINAMICS G120D are listed in the following tables. The connections that are detailed in this section relate to the physical connections that exist on the Inverter.
Page 43
3RK1902-1BA00 PROFINET Port 1 and Port 2 (M12) 6GK1901-0DB20-6AA0 3RK1902-2DA00 Encoder (M12 ) Via KnorrTec: Knorrtec (http://www.knorrtec.de/index.php/en/company- profile/siemens-solution-partner) Digital input and output, analog input (M12 ) 3RK1902-4BA00-5AA0 3RK1902-4DA00-5AA0 Table 4- 5 Push-Pull variant PROFINET and 24 V DC connectors Connector...
Page 44
Installation 4.2 Electrical Installation Cable lengths Table 4- 8 Maximum cable lengths Cable Screening Max. length Motor Screened 15 m (49 ft) Unscreened 30 m (98 ft) Temperature sensor Screened 15 m (49 ft) Unscreened 30 m (98 ft) Motor holding brake Screened 15 m (49 ft) Unscreened...
Installation 4.2 Electrical Installation 4.2.6 Connecting the motor holding brake WARNING Danger to life when live parts are touched in the motor terminal box The temperature sensor and motor holding brake connections are at DC link negative potential. Touching these connections can result in death or severe injury. •...
Installation 4.2 Electrical Installation 4.2.7 Factory settings of the inputs and outputs Factory settings of the inputs and outputs of the control unit CU240D-2 In the factory settings, the fieldbus interface of the inverter is not active. Figure 4-11 Factory settings of the control units CU240D-2 Changing the function of terminals The function of every color-coded terminal can be set.
Installation 4.2 Electrical Installation 4.2.8 Default settings of inputs and outputs Default settings of inputs and outputs (CU240D-2) Default setting 1: Two fixed speeds Default setting 2: Two fixed speeds Default setting 3: Four fixed speeds with safety function Fieldbus interface is not active. Fieldbus interface is not active.
Page 48
Installation 4.2 Electrical Installation Default setting 9: Motorized Default setting 12: Two-wire control Default setting 13: Setpoint via analog potentiometer (MOP) with method 1 input with safety function Fieldbus interface is not active. Fieldbus interface is not active. Fieldbus interface is not active. Default setting 14: Switch over between fieldbus and motorized potentiometer Default setting 24: Communication via (MOP) using DI 3...
Installation 4.2 Electrical Installation 4.2.9 Connecting the PROFINET interface Industrial Ethernet Cables and cable length Listed in the table below are the recommended Ethernet cables. Table 4- 9 Recommended PROFINET cables Max. Cable Length Order Number Industrial Ethernet FC TP 100 m (328 ft) 6XV1840-2AH10 Standard Cable GP 2 x 2...
Installation 4.2 Electrical Installation 4.2.10 Grounding converter and motor Grounding the converter ● Ground the converter via the PE connection in the mains supply connector. ● Ground the connectors as shown in the diagram below. Figure 4-12 Grounding the line supply and motor connectors •...
Installation 4.2 Electrical Installation EMC cable glands Where cable glands are used within the installation of the system, it is recommended that EMC glands are used. The cable gland provides protection to the IP68 standard when fitted correctly. Figure 4-13 Example of a Blueglobe EMC cable gland Table 4- 10 Brass-nickel plated EMC cable gland with metric thread as per EN50262.
Page 52
Installation 4.2 Electrical Installation Installation with power bus For installations with several inverters, the inverters are normally supplied from a 400 V power bus using T distributors. Figure 4-14 Inverter supplied via a power bus The following options are available for the 24 V supply of the inverter: 1.
Installation 4.2 Electrical Installation Example Figure 4-15 Fusing several inverters connected to a power bus The maximum permissible fusing of 32 A is based on the inverter with the lowest rated power of 3 kW. If the inverters are never simultaneously in operation, then also lower cable cross-sections are permissible and smaller fuses are required.
Installation 4.2 Electrical Installation 4.2.13 Connections and interference suppression All connections should be made so that they are permanent. Screwed connections on painted or anodized metal components must be made either by means of special contact washers, which penetrate the isolating surface and establish a metallically conductive contact, or by removing the isolating surface on the contact points.
Page 55
Figure 4-17 Grounding and high-frequency equipotential bonding measures in the drive system and in the plant For general rules for EMC compliant installation see also: EMC design guidelines (http://support.automation.siemens.com/WW/view/en/60612658/0/en) Converter with control units CU240D-2 Operating Instructions, 04/2014, FW V4.7, A5E34262100B AA...
Page 56
Installation 4.2 Electrical Installation Converter with control units CU240D-2 Operating Instructions, 04/2014, FW V4.7, A5E34262100B AA...
Commissioning Commissioning guidelines Procedure Proceed as follows to commission the inverter: 1. Define the requirements of your application placed on the drive. → (Page 58) . 2. Reset the inverter when required to the factory setting. → (Page 62) . 3.
Motor ● Which motor is connected to the inverter? If you are using one of the STARTER commissioning tools or Startdrive and a SIEMENS motor, then you only need the order number of the motor. Otherwise, note down the data on the motor rating plate.
Commissioning 5.2 Preparing for commissioning 5.2.1 Inverter factory setting Motor The inverter is set for an induction motor when first switching on the supply voltage or after restoring the factory settings. The motor data match the technical data of the inverter. Switching the motor on and off The inverter is set in the factory so that after it has been switched on, the motor accelerates up to its speed setpoint in 10 seconds (referred to 1500 rpm).
Commissioning 5.2 Preparing for commissioning 5.2.2 Selecting the control mode Suitable applications and typical control properties V/f control or FCC (flux current Vector control without an Vector control with encoder control) without an encoder encoder Application Horizontal conveyor technology Horizontal conveyor Vertical conveyor •...
Commissioning 5.2 Preparing for commissioning V/f control or FCC (flux current Vector control without an Vector control with encoder control) without an encoder encoder Max. output 240 Hz 200 Hz frequency Field- With induction motor: 1:2 weakening Maximum speed = 2x rated speed of With 1FK7 synchronous motor: range the motor...
Commissioning 5.3 Restoring the factory setting Restoring the factory setting There are cases where something goes wrong when commissioning a drive system e.g.: ● The line voltage was interrupted during commissioning and you were not able to complete commissioning. ● You got confused during the commissioning and you can no longer understand the individual settings that you made.
Page 63
Commissioning 5.3 Restoring the factory setting Proceed as follows to restore the inverter safety functions to the factory settings: 1. p0010 = 30Set Activate reset settings. 2. p9761 = … Enter the password for the safety functions 3. Start restoration using p970 = 5. 4.
Commissioning 5.4 Basic commissioning with IOP Basic commissioning with IOP Commissioning a 1FK7 encoderless synchronous motor If you want to operate the inverter using a 1FK7 encoderless synchronous motor, we recommend using the STARTER for commissioning. Basic commissioning wizard The Basic Commissioning wizard detailed below is for Control Units with version 4.4 software or higher.
Page 65
Commissioning 5.4 Basic commissioning with IOP Select the correct frequency for your Inverter and attached motor. The use of the 87 Hz characteristic allows the motor to operate at 1.73 times of its normal speed. At this stage the wizard will begin to ask for the data relating specifically to the attached motor.
Page 66
Commissioning 5.4 Basic commissioning with IOP 11. Input the correct Motor Speed from the motor rating plate. This value is given in RPM. 12. Select to run or disable Motor Data Identification function. This function, if active, will not start until the first run command is given to the Inverter.
Page 67
Commissioning 5.4 Basic commissioning with IOP 17. Set the Ramp Up time in seconds. This is the time the Inverter/motor system will take from being given the run command, to reaching the selected motor speed. 18. Set the Ramp Down time in seconds. This is the time the Inverter/motor system will take from being given the OFF1 command, for the motor to reach a standstill.
Basic commissioning with STARTER STARTER and STARTER screen forms STARTER is a PC-based tool to commission Siemens inverters. The graphic user interface of STARTER supports you when commissioning your inverter. Most inverter functions are combined in screen forms in STARTER.
Commissioning 5.5 Basic commissioning with STARTER 5.5.2 Transfer inverters connected via USB into the project Procedure Proceed as follows to transfer an inverter connected via USB into your project: 1. Switch on the inverter power supply. 2. First insert a USB cable into your PC and then into the inverter. 3.
Commissioning 5.5 Basic commissioning with STARTER You have set the USB interface. STARTER now shows the inverters connected via USB. 5.5.3 Go online and start wizard for basic commissioning Procedure Proceed as follows to start the basic commissioning online with the converter: 1.
Commissioning 5.5 Basic commissioning with STARTER 5.5.4 Carry-out basic commissioning Procedure Proceed as follows to carry out basic commissioning: Select the control mode. See also Section: Selecting the control mode (Page 60) Select the pre-assignment of the inverter interfaces. The possible configurations can be found in sections: Factory settings of the inputs and outputs (Page 46) and Default settings of inputs and outputs (Page 47).
Commissioning 5.5 Basic commissioning with STARTER If you use an HTL encoder on the motor shaft for the speed control of the converter, either select one of the standard encoders or enter the encoder data. See also Section: Adapting the encoder data (Page 72). …R: Encoder with zero mark 10.
