hit counter script
Honeywell JADE W7220 Installation Instructions Manual

Honeywell JADE W7220 Installation Instructions Manual

Economizer module
Hide thumbs Also See for JADE W7220:

Advertisement

JADE
Economizer Module
(MODEL W7220)
This document describes wiring, power up, basic
Troubleshooting, and common installation issues for the
JADE™ Economizer Module (Model W7220). For further
information on mounting and operation, refer to Honeywell
document 63-2700.

BEFORE INSTALLATION

Review the following before installing the The W7220:
Electrical
Rated Voltage: 20 to 30 Vac RMS; 50/60 Hz
Transformer: 100 VA maximum system input
Relay Digital Output Rating: 30 Vac
IMPORTANT
All inputs and outputs must be Class 2 wiring.
Inputs
A Mixed air (MA) analog sensor is required on all W7220
units; either an OA (Outdoor Air) sensor for dry bulb change
over or an OA Sylkbus sensor for outdoor enthalpy change
over is required in addition to the MA sensor. An additional
Return Air (RA) Sylkbus sensor can be added to the system
INSTALLATION INSTRUCTIONS
for differential enthalpy changeover. JADE can be used with a
CO2 indoor air sensor for Demand Control Ventilation and
with a VFD for two speed fan operation.
DCV (CO
) Sensor (C7232): 2-10 Vdc control signal;
2
minimum impedance >50k ohm.
Outputs
Actuator signal: 2-10 Vdc; minimum actuator impedance is
2k ohm; Sylkbus two-wire output for Honeywell Sylkbus
communicating actuators.
Exhaust fan, Y1, Y2 and AUX1 O: Contact closure (24 Vac)
All Relay Outputs (at 30 Vac):
Running: 1.5A maximum
Inrush: 7.5A maximum

When Installing This Product

1. Read these instructions carefully. Failure to follow them
could damage the product or cause a hazardous condi-
tion.
2. Check ratings given in instructions and on the product to
ensure the product is suitable for your application.
3. Installer must be a trained, experienced service techni-
cian.
4. After installation is complete, check out product opera-
tion as provided in these instructions.
5. For additional detailed information on this product go to
customer.honeywell.com and download the product
data sheet (lit no 63-2700) or scan QR code located on
the label above MAT terminals with your smart phone.

Accessories

50048926-001 2-pin edge connector for sensors
(20 pieces per bag)
50048926-002 6-pin edge connector for field wiring
(20 pieces per bag)
C7250 20k sensor for MA or OA (dry bulb changeover)
C7400S Sylkbus sensor for enthalpy control in OA and/or RA
and RA for differential dry bulb changeover
W7220 PCMOD interface tool for JADE controller and Per-
sonal Computer. Go to www.customer.honeywell.com/
economizertools for the software
50053060-001 Duct mounting kit for sensors
C7632 or C7232 CO
sensors
2
62-0331-13

