6.2
General installation instructions
•
Terminate all branches of the wiring system via a connected bus device (e.g.,
indoor station, outdoor station, system device).
•
Do not install the system controller directly next to the bell transformer and other
power supplies (to avoid interference).
•
Do not install the wires of the system bus together with 100-240 V wires.
•
Do not use common cables for the connecting wires of the door openers and wires
of the system bus.
•
Avoid bridges between different cable types.
•
Use only two wires for the system bus in a four-core or multi-core cable.
•
When looping, never install the incoming and outgoing bus inside the same cable.
•
Never install the internal and external bus inside the same cable.
Pos: 83 /B usch-J aeg er (Neus truk tur )/M odul -Strukt ur/O nline -Doku me ntatio n/Steu er mod ule - Onlin e-Dok ume ntati on ( -- > F ür alle Dok ume nte <- -)/ +++ ++ ++ +++ ++ S eiten umb ruch + +++ ++ ++ +++ + @ 9\m od_ 126 8898 668 093 _0. docx @ 521 49 @ @ 1
|
Check the type supply network (TN system, IT system, TT system)
to secure the following power supply conditions (classic
connection to ground, protective earthing, necessary additional
measures, etc.).