Commissioning 5.5 Basic commissioning with STARTER 3. You have access to the following settings in the "Encoder data" screen form: – You can change all of the encoder data. – You can select another encoder. In this screen form, STARTER only lists the encoder types, which are permitted for the configured interface.
Page 74
Commissioning 5.5 Basic commissioning with STARTER DANGER Risk of injury or material damage as a result of machine movements when switching on the motor Switching on the motor for identification purposes may result in hazardous machine movements. Secure dangerous machine parts before starting motor data identification: •...
Adapt inputs and outputs This chapter describes how you adapt the function of individual digital and analog inputs and outputs of the inverter. If you adapt the function of an input or output, you overwrite the settings made during the basic commissioning.
Adapt inputs and outputs 6.1 Digital inputs Digital inputs Changing the function of a digital input Interconnect the status parameter of the digital input with a binector input of your choice. Binector inputs are marked with "BI" in the parameter list of the List Manual.
Page 77
Adapt inputs and outputs 6.1 Digital inputs Advanced settings You can debounce the digital input signal using parameter p0724. For more information, see the parameter list and the function block diagrams 2210 ff of the List Manual. Analog inputs as digital inputs When required, you can use the analog inputs as additional digital inputs.
Adapt inputs and outputs 6.2 Fail-safe digital input Fail-safe digital input This manual describes the STO safety function with control using a fail-safe input. Additional safety functions, additional fail-safe digital inputs, the fail-safe digital output of the converter and the control of the safety functions using PROFIsafe are described in the Safety Integrated Function Manual.
Page 79
Adapt inputs and outputs 6.2 Fail-safe digital input Special measures when establishing connections When routing cables over longer distances, e.g. between remote control cabinets, you have the following options to reduce the risk of damaged cables of your plant or machine: ●...
Adapt inputs and outputs 6.3 Digital outputs Digital outputs Changing the function of a digital output Interconnect the digital output with a binector output of your choice. Binector outputs are marked with "BO" in the parameter list of the List Manual. Table 6- 2 Binector outputs of the inverter (selection) Deactivating digital output...
Adapt inputs and outputs 6.4 Analog inputs Analog inputs Overview Changing the function of the analog input 1. Define the analog input type using parameter p0756 to voltage input 0 V … 10 V. 2. Specify the function of the analog input by interconnecting parameter p0755 with a connector input CI of your choice.
Page 82
Adapt inputs and outputs 6.4 Analog inputs Defining the analog input function You define the analog input function by interconnecting a connector input of your choice with parameter p0755 . Parameter p0755 is assigned to the particular analog input via its index, e.g.
Configuring the fieldbus Fieldbus versions of the Control Unit Fieldbus interfaces of the Control Units There are different versions of the Control Units for communication with a higher-level control system: Fieldbus Profiles S7 communi- Control Unit cation PROFIdrive PROFIsafe PROFIenergy PROFIBUS ✓...
Configuring the fieldbus 7.2 Communication via PROFINET Communication via PROFINET You can either communicate via Ethernet using the inverter, or integrate the inverter in a PROFINET network. ● The inverter as an Ethernet station (Page 292) ● PROFINET IO operation (Page 85) In PROFINET IO operation, the inverter supports the following functions: –...
– The configuration of the functions is described in the PROFINET system description (http://support.automation.siemens.com/WW/view/en/19292127) manual. This manual describes the control of the inverter using primary control. How to access the inverter as an Ethernet station is described in the Fieldbus function manual (Page 292) in the section "The inverter as an Ethernet station".
Additional information on this topic is provided in the "Fieldbuses" Function Manual, also see Manuals for your converter (Page 292). Configuring the communication using a non-Siemens control 1. Import the device file (GSDML) of the inverter into the configuring tool of your control system.
350: SIEMENS telegram 350, PZD-4/4 352: SIEMENS telegram 352, PZD-6/6 353: SIEMENS telegram 353, PZD-2/2, PKW-4/4 354: SIEMENS telegram 354, PZD-6/6, PKW-4/4 999: Extend telegrams and change signal interconnection (Page 98) A more detailed depiction of the individual telegrams can be found in Section Cyclic communication (Page 91).
Configuring the fieldbus 7.3 Communication via PROFIBUS Communication via PROFIBUS 7.3.1 What do you need for communication via PROFIBUS? Check the communication settings using the following table. If you answer "Yes" to the questions, you have correctly set the communication settings and can control the converter via the fieldbus.
● If the inverter is not listed in the hardware library, you can either install the newest STARTER version or install the GSD of the inverter through "Extras/GSD-Install file" in HW-Config. See also GSD (http://support.automation.siemens.com/WW/view/en/22339653/133100). When you have installed the GSD, configure the communication in the SIMATIC control. 7.3.4...
Page 90
350: SIEMENS telegram 350, PZD-4/4 352: SIEMENS telegram 352, PZD-6/6 353: SIEMENS telegram 353, PZD-2/2, PKW-4/4 354: SIEMENS telegram 354, PZD-6/6, PKW-4/4 999: Cyclic communication (Page 91) A more detailed depiction of the individual telegrams can be found in Section Extend telegrams and change signal interconnection (Page 98).
Configuring the fieldbus 7.4 PROFIdrive profile for PROFIBUS and PROFINET PROFIdrive profile for PROFIBUS and PROFINET 7.4.1 Cyclic communication The send and receive telegrams of the inverter for the cyclic communication are structured as follows: Figure 7-1 Telegrams for cyclic communication Converter with control units CU240D-2 Operating Instructions, 04/2014, FW V4.7, A5E34262100B AA...
Page 92
Configuring the fieldbus 7.4 PROFIdrive profile for PROFIBUS and PROFINET Table 7- 1 Explanation of the abbreviations Abbreviation Explanation Abbreviation Explanation Control word MIST_GLAT Actual smoothed torque Status word PIST_GLAT Actual smoothed active power NSOLL_A Speed setpoint M_LIM Torque limit value NIST_A Speed actual value FAULT_CO...
Configuring the fieldbus 7.4 PROFIdrive profile for PROFIBUS and PROFINET Figure 7-3 Interconnection of the receive words The telegrams use - with the exception of telegram 999 (free interconnection) - the word-by- word transfer of send and receive data (r2050/p2051). If you require an individual telegram for your application (e.g.
Page 94
Configuring the fieldbus 7.4 PROFIdrive profile for PROFIBUS and PROFINET Significance Explanation Signal interconnection Telegram 20 All other in the inverter telegrams 0 = OFF1 The motor brakes with the ramp-down time p1121 of the p0840[0] = ramp-function generator. The inverter switches off the motor r2090.0 at standstill.
Page 95
Configuring the fieldbus 7.4 PROFIdrive profile for PROFIBUS and PROFINET Status word 1 (ZSW1) The status word 1 is pre-assigned as follows. ● Bit 0 … 10 corresponds to PROFIdrive profile ● Bit 11… 15 manufacturer-specific Bit Significance Comments Signal interconnection Telegram 20 All other telegrams...
Configuring the fieldbus 7.4 PROFIdrive profile for PROFIBUS and PROFINET 7.4.1.2 Control and status word 3 Control word 3 (STW3) The control word 3 is pre-assigned as follows. ● Bit 0… 15 manufacturer-specific Bit Value Significance Explanation Signal interconnection in the inverter Telegram 350 Fixed setpoint, bit 0 Selects up to 16 different fixed setpoints.
Page 97
Configuring the fieldbus 7.4 PROFIdrive profile for PROFIBUS and PROFINET Status word 3 (ZSW3) The status word 3 is pre-assigned as follows. ● Bit 0… 15 manufacturer-specific Bit Value Significance Description Signal interconnection in the inverter DC braking active p2051[3] = r0053 |n_act| >...
Standard telegram 20, PZD-2/6 350: SIEMENS telegram 350, PZD-4/4 352: SIEMENS telegram 352, PZD-6/6 353: SIEMENS telegram 353, PZD-2/2, PKW-4/4 354: SIEMENS telegram 354, PZD-6/6, PKW-4/4 r2050[0…11] PROFIdrive PZD receive word Connector output to interconnect the PZD (setpoints) in the word format received from the PROFIdrive controller.
Page 99
Configuring the fieldbus 7.4 PROFIdrive profile for PROFIBUS and PROFINET Freely selecting the signal interconnection of the telegram The signals in the telegram can be freely interconnected. Procedure Proceed as follows to change the signal interconnection of a telegram: 1. Using STARTER or an operator panel, set parameter p0922 = 999. 2.
Configuring the fieldbus 7.4 PROFIdrive profile for PROFIBUS and PROFINET 7.4.1.4 Data structure of the parameter channel Structure of the parameter channel The parameter channel consists of four words. 1. and 2nd word transfer the parameter number and index as well as the type of job (read or write) The 3rd and 4th word contains the parameter contents.
Page 101
Configuring the fieldbus 7.4 PROFIdrive profile for PROFIBUS and PROFINET Table 7- 3 Response identifiers, inverter → control Response Description identifier No response Transfer parameter value (word) Transfer parameter value (double word) Transfer descriptive element Transfer parameter value (field, word) Transfer parameter value (field, double word) Transfer number of field elements Inverter cannot process the request.