Advertisement

Table of Contents
loading

Summary of Contents for Honeywell JADE W7220

  • Page 1: Before Installation

    >50k ohm. Outputs Actuator signal: 2-10 Vdc; minimum actuator impedance is 2k ohm; Sylkbus two-wire output for Honeywell Sylkbus communicating actuators. Exhaust fan, Y1, Y2 and AUX1 O: Contact closure (24 Vac) All Relay Outputs (at 30 Vac): Running: 1.5A maximum...
  • Page 2 ™ JADE ECONOMIZER MODULE INSTALLATION AND SETUP Actuator Wiring Options: 1. The JADE economizer controller can only have one (1) The Economizer module may be mounted in any orientation. communicating actuator connected to it. However, mounting in the orientation shown above permits 2.
  • Page 3 ™ JADE ECONOMIZER MODULE Table 2. Economizer Module - Right hand terminal blocks. Label Type Description Y1-I 24 Vac IN Y1 in - Cooling Stage 1 Input from space thermostat Y1-O 24 Vac OUT Y1 out - Cooling Stage 1 Output to stage 1 mechanical cooling 24 Vac Common 24 Vac...
  • Page 4 WHEN USING A HEAT PUMP THERMOSTAT, THERMOSTAT TERMINALS MAY DIFFER: W1 MAY BE LABELED O OR B AND W2 MAY BE LABELED W. WHEN USING A HEAT PUMP WITH DEFROST FEEDBACK, ADD AN ISOLATION RELAY BETWEEN O AND C. M32564D Fig. 2. Stand-alone dry-bulb Economizer configuration with Honeywell MS7503 Direct Coupled Actuator. 62-0331—13...
  • Page 5 WHEN USING A HEAT PUMP THERMOSTAT, THERMOSTAT TERMINALS MAY DIFFER: W1 MAY BE LABELED O OR B AND W2 MAY BE LABELED W. WHEN USING A HEAT PUMP WITH DEFROST FEEDBACK, ADD AN ISOLATION RELAY BETWEEN O AND C. M32650D Fig. 3. Stand-alone dry-bulb Economizer configuration with Honeywell MS3103J or MS3105J communicating actuators. 62-0331—13...
  • Page 6 MAY DIFFER: W1 MAY BE LABELED O OR B AND W2 MAY BE LABELED W. WHEN USING A HEAT PUMP WITH DEFROST FEEDBACK, ADD AN ISOLATION RELAY BETWEEN O AND C. M32565D Fig. 4. Economizer with Sylk Bus sensors for enthalpy configuration with Honeywell M7215 black motor. 62-0331—13...
  • Page 7 W1 MAY BE LABELED O OR B AND W2 MAY BE LABELED W. WHEN USING A HEAT PUMP WITH DEFROST FEEDBACK, ADD AN ISOLATION RELAY BETWEEN O AND C. M32566D Fig. 5. Economizer with Sylk Bus sensors for enthalpy configuration with a Honeywell MS7505 or MS7503 Direct Coupled Actuator. 62-0331—13...
  • Page 8 RETURN AIR TEMP/HUMIDITY (ENTHALPY) WHEN USING A HEAT PUMP WITH DEFROST FEEDBACK, ADD AN SYLKBUS SENSOR ISOLATION RELAY BETWEEN O AND C. M32653D Fig. 6. Economizer with Sylk bus sensor for enthalpy configuration with Honeywell MS3103 or MS3105 communicating actuators. 62-0331—13...
  • Page 9 TO THERMOSTAT CONV POWER HEAT COOL STATUS LEDS RELAY R822N1011 KIT WITH PRESTIGE AND EIM YTHX9421R5051 TRANSFORMER THM5421R1013 SENSORS THE TRANSFORMER NEEDS TO BE 100VA. M35158 Fig. 7. Economizer with Honeywell MS3103 or MS3105 communicating actuator and thermostat EIM. 62-0331—13...
  • Page 10 WHEN USING A HEAT PUMP WITH DEFROST FEEDBACK, ADD AN ISOLATION RELAY BETWEEN O AND C. M35172 Fig. 8. Economizer with Sylk bus sensor for enthalpy configuration with Honeywell MS3103 or MS3105 communicating actuators, thermostat and VFD for Two-speed fan operation .
  • Page 11 ™ JADE ECONOMIZER MODULE EXH1 OR AUX1 O ACTUATOR NOTE: ON/OFF ACTUATORS CAN BE USED ON THE EXH1 OR AUX1 O TERMINAL WITH GROUND TO THE C TERMINAL. WHEN PROGRAMMING THE EXH1 OR AUX1 O, THE % IS THE PERCENT OPEN POSITION OF THE OUTDOOR AIR DAMPER WHEN THE EXH1 OR AUX1 O TERMINAL IS ENERGIZED AND THE 2-POS DAMPER GOES OPEN.
  • Page 12 (MenuUp/Exit) to return to the Initial Menu Display previous menu. On initial start up, Honeywell displays on the first line and When values are displayed, pressing and holding the Economizer W7220 on the second line. After a brief pause, ...
