Installing the Chassis
c) Secure the bracket to the chassis using four Number-8 Phillips flat-head screws and tighten each screw to 12 in-lb
(1.36 N·m) of torque.
d) Repeat previous step for the other front rack-mount bracket on the other side of the switch and be sure to position
that bracket the same distance from the front of the switch.
Step 2
Install the chassis into the rack.
a) Use two M4 screws to attach the brackets to the rack.
1
Front-mounting position
Grounding the Chassis
Note
The location of the grounding pad on each switch can be found in the
The switch is grounded when you connect the chassis and the power supplies to the earth ground in the
following ways:
• You connect the chassis (at its grounding pad) to the data center ground. If the rack is fully-bonded and
grounded, you can ground the switch by connecting it to the rack.
2
M4 screws (2 each side)
Overview
Cisco Nexus 3600 Hardware Installation Guide
Grounding the Chassis
section.
17