Page 102
Configuring the fieldbus 7.4 PROFIdrive profile for PROFIBUS and PROFINET Description 86 hex Write access only for commissioning (p0010 = 15) (operating status of the inverter prevents a parameter change) 87 hex Know-how protection active, access locked C8 hex Change request below the currently valid limit (change request to a value that lies within the "absolute"...
Page 103
Configuring the fieldbus 7.4 PROFIdrive profile for PROFIBUS and PROFINET Parameter contents Parameter contents can be parameter values or connectors. Table 7- 5 Parameter values in the parameter channel PWE, 3rd word PWE, 4th word Bit 15 … 0 Bit 15 … 8 Bit 7 …...
Page 104
● PWE2, bit 0 … 9: = 2 hex (index of parameter (DI 2 = 2)) Figure 7-6 Telegram, to assign DI 2 with ON/OFF1 "Reading and writing parameters" application example See: Reading and writing parameters via PROFIBUS (http://support.automation.siemens.com/WW/view/en/8894584). Converter with control units CU240D-2 Operating Instructions, 04/2014, FW V4.7, A5E34262100B AA...
Configuring the fieldbus 7.4 PROFIdrive profile for PROFIBUS and PROFINET 7.4.1.5 Slave-to-slave communication "Direct data exchange" is sometimes called "slave-to-slave communication" or "data exchange broadcast". Here, slaves exchange data without any direct involvement of the master. You can find more information in: "Manuals for your inverter in the fieldbus communications manual (Page 292)".
Page 106
Configuring the fieldbus 7.4 PROFIdrive profile for PROFIBUS and PROFINET Converter with control units CU240D-2 Operating Instructions, 04/2014, FW V4.7, A5E34262100B AA...
Setting functions Overview of the converter functions Figure 8-1 Overview of inverter functions Converter with control units CU240D-2 Operating Instructions, 04/2014, FW V4.7, A5E34262100B AA...
Page 108
Setting functions 8.1 Overview of the converter functions Functions relevant to all applications Functions required in special applications only The functions that you require in each application are shown The functions whose parameters you only need to adapt in a dark color in the function overview above. when actually required are shown in white in the function overview above.
Setting functions 8.2 Inverter control Inverter control 8.2.1 Switching the motor on and off After switching the supply voltage on, the converter normally goes into the "ready to start" state. In this state, the converter waits for the command to switch-on the motor: •...
Setting functions 8.2 Inverter control The abbreviations S1 … S5b to identify the converter states are defined in the PROFIdrive profile. Converter Explanation status In this state, the converter does not respond to the ON command. The converter goes into this state under the following conditions: ON was active when switching on the converter.
Page 111
Setting functions 8.2 Inverter control The inverter must be ready to start before you issue the "Jog" control command. If the motor is already switched on, then the "Jog" command has no effect. Jog settings Parameter Description p1058 Jogging 1 speed setpoint (factory setting 150 rpm) p1059 Jogging 2 speed setpoint (factory setting -150 rpm) p1082...
Setting functions 8.2 Inverter control 8.2.3 Switching over the inverter control (command data set) In several applications, the inverter must be able to be operated from different, higher-level control systems. Example: You control the motor either from a central control system, via fieldbus or from a local control panel.
Page 113
Setting functions 8.2 Inverter control An overview of all the parameters that belong to the command data sets is provided in the List Manual. Note The converter requires approx. 4 ms to switch over the command data set. Advanced settings To change the number of command data sets in STARTER, you must open your STARTER project offline.
Setting functions 8.3 Setpoints Setpoints 8.3.1 Overview The inverter receives its main setpoint from the setpoint source. The main setpoint generally specifies the motor speed. Figure 8-6 Setpoint sources for the inverter You have the following options when selecting the source of the main setpoint: ●...
Setting functions 8.3 Setpoints 8.3.2 Analog input as setpoint source Interconnecting an analog input If you have selected a pre-assignment without a function of the analog input, then you must interconnect the parameter of the main setpoint with an analog input. Figure 8-7 Example: Analog input 0 as setpoint source Table 8- 1...
Setting functions 8.3 Setpoints 8.3.4 Motorized potentiometer as setpoint source The "Motorized potentiometer" function emulates an electromechanical potentiometer. The output value of the motorized potentiometer can be continually set using the "up" and "down" control signals. Interconnecting the motorized potentiometer (MOP) with the setpoint source Figure 8-9 Motorized potentiometer as setpoint source Table 8- 3...
Page 117
Setting functions 8.3 Setpoints Table 8- 5 Extended setup of motorized potentiometer Parameter Description p1030 MOP configuration (factory setting: 00110 bin) Parameter value with five independently adjustable bits 00 … 04 Bit 00: Save setpoint after switching off motor 0: After the motor is switched on, p1040 is specified as the setpoint 1: Setpoint is saved after the motor is switched off and set to the saved value once it is switched on Bit 01: Configure ramp-function generator in automatic mode (1-signal via BI: p1041)
Setting functions 8.3 Setpoints 8.3.5 Fixed speed as setpoint source In many applications after switching on the motor, all that is needed is to run the motor at a constant speed or to switch between different speeds. Example: After it has been switched on, a conveyor belt only runs with two different velocities.
Page 119
Setting functions 8.3 Setpoints Additional information about direct selection can be found in function diagram 3011 in the List Manual. 2. Binary selection: You set 16 different fixed setpoints. You precisely select one of these 16 fixed setpoints by a combination of four selection bits. Additional information about binary selection can be found in function diagram 3010 in the List Manual.
Page 120
Setting functions 8.3 Setpoints Example: Select two fixed setpoints directly The motor should operate at different speeds as follows: ● The signal on digital input 0 switches the motor on and accelerates it to 300 rpm. ● The signal at digital input 1 accelerates the motor to 2000 rpm. ●...
Setting functions 8.4 Setpoint calculation Setpoint calculation 8.4.1 Overview of setpoint processing The setpoint can be modified as follows using the setpoint processing: ● Invert setpoint to reverse the motor direction of rotation (reversing). ● Inhibit positive or negative direction of rotation, e.g. for conveyor belts, pumps or fans. ●...
Setting functions 8.4 Setpoint calculation 8.4.2 Invert setpoint The inverter provides an option to invert the setpoint sign using a bit. As an example, the setpoint inversion is shown through a digital input. In order to invert the setpoint through the digital input DI 1, connect the parameter p1113 with a binary signal, e.g.
Setting functions 8.4 Setpoint calculation 8.4.4 Skip frequency bands and minimum speed Skip frequency bands The converter has four skip frequency bands that prevent continuous motor operation within a specific speed range. You can find additional information in function diagram 3050 of the List Manual, see also: Manuals for your converter (Page 292).
Setting functions 8.4 Setpoint calculation 8.4.5 Speed limitation The maximum speed limits the speed setpoint range for both directions of rotation. The converter generates a message (fault or alarm) when the maximum speed is exceeded. If you must limit the speed depending on the direction of rotation, then you can define speed limits for each direction.
Setting functions 8.4 Setpoint calculation 8.4.6 Ramp-function generator The ramp-function generator in the setpoint channel limits the rate that the speed setpoint changes. As a consequence the motor accelerates and brakes more softly, reducing the stress on the mechanical system of the driven machine. You can select between two different ramp-function generator types: ●...
Page 126
Setting functions 8.4 Setpoint calculation Table 8- 13 Additional parameters to set the extended ramp-function generator Parameter Description p1115 Ramp-function generator selection (factory setting: 1) Select ramp-function generator: 0: Basic ramp-function generator 1: Extended ramp-function generator p1120 Ramp-function generator, ramp-up time (factory setting: 10 s) Accelerating time in seconds from zero speed up to the maximum speed p1082 p1121 Ramp-function generator, ramp-down time (factory setting: 10 s)
Page 127
Setting functions 8.4 Setpoint calculation Setting the extended ramp-function generator Procedure Proceed as follows to set the extended ramp-function generator: 1. Enter the highest possible speed setpoint. 2. Switch on the motor. 3. Evaluate your drive response. – If the motor accelerates too slowly, then reduce the ramp-up time. An excessively short ramp-up time means that the motor will reach its current limiting when accelerating, and will temporarily not be able to follow the speed setpoint.
Page 128
Setting functions 8.4 Setpoint calculation Basic ramp-function generator When compared to the extended ramp- function generator, the basic ramp- function generator has no rounding times. Table 8- 14 Parameters for setting the ramp-function generator Parameter Description p1115 = 0 Ramp-function generator selection (factory setting: 1) Select ramp-function generator: 0: Basic ramp-function generator 1: Extended ramp-function generator...
Page 129
Setting functions 8.4 Setpoint calculation Example In the following example, the higher-level control sets the ramp-up and ramp-down times of the inverter via PROFIBUS. Figure 8-14 Example for changing the ramp-function generator times in operation Preconditions ● You have commissioned the communication between the inverter and the control system. ●...
Setting functions 8.5 Motor control Motor control Decision-making criteria for the control mode that is suitable for your application is provided in Section Selecting the control mode (Page 60) 8.5.1 V/f control U/f control sets the voltage at the motor terminals on the basis of the specified speed setpoint.
Setting functions 8.5 Motor control 8.5.1.1 Characteristics of U/f control The converter has several U/f characteristics. Based on the characteristic, as the frequency increases, the converter increases the voltage at the motor. ① The voltage boost of the characteristic improves motor behavior at low speeds. The voltage boost is effective for frequencies <...
