L7224U
Oil Electronic Aquastat
APPLICATION
The EnviraCOM ™ enabled L7224U Oil Electronic
®
Aquastat
Controller provides electronic temperature
sensing in a UL limit-rated controller with a single
sensing probe. The L7224U controls the circulator, oil
burner and boiler temperature.
The L7224U is "Outdoor Temperature Reset" ready,
which is enabled when connected to the 50022037-002
Outdoor Reset Module. (option 1)
Additionally, the L7224U provides adjustable short cycle.
The L7224U replaces the L8124A, L8124C, L7124U,
L7148A, L7248A,C, L7224A,C, and L8148A Controllers.
The Aquastat Controller is intended for use in residential-
type applications.
The L7224U provides status and diagnostic information
through an LED display combined with LED lights as well
as EnviraCOM enabled thermostats and diagnostic tools
to enhance the diagnostic process.
SPECIFICATIONS
Electrical Ratings:
Voltage: 120 Vac, 60 Hz.
Power: 7 VA maximum at 120 Vac plus external loads.
Thermostat current: 100 mA nominal at 24 Vac.
Burner Relay:
7.4 A at 120 Vac Full Load Amperage (FLA);
44.4 A inrush Locked Rotor Amperage (LRA);
Less Ignition Load: 360 VA.
Circulator Relay:
7.4 A at 120 Vac FLA; 44.4 A inrush LRA.
Zone Controller (ZC): 7.4 A at 120 Vac FLA;
44.4 A inrush LRA.
NOTE: All loads combined cannot exceed 2000 VA.
Environmental Ratings:
Temperature: -30° F to +150° F (-34° C to +66° C).
Humidity: 0 to 95% relative humidity, noncondensing.
Approvals:
Underwriters Laboratories Inc. Component Recognized.
Canadian Underwriters Laboratories Inc. Component
Recognized.
®
Controller
Accessories (Ordered Separately):
50022037-002 AquaReset™ Outdoor Reset Module
C7089U1006 Outdoor Temperature Sensor (used with
the 50022037-002)
W8735S1000 (AquaReset™ Outdoor Reset Kit) includes
50022037-002 and C7089U1006)
50022037-005 Domestic Hot Water Module
32003971-003 Temperature Sensor (used with
50022037-005)
W8735S1008 AquaReset™ Domestic Hot Water Kit
(includes 50022037-005 and 32003971-003)
Sensor (See Table 2).
Sensor Well Clamp 121371AA.
14,000,485-016 1/4 in. (6.35 mm) diameter, 1-1/4 in.
(31.75 mm) length glass cartridge Fuse, 1 A,
Slow-Blow.
120650 Heat Conductive Compound.
Table 1. Wells for L7224U Controller.
Part
Spud Size
Number
in. (mm)
123869A 1/2 (12.7) NPT
123870A 3/4 (19.05) NPT 3 (76.2)
Table 2. Sensors for L7224U Controller.
Length in.
Part Number
(mm)
50001464-001
12 (304.8) Well-mounted controls
50001464-002
18 (457.2) Flush-mounted controls
50001464-003
24 (609.6)
50001464-004
36 (914.4)
50001464-005
48 (1219.2)
Insertion
Insulation
in. (mm)
in. (mm)
3 (76.2)
1-1/2 (38.1)
1-1/2 (38.1)
Application
69-1720-03