Technical specifications
15.4 Mechanical and climatic ambient conditions
15.4
Mechanical and climatic ambient conditions
Operating conditions
The S7-1500 automation system/ET 200MP distributed I/O system is suitable for use in
weather-proof, fixed locations. The operating conditions exceed requirements according to
DIN IEC 60721-3-3:
● Class 3M3 (mechanical requirements)
● Class 3K3 (climatic requirements)
Test of mechanical ambient conditions
The table below provides important information with respect to the type and scope of the test
of ambient mechanical conditions.
Table 15- 8
Test of mechanical ambient conditions
Condition tested
Test Standard
Vibration
Vibration test according to
IEC 60068-2-6 (Sinus)
Shock
Shock, tested according to
IEC 60068-2-27
Continuous shock
Shock, tested according to
IEC 60068-2-27
Reduction of vibrations
If your S7-1500 automation system/ET 200MP distributed I/O system is exposed to severe
shock or vibration, take appropriate measures to reduce the acceleration or the amplitude.
We recommend the installation of the S7-1500 automation system/ET 200MP distributed I/O
system on damping materials (for example, rubber-bonded metal mounting).
214
Comment
Type of oscillation: Frequency sweeps with a rate of change of
1 octave/minute.
5 Hz ≤ f ≤ 8.4 Hz, constant amplitude 7 mm
8.4 Hz ≤ f ≤ 150 Hz, constant acceleration 2 g
Duration of oscillation: 10 frequency sweeps per axis, along each of the
3 mutually perpendicular axes
Type of shock: Half-sine
Shock intensity: 15 g max., duration 11 ms
Direction of shock: 3 shocks each in (+/-) direction, along each of the
3 mutually perpendicular axes
Type of shock: Half-sine
Shock intensity: 250 m/s
2
Direction of shock: 1000 shocks each in (+/-) direction, along each of the
3 mutually perpendicular axes
peak value, 6 ms duration