Page 132
Setting functions 8.5 Motor control The converter increases its output voltage – also above the motor rated speed up to the maximum output voltage. The higher the line voltage, the greater the maximum converter output voltage. If the converter has reached its maximum output voltage, then it can only increase its output frequency.
Setting functions 8.5 Motor control 8.5.1.2 Selecting the U/f characteristic Table 8- 16 Linear and parabolic characteristics Requirement Application examples Remark Characteristic Parameter The required Conveyor belts, roller Linear p1300 = 0 torque is conveyors, chain The inverter equalizes the voltage drops Linear with Flux p1300 = 1 independent of the...
Setting functions 8.5 Motor control 8.5.1.3 Optimizing with a high break loose torque and brief overload Setting the voltage boost for U/f control The voltage boost acts on every U/f characteristic. The adjacent diagram shows the voltage boost using a linear characteristic as example.
Setting functions 8.5 Motor control 8.5.2 Vector control Sensorless vector control Using a motor model, the vector control calculates the load and the motor slip. As a result of this calculation, the converter controls its output voltage and frequency so that the motor speed follows the setpoint, independent of the motor load.
Setting functions 8.5 Motor control 8.5.2.1 Checking the encoder signal If you use an encoder to measure the speed, you should check the encoder signal before the encoder feedback is active. Procedure Proceed as follows to check the encoder signal using STARTER: 1.
The inverter must measure the pole position for motors not equipped with an encoder, or for encoders, which do not supply the information regarding the pole position. If you are using a Siemens motor, then the inverter automatically selects the appropriate technique to determine the pole position, and when required starts the pole position identification.
Setting functions 8.5 Motor control 8.5.2.4 Optimizing the speed controller Optimum control response - post optimization not required You do not have to manually adapt the speed controller if, after the speed controller self optimization, the motor manifests the following acceleration response: Optimum control response for applications that do not permit any overshoot.
Setting functions 8.5 Motor control 4. Optimize the controller by adjusting the controller parameters K and T The actual value only slowly approaches the setpoint. Increase the proportional component K and reduce the • integration time T The actual value quickly approaches the setpoint, but overshoots too much.
Page 140
Setting functions 8.5 Motor control Function when accelerating or braking The motor torque M is the total of the load torque M and the acceleration torque M The moment of inertia estimator calculates the moment of inertia J of the motor and load from the acceleration torque M and the angular acceleration α...
Page 141
Setting functions 8.5 Motor control Activating the moment of inertia estimator The moment of inertia estimator is deactivated in the factory setting: p1400.18 = 0, p1400.20 = 0, p1400.22 = 0. If you carried out a rotating measurement of the motor in basic commissioning, we recommend leaving the moment of inertia estimator deactivated.
Page 142
Setting functions 8.5 Motor control Parameter Explanation p0341 Motor moment of inertia (factory setting: 0 kgm The inverter sets the parameter when selecting a listed motor. The parameter is then write-protected. p0342 Moment of inertia total ratio to motor (factory setting: 1) Ratio of moment of inertia load + motor to moment of inertia of motor without load p1400 Speed control configuration...
Setting functions 8.5 Motor control 8.5.2.6 Advanced settings - and T adaptation The K - and T adaptation suppresses possible speed controller oscillations. During basic commissioning, the inverter optimizes the speed controller using the "rotating measurement" function. If you have performed the rotating measurement, then the K - and T adaptation has been set.
Setting functions 8.5 Motor control 8.5.3 Torque control Torque control is part of the vector control and normally receives its setpoint from the speed controller output. By deactivating the speed controller and directly entering the torque setpoint, the closed-loop speed control becomes closed-loop torque control. The inverter then no longer controls the motor speed, but the torque that the motor generates.
Setting functions 8.6 Protection and monitoring functions Protection and monitoring functions The frequency inverter offers protective functions against overtemperature and overcurrent for both the frequency inverter as well as the motor. Further, the frequency inverter protects itself against an excessively high DC link voltage when the motor is regenerating. 8.6.1 Inverter temperature monitoring The inverter temperature is essentially defined by the following effects:...
Page 146
Setting functions 8.6 Protection and monitoring functions Overload response for p0290 = 0 The inverter responds depending on the control mode that has been set: ● In vector control, the inverter reduces the output current. ● In U/f control, the inverter reduces the speed. Once the overload condition has been removed, the inverter re-enables the output current or speed.
Page 147
Setting functions 8.6 Protection and monitoring functions Overload response for p0290 = 3 If you operate the inverter with increased pulse frequency, then the inverter reduces its pulse frequency starting at the pulse frequency setpoint p1800. In spite of the temporarily reduced pulse frequency, the maximum output current remains unchanged at the value that is assigned to the pulse frequency setpoint.
Setting functions 8.6 Protection and monitoring functions 8.6.2 Motor temperature monitoring using a temperature sensor You can use one of the following sensors to protect the motor against overtemperature: ● Temperature switch (e. g. bi-metal switch) ● PTC sensor ● KTY 84 sensor Connect the motor's temperature sensor through the motor output cable on the Power Module.
Page 149
Setting functions 8.6 Protection and monitoring functions PTC sensor The converter interprets a resistance > 1650 Ω as being an overtemperature and responds according to the setting for p0610. The converter interprets a resistance < 20 Ω as being a short-circuit and responds with alarm A07015.
Page 150
Setting functions 8.6 Protection and monitoring functions Setting parameters for the temperature monitoring Parameter Description p0335 Specify the motor cooling 0: Natural cooling - with fan on the motor shaft (factory setting) 1: Forced ventilation - with a separately driven fan 2: Liquid cooling 128: No fan p0601...
Setting functions 8.6 Protection and monitoring functions 8.6.3 Protecting the motor by calculating the motor temperature The temperature calculation is only possible in the vector-control control mode (p1300 ≥ 20) and functions by calculating using a thermal motor model. Table 8- 19 Parameters for temperature acquisition without using a temperature sensor Parameter Description...
Page 152
Setting functions 8.6 Protection and monitoring functions Parameter Description p0621 Identification of stator resistance (Rs) when switched on again (factory setting: 0) The inverter measures the current stator resistance and from this calculates the current motor temperature as the start value of the thermal motor model. No Rs identification Rs identification on first switching on the motor Rs identification each time the motor is switched on...
Setting functions 8.6 Protection and monitoring functions 8.6.4 Overcurrent protection The vector control ensures that the motor current remains within the set torque limits. If you use U/f control, you cannot set any torque limits. The U/f control prevents too high a motor current by influencing the output frequency and the motor voltage (I-max controller).
Setting functions 8.7 Application-specific functions Application-specific functions 8.7.1 Functions that match the application The inverter offers a series of functions that you can use depending on your particular application: ● Unit changeover (Page 155) ● Braking functions – Electrically braking the motor (Page 159) –...
Setting functions 8.7 Application-specific functions 8.7.2 Unit changeover Description With the unit changeover function, you can adapt the inverter to the line supply (50/60 Hz) and also select US units or SI units as base units. Independent of this, you can define the units for process variables or change over to percentage values.
Setting functions 8.7 Application-specific functions 8.7.2.1 Changing over the motor standard You change over the motor standard using p0100. The following applies: ● p0100 = 0: IEC motor (50 Hz, SI units) ● p0100 = 1: NEMA motor (60 Hz, US units) ●...
Setting functions 8.7 Application-specific functions Note Special features The percentage values for p0505 = 2 and for p0505 = 4 are identical. For internal calculation and for the output of physical variables, it is, however, important whether the conversion is made to SI or US units. In the case of variables for which changeover to % is not possible, the following applies: p0505 = 1 ≙...
Setting functions 8.7 Application-specific functions 8.7.2.4 Switching units with STARTER Precondition The inverter must be in the offline mode in order to change over the units. STARTER shows whether you change settings online in the inverter or change offline in the PC ( You switch over the mode using the adjacent buttons in the menu bar.
Setting functions 8.7 Application-specific functions 8.7.3 Electrically braking the motor Regenerative power If a motor electrically brakes the connected load and the mechanical power exceeds the electrical losses, then it works as a generator. The motor converts mechanical power by generating electrical power.
Page 160
Setting functions 8.7 Application-specific functions DC braking when falling below a start speed DC braking when a fault occurs Precondition: p1230 = 1 and p1231 = 14 Precondition: Fault number and fault response are assigned using p2100 and p2101 DC braking initiated using a control command DC braking when switching off the motor Precondition: p1231 = 4 and p1230 = control Precondition: p1231 = 5 or p1230 = 1 and p1231...
Page 161
Setting functions 8.7 Application-specific functions DC braking when the motor is switched off 1. The higher-level control switches off the motor (OFF1 or OFF3). 2. The motor brakes along the down ramp to the speed for the start of DC braking. 3.
Setting functions 8.7 Application-specific functions 8.7.3.2 Braking with regenerative feedback to the line Typical applications for braking with energy recovery (regenerative feedback into the line supply): ● Hoist drives ● Centrifuges ● Unwinders For these applications, the motor must brake for longer periods of time. The inverter can feed back up to 100% of its power into the line supply (referred to "High Overload"...