  • Page 13 ™ JADE ECONOMIZER MODULE Table 4. Menu Structure Parameter Parameter Range and Default Menu Parameter Value Increment Notes YES = economizing available; the system can use Outdoor Air for STATUS ECON AVAIL YES/NO free cooling when required. ECONOMIZING YES/NO YES = Outdoor Air being used for 1 stage cooling.
  • Page 14 ™ JADE ECONOMIZER MODULE Table 4. Menu Structure . (Continued) Parameter Parameter Range and Default Menu Parameter Value Increment Notes Output of AUX1 O terminal, if programmed for EXH2. Displays STATUS EXH2 OUT ON/OFF ON when damper position reaches programmed percentage CONTINUED setpoint ON = 24 Vac Output, OFF = No Output;...
  • Page 15 ™ JADE ECONOMIZER MODULE Table 4. Menu Structure . (Continued) Parameter Parameter Range and Default Menu Parameter Value Increment Notes Only when AUX1 O = ERV SETPOINTS 32ºF 0 to 50 ºF; ERV OAT SP CONTINUED increment by 1 Setpoint for OA damper position when exhaust fan 1 is powered EXH1 SET 0 to 100%;...
  • Page 16 ™ JADE ECONOMIZER MODULE Table 4. Menu Structure . (Continued) Parameter Parameter Range and Default Menu Parameter Value Increment Notes Temp to activate Freeze Protection (close damper or modulate to ADVANCED MA LO SET 45 ºF 35 to 65 ºF; MIN POS if Mixed air temperature falls below set value) SETUP increment by 1º...
  • Page 17 ™ JADE ECONOMIZER MODULE Table 4. Menu Structure . (Continued) Parameter Parameter Range and Default Menu Parameter Value Increment Notes The checkout for the damper minimum positions is based on the DAMPER MINIMUM CHECKOUT system. See Table 5. POSITION Positions damper to the full open position. DAMPER OPEN Exhaust fan contacts enable during the DAMPER OPEN test.
  • Page 18 Heating mode the ERV terminal will be energized when the OA is below the ERV OAT setpoint in the setpoint menu. When used with Honeywell communicating actuator the damper out is reported in XX.X% open versus XX.X Vdc. After 10 minutes without a command or mode change, the controller will change to normal operation.
  • Page 19 ™ JADE ECONOMIZER MODULE SEQUENCE OF OPERATION Table 6. Dry Bulb Operation No DCV (CO2 sensor) - 1 Speed Fan. OA Good to economize? Y1-I Y2-I FAN SPD Y1-O Y2-O Occupied Unoccupied None High 0-v/Off 0-v/Off MIN POS Closed High 24-v/On 0-v/Off MIN POS...
  • Page 20 ™ JADE ECONOMIZER MODULE Table 8. Enthalpy Operation No DCV (CO2 sensor) - 1 Speed Fan. OA Good to economize? Y1-I Y2-I FAN SPD Y1-O Y2-O Occupied Unoccupied None High 0-v/Off 0-v/Off MIN POS Closed High 24-v/On 0-v/Off MIN POS Closed High 24-v/On...
  • Page 21 ™ JADE ECONOMIZER MODULE Table 10. Dry Bulb Operation No DCV (CO2 sensor) - 2 Speed Fan. OA Good to economize? Y1-I Y2-I FAN SPD Y1-O Y2-O Occupied Unoccupied None 0-v/Off 0-v/Off MIN POS L Closed 24-v/On 0-v/Off MIN POS L Closed High 24-v/On...
  • Page 22 ™ JADE ECONOMIZER MODULE Table 12. Enthalpy Operation No DCV (CO2 sensor) - 2 Speed Fan. OA Good to economize? Y1-I Y2-I FAN SPD Y1-O Y2-O Occupied Unoccupied NO CO2 0-v/Off 0-v/Off MIN POS L Closed SENSOR 24-v/On 0-v/Off MIN POS L Closed High 24-v/On...
  • Page 23: Troubleshooting

    ™ JADE ECONOMIZER MODULE TROUBLESHOOTING NOTE: If an alarm still exists after you clear it, it re-dis- plays within 5 seconds. Alarms Checkout Tests The Economizer module provides alarm messages that Use the Checkout menu (Table 4) to test the damper operation display on the 2-line LCD.
  • Page 24 ™ JADE ECONOMIZER MODULE Automation and Control Solutions Honeywell International Inc. 1985 Douglas Drive North ® U.S. Registered Trademark Golden Valley, MN 55422 © 2014 Honeywell International Inc. 62-0331—13 M.S. Rev. 04-14 customer.honeywell.com Printed in United States...

Table of Contents