Preface SIMATIC ET 200S distributed I/O 2AI TC HF analog electronic module (6ES7134-4NB01-0AB0) ______________ Properties ______________ Parameters SIMATIC ______________ Diagnostics ET 200S distributed I/O 2AI TC HF analog electronic ______________ Analog value representation module (6ES7134-4NB01-0AB0) ______________ Connecting Manual 04/2007 A5E01076892-01...
Page 2
Trademarks All names identified by ® are registered trademarks of the Siemens AG. The remaining trademarks in this publication may be trademarks whose use by third parties for their own purposes could violate the rights of the owner.
Additional support If you have any questions relating to the products described in these operating instructions, and do not find the answers in this document, please contact your local Siemens representative. http://www.siemens.com/automation/partner...
Page 4
● The bulletin board, a worldwide knowledge exchange for users and experts. ● Your local contact for Automation & Drives in our contact database. ● Information about on-site services, repairs, spare parts. Lots more can be found on our "Services" pages. 2AI TC HF analog electronic module (6ES7134-4NB01-0AB0) Manual, 04/2007, A5E01076892-01...
Table of contents Preface ..............................3 Properties ..............................7 2AI TC HF analog electronic module (6ES7134-4NB01-0AB0) ............7 Parameters .............................. 13 Parameters...........................13 Parameter description........................14 Diagnostics .............................. 15 Diagnostics using LED display.....................15 Error types............................16 Analog value representation ........................17 Introduction ..........................17 Analog value representation for measuring range with SIMATIC S7 ..........17 Measuring ranges ........................19...
Page 6
Table of contents 2AI TC HF analog electronic module (6ES7134-4NB01-0AB0) Manual, 04/2007, A5E01076892-01...
Properties 2AI TC HF analog electronic module (6ES7134-4NB01-0AB0) Properties ● 2 inputs for thermocouple or voltage measurement ● Input ranges: – Voltage measurement: ± 80 mV, resolution 15 bits + sign – Thermocouples: Types E, N, J, K, L, S, R, B, T, C, resolution 15 bits + sign ●...
Page 8
Properties 1.1 2AI TC HF analog electronic module (6ES7134-4NB01-0AB0) Usable terminal modules Usable terminal modules for 2AI TC HF (6ES7134-4NB01-0AB0) TM-E15C24-AT Spring terminal (6ES7193-4CL30-0AA0) TM-E15S24-AT (6ES7193-4CL20-0AA0) Screw-type terminal Block diagram Figure 1-1 Block diagram of the 2AI TC HF 2AI TC HF analog electronic module (6ES7134-4NB01-0AB0)
Page 9
Properties 1.1 2AI TC HF analog electronic module (6ES7134-4NB01-0AB0) 2AI TC HF technical specifications (6ES7134-4NB01-0AB0) Dimensions and weight Width (mm) Weight Approx. 40 g Module-specific data Supports isochronous operation Number of inputs Cable length Shielded • Max. 50 m Parameter length...
Page 10
Properties 1.1 2AI TC HF analog electronic module (6ES7134-4NB01-0AB0) Suppression of interference, limits of error Noise suppression for f = n x (f1 ± 1 %), (f1 = interference frequency) Common-mode interference (U • min. 90 dB min. 70 dB Series-mode interference •...
Page 11
Compensation of thermocouples with a compensating box As well as the error limits of the 2AI TC HF electronic module (see Table "Technical specifications 2AI TC HF (6ES7134-4NB01-0AB0)" in this chapter) you must also take the accuracy of the compensating box into account.
TC-EL Type L (Fe-Cu-Ni) • Only with thermocouples. A parameter assignment error occurs when the wire break diagnostics are enabled in the voltage measuring range. The module does not start up. 2AI TC HF analog electronic module (6ES7134-4NB01-0AB0) Manual, 04/2007, A5E01076892-01...
The following diagrams show the step response with the various smoothing factors in relation to the number of module cycles. Figure 2-1 Smoothing with the 2AI TC HF 2AI TC HF analog electronic module (6ES7134-4NB01-0AB0) Manual, 04/2007, A5E01076892-01...
Event (LED) Cause Remedy No configuration or incorrect Check the parameter module plugged in. No load assignment. Check the load voltage.present There is a voltage. Evaluate the diagnostic message. diagnostics. 2AI TC HF analog electronic module (6ES7134-4NB01-0AB0) Manual, 04/2007, A5E01076892-01...
00110: Line to the encoder Correct the process wiring. Open circuit interrupted. 10101: Error on the reference channel Check the reference module Reference channel error 2AI TC HF analog electronic module (6ES7134-4NB01-0AB0) Manual, 04/2007, A5E01076892-01...
Analog value Bit number Significance of the bits Sign The sign (S) of the analog value is always in bit number 15: ● "0" → + ● "1" → – 2AI TC HF analog electronic module (6ES7134-4NB01-0AB0) Manual, 04/2007, A5E01076892-01...
Page 18
S 0 0 0 0 0 0 0 0 0 0 0 1 x x 15 + sign S 0 0 0 0 0 0 0 0 0 0 0 0 0 1 2AI TC HF analog electronic module (6ES7134-4NB01-0AB0) Manual, 04/2007, A5E01076892-01...
Overflow 7FFF End of the overshoot range +1 plus overflow bit Underflow 8000 End of the underrange -1 plus overflow Prior to parameter assignment, or 7FFF 7FFF incorrect parameter assignment 2AI TC HF analog electronic module (6ES7134-4NB01-0AB0) Manual, 04/2007, A5E01076892-01...
Page 26
Analog value representation 4.4 Effect on analog value representation 2AI TC HF analog electronic module (6ES7134-4NB01-0AB0) Manual, 04/2007, A5E01076892-01...
The steps you have to take are described in this chapter. 2AI TC HF analog electronic module (6ES7134-4NB01-0AB0) Manual, 04/2007, A5E01076892-01...
Page 28
The following schematic representation illustrates the connection of isolated measuring encoders to the optically isolated analog input modules. ① Logic ② Backplane bus ③ Ground bus ④ Central grounding point ⑤ Isolated measuring encoders 2AI TC HF analog electronic module (6ES7134-4NB01-0AB0) Manual, 04/2007, A5E01076892-01...
Page 29
Logic ② Backplane bus ③ Ground bus ④ Equipotential bonding conductor ⑤ Non-isolated measuring encoders Non-isolated thermocouples When using non-isolated thermocouples, you must comply with the permitted common mode voltage. 2AI TC HF analog electronic module (6ES7134-4NB01-0AB0) Manual, 04/2007, A5E01076892-01...
ET 200S terminal module. The compensating lines are made of the same material as the wires of the thermocouple. The supply lines are made of copper. Ensure the correct polarity when connecting. 2AI TC HF analog electronic module (6ES7134-4NB01-0AB0) Manual, 04/2007, A5E01076892-01...
● To adhere to the permissible potential differences (U ), you must wire jumpers on the terminal module for the unused channels. Analog input module TM connecting terminal Channel 0 Channel 1 2AI TC HF 2AI TC HF analog electronic module (6ES7134-4NB01-0AB0) Manual, 04/2007, A5E01076892-01...
Page 32
● Use shielded wires to the sensors and actuators. ● Lay out the wire shields on the shield connection. ● Connect the shield connection to the ground bus with low impedance. 2AI TC HF analog electronic module (6ES7134-4NB01-0AB0) Manual, 04/2007, A5E01076892-01...