Setting functions 8.7 Application-specific functions 8.7.4 Motor holding brake The motor holding brake prevents the motor turning when it is switched off. The converter has internal logic to optimally control a motor holding brake. Function after OFF1 and OFF3 command The inverter controls the motor holding brake in the following way: ●...
Page 164
Setting functions 8.7 Application-specific functions Function after OFF2 The brake closing time is not taken into account after an OFF2 command: After an OFF2, the inverter issues the signal to immediately close the motor holding brake, independent of the motor speed. Figure 8-22 Controlling the motor holding brake after OFF2 Commissioning a motor holding brake...
Page 165
Setting functions 8.7 Application-specific functions 3. Take the opening and closing times of the connected brake from the technical data for the motor holding brake. – Depending on the brake size, brake opening times lie between 25 ms and 500 ms. –...
Page 166
Setting functions 8.7 Application-specific functions Table 8- 23 Setting the control logic of the motor holding brake Parameter Description p1215 = 1 Enable motor holding brake 0 Motor holding brake locked (factory setting) 1 Motor holding brake just like the sequence control 2: Motor holding brake permanently open 3: Motor holding brake just like the sequential control, connected via BICO p1216...
Setting functions 8.7 Application-specific functions 8.7.5 PID technology controller 8.7.5.1 Overview The technology controller controls process variables, e.g. pressure, temperature, level or flow. Figure 8-23 Example: Technology controller as a level controller Converter with control units CU240D-2 Operating Instructions, 04/2014, FW V4.7, A5E34262100B AA...
Setting functions 8.7 Application-specific functions 8.7.5.2 Setting the controller Simplified representation of the technology controller The technology controller is implemented as PID controller (controller with proportional, integral and differential component) and so can be adapted very flexibly. Figure 8-24 Simplified representation of the technology controller ①...
Page 169
Setting functions 8.7 Application-specific functions Setting the technology controller Parameter Remark p2200 = 1 Enable technology controller. p1070 = 2294 Interconnect the main speed setpoint with the output of the technology controller. p2253 Define the setpoint for the technology controller. Example: p2253 = 2224: The inverter interconnects the fixed setpoint p2201 with the setpoint of the technology controller.
Setting functions 8.7 Application-specific functions 8.7.5.3 Optimizing the controller Setting the technology controller from a practical perspective Procedure Proceed as follows to set the technology controller: 1. Temporarily set the ramp-up and ramp-down times of the ramp-function generator (p2257 and p2258) to zero. 2.
Setting functions 8.7 Application-specific functions 8.7.6 Monitoring the load torque (system protection) In many applications, it is advisable to monitor the motor torque: ● Applications where the load speed can be indirectly monitored by means of the load torque. For example, in fans and conveyor belts with too low a torque indicates that the drive belt is torn.
Page 172
Setting functions 8.7 Application-specific functions Parameter Description No-load monitoring p2179 Current limit for no-load detection If the inverter current is below this value, the message "no load" is output. p2180 Delay time for the "no load" message Blocking protection p2177 Delay time for the "motor locked"...
Setting functions 8.7 Application-specific functions 8.7.7 Load failure monitoring Load failure Using this function, the inverter monitors the speed or velocity of a machine component. The inverter evaluates whether an encoder signal is present. If the encoder signal fails for a time that can be adjusted, then the inverter signals a fault.
Setting functions 8.7 Application-specific functions 8.7.8 Speed deviation monitoring Speed deviation Using this function, the inverter calculates and monitors the speed or velocity of a machine component. The inverter analyzes an encoder signal, calculates a speed from the signal, compares it to the motor speed and reports any excessive deviation between the encoder signal and the motor speed.
Page 175
Setting functions 8.7 Application-specific functions Parameter Description p0490 Invert probe (factory setting 0000bin) Using the 3rd bit of the parameter value, invert the input signals of digital input 3 for the probe. p0580 Probe Input terminal (factory setting 0) Connect input of probe with a digital input. p0581 Probe Edge (factory setting 0)
You can find an example for using the free function blocks in Chapter Interconnecting signals in the inverter (Page 276). Application description for the free function blocks See also: FAQ (http://support.automation.siemens.com/WW/view/en/85168215) Converter with control units CU240D-2 Operating Instructions, 04/2014, FW V4.7, A5E34262100B AA...
Setting functions 8.8 Safe Torque Off (STO) safety function Safe Torque Off (STO) safety function These operating instructions describe the commissioning of the STO safety function when it is controlled via a fail-safe digital input. You will find a detailed description of all safety functions and control using PROFIsafe in the Safety Integrated Function Manual, see Section Manuals for your converter (Page 292).
Page 178
Setting functions 8.8 Safe Torque Off (STO) safety function The STO safety function is standardized The STO function is defined in IEC/EN 61800-5-2: "[…] [The inverter] does not supply any energy to the motor which can generate a torque (or for a linear motor, a force)."...
Table 8- 26 PC-based commissioning tools Tool Can be downloaded at no charge Order number STARTER STARTER 6SL3072-0AA00-0AG0 (http://support.automation.siemens.com/WW/view/en/1080 4985/130000) Startdrive Startdrive 6SL3072-4CA02-1XG0 (http://support.automation.siemens.com/WW/view/en/6803 4568) Commissioning the safety functions with STARTER is subsequently described. A tutorial is available for Startdrive: Startdrive tutorial (http://support.automation.siemens.com/WW/view/en/73598459).
Setting functions 8.8 Safe Torque Off (STO) safety function 8.8.3.2 Protection of the settings from unauthorized changes The safety functions are protected against unauthorized changes by a password. Table 8- 27 Parameter Description p9761 Entering a password (factory setting 0000 hex) Permissible passwords lie in the range 1 …...
Setting functions 8.8 Safe Torque Off (STO) safety function Parameters Description p0010 Drive, commissioning parameter filter Ready Parameter reset p9761 Enter a password (factory setting: 0000 hex) Permissible passwords lie in the range 1 … FFFF FFFF. p9762 New password p9763 Password confirmation Confirming the new Safety Integrated password.
Setting functions 8.8 Safe Torque Off (STO) safety function 4. Selecting "STO via terminal": You have completed the following commissioning steps: ● You have started to commission the safety functions. ● You have selected the basic functions with control via onboard terminals of the inverter. Table 8- 28 Parameter Parameter...
Setting functions 8.8 Safe Torque Off (STO) safety function 8.8.3.6 Setting the filter for safety-related inputs Procedure To set the input filter and simultaneity monitoring of the safety-related input, proceed as follows: 1. Select the advanced settings for STO. 2. Set the debounce time for the F-DI input filter. 3.
Page 184
Setting functions 8.8 Safe Torque Off (STO) safety function The tolerance time does not extend the inverter response time. The inverter selects its safety function as soon as one of the two F-DI signals changes its state from high to low. Figure 8-30 Tolerance regarding discrepancy Filter to suppress short signals...
Page 185
Setting functions 8.8 Safe Torque Off (STO) safety function Figure 8-31 Inverter response to a bit pattern test An adjustable signal filter in the inverter suppresses temporary signal changes using bit pattern test or contact bounce. The filter increases the inverter response time. The inverter only selects its safety function after the debounce time has elapsed.
Setting functions 8.8 Safe Torque Off (STO) safety function 8.8.3.7 Setting the forced checking procedure (test stop) Procedure To set the forced checking procedure (test stop) of the basic functions, proceed as follows: 1. Select the advanced settings for STO. 2.
Setting functions 8.8 Safe Torque Off (STO) safety function 8.8.3.8 Activate settings Activate settings Procedure To activate the settings for the safety functions, proceed as follows: 1. Press the "Copy parameters" button, to create a redundant image of your inverter settings.
Page 188
Setting functions 8.8 Safe Torque Off (STO) safety function Figure 8-34 Example: Assignment of digital inputs DI 4 and DI 5 with STO Procedure In order to prevent the safety-related inputs of the safety functions unintentionally controlling "standard" functions in the inverter, proceed as follows: 1.
Setting functions 8.8 Safe Torque Off (STO) safety function 8.8.3.10 Acceptance - completion of commissioning What is an acceptance? The machine manufacturer is responsible in ensuring that his plant or machine functions perfectly. As a consequence, after commissioning, the machine manufacturer must check those functions or have them checked by specialist personnel, which represent an increased risk of injury to personnel or material damage.
Page 190
Setting functions 8.8 Safe Torque Off (STO) safety function Documentation of the inverter The following must be documented for the inverter: ● The results of the acceptance test. ● The settings of the integrated drive safety functions. The commissioning tool STARTER logs the settings of the integrated drive functions, if necessary.
Page 191
Setting functions 8.8 Safe Torque Off (STO) safety function STARTER has templates in German and English. 2. Select the suitable template and create a report for each drive of your machine or system: – Template for the machine documentation: de_G120x_Dokumentation_Maschine: German template. en_G120x_Documentation_machine: English template.
Setting functions 8.9 Switchover between different settings Switchover between different settings There are applications that require different inverter settings. Example: You connect different motors to one inverter. Depending on the particular motor, the inverter must operate with the associated motor data and the appropriate ramp-function generator. Drive data sets (DDS) Your can set several inverter functions differently and then switch over between the different settings.
