ABB RPBA-01 User Manual page 34

Profibus dp adapter module
Table of Contents

Advertisement

34
Note: The new settings take effect only when the module is
powered up the next time or when the module receives a 'Fieldbus
Adapter parameter refresh' command from the drive.
Data transfer rates supported
The RPBA-01 supports the following PROFIBUS communication
speeds: 9.6 kbit/s, 19.2 kbit/s, 45.45 kbit/s, 93.75 kbit/s, 187.5
kbit/s, 500 kbit/s, 1.5 Mbit/s, 3 Mbit/s, 6 Mbit/s, 12 Mbit/s.
The RPBA-01 automatically detects the communication speed
and PPO-type used.
Table 5. The RPBA-01 configuration parameters.
Par.
Parameter name
no.
1
MODULE TYPE
2
NODE ADDRESS
3
BAUD RATE
4
PPO-TYPE
5
PZD3 OUT
6
PZD3 IN
7
PZD4 OUT
8
PZD4 IN
...
...
Programming
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Alternative settings
(Read-only)
0 to 126
1)
(12000) 12 Mbit/s; (6000) 6 Mbit/s;
(3000) 3 Mbit/s; (1500) 1.5 Mbit/s;
(500) 500 kbit/s; (187) 187.5 kbit/s;
(93) 93.75 kbit/s; (45) 45.45 kbit/s;
(19) 19.2 kbit/s; (9) 9.6 kbit/s;
(Read-only)
1)
(1) PPO 1; (2) PPO 2; (3) PPO 3;
(4) PPO 4; (5) PPO 5; (6) PPO 6;
(Read-only)
0 to 32767 with format xxyy, where
xx = Parameter Group and
yy = Parameter Index.
See description below.
See PZD3 OUT above
See PZD3 OUT above
See PZD3 OUT above
Default
setting
PROFIBUS DP
3
1500
(1) PPO 1
0
0
0
0