Page 193
Setting functions 8.9 Switchover between different settings Table 8- 30 Parameters for switching the drive data sets: Parameter Description p0820[0…n] Drive data set selection DDS bit 0 If you use several command data sets CDS, then you must set this parameter for each CDS. p0821[0…n] Drive data set selection DDS bit 1 The parameters are assigned to a CDS through...
Page 194
Setting functions 8.9 Switchover between different settings Converter with control units CU240D-2 Operating Instructions, 04/2014, FW V4.7, A5E34262100B AA...
Backing up data and series commissioning External data backup After commissioning, your settings are saved in the converter so that they are protected against power failure. We recommend that you additionally back up the settings on a storage medium outside the converter.
Backing up data and series commissioning 9.1 Saving settings on a memory card Saving settings on a memory card What memory cards do we recommend? You will find the recommended memory cards in Section: Commissioning tools (Page 25). Using memory cards from other manufacturers The inverter only supports memory cards up to 2 GB.
Backing up data and series commissioning 9.1 Saving settings on a memory card 9.1.1 Saving settings to the memory card We recommend that you insert the memory card before switching on the converter for the first time. If a memory card is inserted, the converter saves every modified parameter value on the card.
Backing up data and series commissioning 9.1 Saving settings on a memory card 9.1.2 Transferring the settings from the memory card Download Procedure Proceed as follows to transfer the parameter settings from a memory card into the converter (download): 1. Switch off the converter power supply. 2.
Page 199
Backing up data and series commissioning 9.1 Saving settings on a memory card To safely remove the memory card using STARTER, proceed as follows: 1. In the Drive Navigatorselect the following screen form: 2. Click on the button to safely remove the memory card. 3.
Backing up data and series commissioning 9.2 Backing up and transferring settings using STARTER Backing up and transferring settings using STARTER With the supply voltage switched on, you can transfer the converter settings from the converter to a PG/PC, or the data from a PG/PC to the converter.
Page 201
Backing up data and series commissioning 9.2 Backing up and transferring settings using STARTER Procedure with enabled safety functions To load the settings from the PG to the inverter and to activate the safety functions, proceed as follows: 1. Go online with STARTER : 2.
Backing up data and series commissioning 9.3 Saving settings and transferring them using an operator panel Saving settings and transferring them using an operator panel Precondition When the power supply is switched on, you can transfer the inverter settings to the IOP or vice versa, transfer the IOP data to the inverter.
On the memory card, you can back up 99 other settings in addition to the default setting. You will find additional information on the Internet at: Memory options (http://support.automation.siemens.com/WW/view/en/43512514). Converter with control units CU240D-2 Operating Instructions, 04/2014, FW V4.7, A5E34262100B AA...
Backing up data and series commissioning 9.5 Write and know-how protection Write and know-how protection The inverter offers the option to protect configured settings from being changed or copied. Write protection and know-how protection are available for this purpose. 9.5.1 Write protection Write protection prevents converter settings from being inadvertently changed.
Page 205
Backing up data and series commissioning 9.5 Write and know-how protection Points to note about restoring the factory settings If you select "Reset to factory settings" using the button when write protection is active, the following confirmation prompt opens. The confirmation prompt is not issued, if you select another way to restore the factory setting, e.g.
The know-how protection with copy protection is possible only with the recommended Siemens memory card; also see Section: Commissioning tools (Page 25) Exception list The active know-how protection permits an exception list for parameters to be defined that the customer may access.
Page 207
Backing up data and series commissioning 9.5 Write and know-how protection Actions that are possible during active know-how protection ● Restoring factory settings ● Acknowledging messages ● Displaying messages ● Show message history ● Reading out diagnostic buffer ● Switching to the control panel (complete control panel functionality: Fetch master control, all buttons and setting parameters) ●...
● You are online with STARTER. If you have created a project offline on your computer, you must download it to the inverter and go online. ● You have inserted the recommended Siemens card. See also Section: Commissioning tools (Page 25). Procedure Proceed as follows to activate know-how protection: 1.
Page 209
9.5 Write and know-how protection Deactivate know-how protection, delete password Preconditions ● You are online with STARTER. ● You have inserted the recommended Siemens card. See also Section: Commissioning tools (Page 25). Procedure Proceed as follows to deactivate know-how protection: 1.
Backing up data and series commissioning 9.5 Write and know-how protection 9.5.2.2 Creating an exception list for the know-how protection Using the exception list, you as a machine manufacturer may make individual adjustable parameters accessible to end customers although know-how protection is active. You may define the exception list via parameters p7763 and p7764 in the expert list.
Corrective maintenance 10.1 Spare parts - external fan External fan for Frame Size C Frame Size C is fitted with an external fan to provide additional cooling. Should the fan need replacing the fitting process is shown in the diagram below. The external fan can be ordered under the part number: 6SL3500-0SF01-0AA0.
Corrective maintenance 10.2 Overview of replacing converter components 10.2 Overview of replacing converter components Permissible replacement of components In the event of a long-term function fault, you must replace the Power Module or Control Unit. The converter's Power Module and Control Unit can be replaced independently of each other.
Page 213
SIMATIC S7 controller with DriveES – using DriveES. Details of the device replacement without removable storage medium can be found in the Profinet system description (http://support.automation.siemens.com/WW/view/en/19292127). Converter with control units CU240D-2 Operating Instructions, 04/2014, FW V4.7, A5E34262100B AA...
Corrective maintenance 10.3 Replacing a Control Unit with enabled safety function 10.3 Replacing a Control Unit with enabled safety function Replacing a Control Unit with data backup on a memory card Precondition You have a memory card with the actual settings of the Control unit to be replaced. If you use a memory card with firmware, after the replacement, you obtain a precise copy (firmware and settings) of the replaced Control Unit.
Page 215
Corrective maintenance 10.3 Replacing a Control Unit with enabled safety function Replacing a Control Unit with data backup in the PC Precondition You have backed up the actual settings of the Control Unit to be replaced to a PC using STARTER.
Page 216
Corrective maintenance 10.3 Replacing a Control Unit with enabled safety function Replacing the Control Unit with data backup in the operator Panel Precondition You have backed up the actual settings of the Control Unit to be replaced to an operator panel.
Page 217
Corrective maintenance 10.3 Replacing a Control Unit with enabled safety function 21.Switch on the inverter power supply again (power on reset). 22.Perform a reduced acceptance test, see the section Reduced acceptance test after function expansions (Page 190). You have replaced the Control Unit and transferred the safety function settings from the operator panel to the new Control Unit.
Corrective maintenance 10.4 Replacing the Control Unit without the safety functions enabled 10.4 Replacing the Control Unit without the safety functions enabled Replacing a Control Unit with data backup on a memory card Procedure Proceed as follows to exchange the Control Unit: 1.
Page 219
Corrective maintenance 10.4 Replacing the Control Unit without the safety functions enabled Replacing a Control Unit with data backup in the PC Procedure Proceed as follows to exchange the Control Unit: 1. Disconnect the line voltage to the Power Module and (if installed) the external 24 V supply or the voltage for the digital outputs of the Control Unit.
Corrective maintenance 10.5 Replacing the Control Unit without data backup 10.5 Replacing the Control Unit without data backup If you do not backup the settings, then you must recommission the drive after replacing the Control Unit. Procedure To replace the Control Unit without backed-up settings, proceed as follows: 1.
If know-how protection with copy protection is active, the inverter cannot be replaced as described in "Overview of replacing converter components (Page 212)". However, to allow the inverter to be replaced, you must use a Siemens memory card, and the machine manufacturer must have an identical machine that he uses as sample.
Page 222
– copies the encrypted project from the card to his PC – for example, sends it by e-mail to the end customer ● The end customer copies the project to the Siemens memory card that belongs to the machine, inserts it in the inverter and switches on the inverter.
Corrective maintenance 10.7 Replacing a Power Module with enabled safety function 10.7 Replacing a Power Module with enabled safety function DANGER Danger from touching energized Power Module connections After switching off the mains voltage, it will take up to 5 minutes until the capacitors in the Power Module are sufficiently discharged for the residual voltage to be safe.
Corrective maintenance 10.8 Replacing a Power Module without the safety function being enabled 10.8 Replacing a Power Module without the safety function being enabled Procedure Proceed as follows to exchange a Power Module: 1. Switch off the supply voltage to the Power Module. You do not have to switch off an external 24 V power supply for the Control Unit if one is being used.
Corrective maintenance 10.9 Upgrading firmware 10.9 Upgrading firmware When upgrading firmware you replace the inverter's firmware with a newer version. Only update the firmware to a newer version if you require the expanded range of functions of that newer version. Conditions 1.
Page 226
Corrective maintenance 10.9 Upgrading firmware Note Damaged firmware if the power supply is interrupted while transferring data If the power supply is interrupted while transferring data, this can damage the inverter's firmware. • Do not switch off the inverter's power supply while data is being transferred. 7.
Corrective maintenance 10.10 Firmware downgrade 10.10 Firmware downgrade When downgrading firmware you replace the inverter's firmware with an older version. Only update the firmware to an older level if, after replacing an inverter, you require the same firmware in all inverters. Precondition 1.
Page 228
Corrective maintenance 10.10 Firmware downgrade Note Damaged firmware if the power supply is interrupted while transferring data If the power supply is interrupted while transferring data, this can damage the inverter's firmware. • Do not switch off the inverter's power supply while data is being transferred. 7.
Corrective maintenance 10.11 Correcting a failed firmware upgrade or downgrade 10.11 Correcting a failed firmware upgrade or downgrade How does the inverter report a failed upgrade or downgrade? The inverter signals a failed firmware upgrade or downgrade with a quickly flashing RDY LED and a lit up BF LED.
Corrective maintenance 10.12 Reduced acceptance test after component replacement 10.12 Reduced acceptance test after component replacement After a component has been replaced or the firmware updated, a reduced acceptance test of the safety functions must be performed. Measure Acceptance test Acceptance test Documentation Replacing the Control Unit.
Corrective maintenance 10.13 If the converter no longer responds 10.13 If the converter no longer responds If the inverter no longer responds For example, when loading an incorrect file from the memory card, the inverter can go into a state where it can no longer respond to commands from the operator panel or from a higher- level control system.
Page 232
Corrective maintenance 10.13 If the converter no longer responds Case 2 ● The motor is switched off. ● You cannot communicate with the inverter, either via the operator panel or other interfaces. ● The LEDs flash and are dark - this process is continually repeated. Procedure Proceed as follows to restore the inverter factory settings: 1.
Alarms, faults and system messages 11.1 Alarms Alarms have the following properties: ● They do not have a direct effect in the converter and disappear once the cause has been removed ● They do not need have to be acknowledged ●...
Page 234
Alarms, faults and system messages 11.1 Alarms If an additional alarm is received, then this is also saved. The first alarm is still saved. The alarms that have occurred are counted in p2111. Figure 11-2 Saving the second alarm in the alarm buffer The alarm buffer can contain up to eight alarms.
Page 235
Alarms, faults and system messages 11.1 Alarms Figure 11-4 Shifting alarms that have been removed into the alarm history Any alarms that have not been removed remain in the alarm buffer. The converter sorts the alarms and closes gaps between the alarms. If the alarm history is filled up to index 63, each time a new alarm is accepted in the alarm history, the oldest alarm is deleted.
Page 236
Alarms, faults and system messages 11.1 Alarms Parameters of the alarm buffer and the alarm history Parameter Description r2122 Alarm code Displays the numbers of alarms that have occurred r2123 Alarm time received in milliseconds Displays the time in milliseconds when the alarm occurred r2124 Alarm value Displays additional information about the alarm...
Alarms, faults and system messages 11.2 Faults 11.2 Faults A fault indicates a severe fault during inverter operation. The inverter signals a fault as follows: ● At the operator panel with Fxxxxx ● At the inverter using the red LED RDY ●...
Page 238
Alarms, faults and system messages 11.2 Faults The fault buffer can accept up to eight actual faults. The next to last fault is overwritten if an additional fault occurs after the eighth fault. Figure 11-7 Complete fault buffer Acknowledgement You have multiple options to acknowledge a fault, e.g.: ●...
Page 239
Alarms, faults and system messages 11.2 Faults Figure 11-8 Fault history after acknowledging the faults After acknowledgment, the faults that have not been removed are located in the fault buffer as well as in the fault history. For these faults, the "fault time coming" remains unchanged and the "fault time removed"...
Page 240
Alarms, faults and system messages 11.2 Faults Parameters of the fault buffer and the fault history Parameter Description r0945 Fault code Displays the numbers of faults that have occurred r0948 Fault time received in milliseconds Displays the time in milliseconds when the fault occurred r0949 Fault value Displays additional information about the fault...
Alarms, faults and system messages 11.3 Status LED overview 11.3 Status LED overview LED status indicators The Control Unit has number of dual-colour LEDs which are designed to indicate the operational state of the Inverter. The LEDs are used to indicate the status of the following states: ●...
Page 242
Alarms, faults and system messages 11.3 Status LED overview Explanation of status LEDs An explanation of the various states indicated by the LEDs are given in the tables below. Table 11- 1 Description of general status LEDS Description of function GREEN - On Ready for operation (no active fault) GREEN - flashing slowly...
Alarms, faults and system messages 11.5 System runtime 11.5 System runtime By evaluating the system runtime of the inverter, you can decide whether you must replace components subject to wear such as fans, motors and gear units. Principle of operation The inverter starts the system runtime as soon as the inverter is supplied with power.
Alarms, faults and system messages 11.6 List of alarms and faults 11.6 List of alarms and faults Axxxxx Alarm Fyyyyy: Fault Table 11- 6 Faults, which can only be acknowledged by switching the converter off and on again (power on reset) Number Cause Remedy...
Page 246
Alarms, faults and system messages 11.6 List of alarms and faults Number Cause Remedy p0970 = 5 Reset Start Safety Parameter. The converter sets p0970 = 5 if it has reset the parameters. Then reset the converter to the factory setting again. A01666 Static 1 signal atF-DI for safe F-DI to a logical 0 signal.
Page 247
Alarms, faults and system messages 11.6 List of alarms and faults Number Cause Remedy A05000 Power Module overtemperature Check the following: A05001 - Is the ambient temperature within the defined limit values? A05002 - Are the load conditions and duty cycle configured accordingly? A05004 - Has the cooling failed? A05006...
Page 248
Alarms, faults and system messages 11.6 List of alarms and faults Number Cause Remedy F07801 Motor overcurrent Check current limits (p0640). Vector control: Check current controller (p1715, p1717). U/f control: Check the current limiting controller (p1340 … p1346). Increase acceleration ramp (p1120) or reduce load. Check motor and motor cables for short circuit and ground fault.
Page 249
Alarms, faults and system messages 11.6 List of alarms and faults Number Cause Remedy A07922 Torque/speed out of tolerance Check the connection between the motor and the load. • Adapt the parameterization corresponding to the load. • F07923 Torque/speed too low Check the connection between the motor and the load.
Page 250
Alarms, faults and system messages 11.6 List of alarms and faults Number Cause Remedy F30001 Overcurrent Check the following: Motor data, if required, carry out commissioning • Motor connection method (Υ / Δ) • U/f operation: Assignment of rated currents of motor and Power •...
Page 251
Alarms, faults and system messages 11.6 List of alarms and faults Number Cause Remedy Check the fan filter elements. • F30036 Overtemperature, inside area Check whether the ambient temperature is in the permissible range. • F30037 Rectifier overtemperature See F30035 and, in addition: Check the motor load.
Page 252
Alarms, faults and system messages 11.6 List of alarms and faults Converter with control units CU240D-2 Operating Instructions, 04/2014, FW V4.7, A5E34262100B AA...
2 programmable inputs 0 V ... 10 V with 12 bit resolution. Max. 10 mA Encoder interface HTL bipolar, ≤ 2048 pulses, ≤ 100 mA, • e. g. SIEMENS encoders 1XP8001-1, 1XP80X2-1X. Max. cable length: 30 m shielded • Temperature sensor PTC: Short-circuit monitoring 22 Ω, switching threshold 1650 Ω...
Page 254
Technical data 12.1 Performance ratings Control Unit Feature Specification Fail-safe input DI 4 and DI 5 form the fail-safe digital input. • Maximum input voltage 30 V, 5.5 mA • Response time: • – Typical: 5 ms + debounce time p9651 –...
The specification only refers to the total instantaneous regenerative feedback, however not to the total connected power of all of the power modules connected to the same transformer. Further information: FAQ (http://support.automation.siemens.com/WW/view/en/34189181). Output voltage 3 AC 0 V … line volage × 0.87 (max.) Input frequency 47 Hz …...
Technical data 12.3 SINAMICS G120D specifications 12.3 SINAMICS G120D specifications Power Module Specifications Note UL certified Fuses must be used In order that the system is in compliance with UL requirements, UL listed class H, J or K fuses, circuit breakers or self-protected combination motor-controllers must be used.
Relative air humidity for the SINAMICS G120D is ≤ 95 % non-condensing. Shock and vibration Do not drop the SINAMICS G120D or expose to sudden shock. Do not install the SINAMICS G120D in an area where it is likely to be exposed to constant vibration.
Technical data 12.5 Derating as a function of the installation altitude 12.5 Derating as a function of the installation altitude Voltage The clearance within the converter can isolate surge voltages in accordance with overvoltage category III in compliance with the EN 60664-1 regulation up to 2000 m above sea level.
Technical data 12.6 Pulse frequency and current reduction 12.6 Pulse frequency and current reduction Pulse frequency and current reduction Table 12- 5 Current reduction depending on pulse frequency Power Frame Inverter Output current at pulse frequency of rating at size current 400 V rating...
EN 60204-1 — Safety of machinery –Electrical equipment of machines European Machinery Directive The SINAMICS G120D-2 inverter series does not fall under the scope of the Machinery Directive. However, the products have been fully evaluated for compliance with the essential Health & Safety requirements of the directive when used in a typical machine application.
Technical data 12.8 Electromagnetic Compatibility 12.8 Electromagnetic Compatibility The SINAMICS G120 drives have been tested in accordance with the EMC Product Standard EN 61800-3:2004. Details see declaration of conformity Note Install all drives in accordance with the manufacturer’s guidelines and in accordance with good EMC practices.
Page 262
Technical data 12.8 Electromagnetic Compatibility Table 12- 7 Conducted disturbance voltage and radiated emissions EMC Phenomenon Converter type Level acc. to Remark IEC 61800-3 Conducted emissions All converters with integrated class A filters. Category C2 (disturbance voltage) First Environment - Order number: Professional Use 6SL3525-0PE**-*A**...
Page 263
Technical data 12.8 Electromagnetic Compatibility EMC Immunity The SINAMICS G120D drives have been tested in accordance with the immunity requirements of category C3 (industrial) environment: Table 12- 9 EMC Immunity EMC Phenomenon Standard Level Performance Criterion Electrostatic Discharge (ESD) EN 61000-4-2...
Page 264
Technical data 12.8 Electromagnetic Compatibility Converter with control units CU240D-2 Operating Instructions, 04/2014, FW V4.7, A5E34262100B AA...
Appendix New and extended functions Table A- 1 New functions and function changes in Firmware 4.6 Function SINAMICS G120 G120D Support for the new Power Modules ✓ ✓ ✓ ✓ PM240-2 IP20 FSB … FSC • PM240-2 in through-hole technology FSB ... FSC •...
Page 266
Appendix A.1 New and extended functions Function SINAMICS G120 G120D Safety info channel ✓ ✓ ✓ ✓ BICO source r9734.0…14 for the status bits of the extended safety • functions Diagnostic alarms for PROFIBUS ✓ ✓ ✓ ✓ ✓ ✓ ✓...
Page 267
Appendix A.1 New and extended functions Table A- 3 New functions and function changes in Firmware 4.7 Function SINAMICS G120 G120D Supporting the identification & maintenance datasets ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ (I&M1 … 4) Fall in pulse rate with increased drive power required by the ✓...
Before you connect the motor, ensure that the motor has the appropriate connection for your application: Motor is connected in the star or delta configuration With SIEMENS motors, you will see a diagram of both connection methods on the inside of the cover of the terminal box: •...
Appendix A.3 Parameter Parameter Parameters are the interface between the firmware of the converter and the commissioning tool, e.g. an Operator Panel. Adjustable parameters Adjustable parameters are the "adjusting screws" with which you adapt the converter to its particular application. If you change the value of an adjustable parameter, then the converter behavior also changes.
Page 270
Appendix A.3 Parameter Table A- 7 How to set the ramp-up and ramp-down Parameter Description p1080 Minimum speed 0.00 [rpm] factory setting p1082 Maximum speed 1500.000 [rpm] factory setting p1120 Ramp-up time 10.00 [s] p1121 Ramp-down time 10.00 [s] Table A- 8 This is how you set the closed-loop type Parameter Description...
Page 271
Appendix A.3 Parameter Table A- 10 How to change the inverter pulse frequency Parameter Description p1800 Setting the inverter pulse frequency The pulse frequency depends on the power unit. You can find the setting limits and the factory setting in Section Performance ratings Power Module (Page 255).
Appendix A.4 Handling STARTER Handling STARTER A.4.1 Change settings After the basic commissioning, you can adapt the inverter to your application as described in the Commissioning guidelines (Page 57). STARTER offers two options: ● Change the settings using the appropriate screen forms - our recommendation. ①...
Appendix A.4 Handling STARTER Go offline You can now exit the online connection after the data backup (RAM to ROM) with "Disconnect from target system". A.4.2 Optimize the drive using the trace function Description The trace function is used for inverter diagnostics and helps to optimize the behavior of the drive.
Page 274
Appendix A.4 Handling STARTER Trigger You can create your own start condition (trigger) for the trace. With the factory setting (default setting) the trace starts as soon as you press the button (Start Trace). Using the button , you can define another trigger to start the measurement. Using pretrigger, set the time for the recording before the trigger is set.
Page 275
Appendix A.4 Handling STARTER Display options In this area, you can set how the measurement results are displayed. ● Repeating measurements This places the measurements that you wish to perform at different times above one other. ● Arrange the curves in tracks This means you define whether the trace of all measured values is displayed with respect to a common zero line –...
Appendix A.5 Interconnecting signals in the inverter Interconnecting signals in the inverter A.5.1 Fundamentals The following functions are implemented in the converter: ● Open-loop and closed-loop control functions ● Communication functions ● Diagnosis and operating functions Every function comprises one or several blocks that are interconnected with one another. Figure A-3 Example of a block: Motorized potentiometer (MOP) Most of the blocks can be adapted to specific applications using parameters.
Page 277
Appendix A.5 Interconnecting signals in the inverter Binectors and connectors Connectors and binectors are used to exchange signals between the individual blocks: ● Connectors are used to interconnect "analog" signals. (e.g. MOP output speed) ● Binectors are used to interconnect "digital" signals. (e.g. 'Enable MOP up' command) Figure A-5 Symbols for binector and connector inputs and outputs Binector/connector outputs (CO/BO) are parameters that combine more than one binector...
Appendix A.5 Interconnecting signals in the inverter A.5.2 Example Moving a basic control logic into the inverter A conveyor system is to be configured in such a way that it can only start when two signals are present simultaneously. These could be the following signals, for example: ●...
Page 279
Appendix A.5 Interconnecting signals in the inverter Explanation of the example using the ON/OFF1 command Parameter p0840[0] is the input of the "ON/OFF1" block of the inverter. Parameter r20031 is the output of the AND block. To interconnect ON/OFF1 with the output of the AND block, set p0840 = 20031.
Appendix A.6 Application Examples Application Examples A.6.1 Setting an absolute encoder Encoder data In the following example, the inverter must evaluate an SSI encoder. The encoder data sheet also includes the following encoder data: Table A- 11 Excerpt from the data sheet of the absolute encoder Feature Value Configuring an...
Page 281
Appendix A.6 Application Examples Configuring an encoder When configuring the encoder, you must select an encoder type that has the best possible fit to the real encoder. Precondition You have started to configure the drive. Procedure Proceed as follows to set an absolute encoder in STARTER: 1.
Page 282
Appendix A.6 Application Examples Adapting the encoder data After the configuration you may now adapt the encoder data. Preconditions ● You have now configured an absolute encoder. ● You have completely configured the drive. Procedure Proceed as follows to adapt the encoder data: 1.
Page 283
Appendix A.6 Application Examples 3. … 10. In the "Encoder data" screen form, adapt the settings corresponding to the data sheet of your encoder. The "Details" tab is used for application-specific settings, e.g. to invert the encoder signal. The fine resolution can be separately set for the process data Gx_XIST1 and Gx_XIST2. 2 bit fine resolution is practical for square wave encoders.
Appendix A.7 Setting a non standard HTL encoder A.6.2 Connecting the safety-related input The following examples show the interconnection of the safety-related input accordance with PL d to EN 13849-1 and SIL2 according to IEC61508. You can find further examples and information in the Safety Integrated Function Manual.
Appendix A.7 Setting a non standard HTL encoder Setting a non standard HTL encoder Proceeding: manually configuring the encoder 1. Set p0010 = 4. This allows the encoder parameters to be accessed. 2. Configure the encoder using the table below. 3.
Appendix A.8 Acceptance tests for the safety functions Acceptance tests for the safety functions A.8.1 Recommended acceptance test The following descriptions for the acceptance test are recommendations that illustrate the principle of acceptance. You may deviate from these recommendations if you check the following once you have completed commissioning: ●...
Page 287
Appendix A.8 Acceptance tests for the safety functions Figure A-10 Acceptance test for STO (basic functions) Converter with control units CU240D-2 Operating Instructions, 04/2014, FW V4.7, A5E34262100B AA...
Page 288
Appendix A.8 Acceptance tests for the safety functions Procedure To perform an acceptance test of the STO function as part of the basic functions, proceed as follows: Status The inverter is ready The inverter signals neither faults nor alarms of the safety functions (r0945[0…7], •...
Appendix A.8 Acceptance tests for the safety functions A.8.2 Machine documentation Machine or plant description Designation … Type … Serial number … Manufacturer … End customer … Block diagram of the machine and/or plant: … … … … … … …...
Page 290
Appendix A.8 Acceptance tests for the safety functions Acceptance test reports File name of the acceptance reports … … … … Data backup Data Storage medium Holding area Archiving type Designation Date Acceptance test reports … … … … PLC program …...
Appendix A.8 Acceptance tests for the safety functions A.8.3 Log the settings for the basic functions, firmware V4.4 ... V4.7 Drive = <pDO-NAME_v> Table A- 14 Firmware version Name Number Value Control Unit firmware version <r18_v> SI version, safety functions integrated in the drive (processor 1) r9770 <r9770_v>...
Download or order number depth languages Getting Started Guide Installing and commissioning English, Documentation download the converter. German (http://support.automation. siemens.com/WW/view/en/ Operating instructions (this manual) 36426537/133300) for the SINAMICS G110M, SINAMICS Manual CU240M and PM240M Collection Function Manual for Safety Configuring PROFIsafe.
(www.siemens.en/sinamics-g120) SINAMICS G inverters Italian, French, Spanish Online catalog (Industry Ordering data and technical English, Mall) information for all SIEMENS German products SIZER The overall configuration tool for English, You obtain SIZER on a DVD SINAMICS, MICROMASTER German, (Order number: 6SL3070-0AA00-0AG0)
Page 294
If you come across any mistakes when reading this manual or if you have any suggestions for how it can be improved, then please send your suggestions to the following address or by E-mail: Siemens AG Drive Technologies Motion Control Systems...