  • Page 2 ___________________ Preface ___________________ Documentation guide ___________________ SIMATIC Product overview ___________________ Wiring ET 200SP Digital output module ___________________ DI 8x24VDC SRC BA Parameters/address space (6ES7131-6BF61-0AA0) ___________________ Interrupts/diagnostics alarms Manual ___________________ Technical specifications ___________________ Parameter data record 09/2017 A5E32855511-AC...
  • Page 3 Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
  • Page 4: Preface

    Purpose of the documentation This manual supplements the system manual ET 200SP distributed I/O system (http://support.automation.siemens.com/WW/view/en/58649293). Functions that generally relate to the system are described in this manual. The information provided in this manual and in the system/function manuals supports you in commissioning the system.
  • Page 5 Siemens' products and solutions undergo continuous development to make them more secure. Siemens strongly recommends that product updates are applied as soon as they are available and that the latest product versions are used. Use of product versions that are no longer supported, and failure to apply the latest updates may increase customers' exposure to cyber threats.
  • Page 6: Table Of Contents

    Table of contents Preface ..............................4 Documentation guide ..........................7 Product overview ..........................12 Properties ..........................12 Wiring ..............................14 Wiring and block diagram ...................... 14 Parameters/address space ........................17 Parameters ..........................17 Explanation of parameters ..................... 19 Address space ........................20 Interrupts/diagnostics alarms.........................
  • Page 7: Documentation Guide

    Documentation guide The documentation for the SIMATIC ET 200SP distributed I/O system is arranged into three areas. This arrangement enables you to access the specific content you require. Basic information The system manual describes in detail the configuration, installation, wiring and commissioning of the SIMATIC ET 200SP.
  • Page 8 Documentation guide General information The function manuals contain detailed descriptions on general topics regarding the SIMATIC ET 200SP distributed I/O system, e.g. diagnostics, communication, Web server, motion control and OPC UA. You can download the documentation free of charge from the Internet (https://support.industry.siemens.com/cs/ww/en/view/109742709).
  • Page 9 With the TIA Selection Tool, you can select, configure and order devices for Totally Integrated Automation (TIA). This tool is the successor of the SIMATIC Selection Tool and combines the known configurators for automation technology into one tool. With the TIA Selection Tool, you can generate a complete order list from your product selection or product configuration.
  • Page 10 SIMATIC Automation Tool You can use the SIMATIC Automation Tool to run commissioning and maintenance activities simultaneously on various SIMATIC S7 stations as a bulk operation independently of the TIA Portal. The SIMATIC Automation Tool provides a multitude of functions: ●...
  • Page 11 Documentation guide SINETPLAN SINETPLAN, the Siemens Network Planner, supports you in planning automation systems and networks based on PROFINET. The tool facilitates professional and predictive dimensioning of your PROFINET installation as early as in the planning stage. In addition, SINETPLAN supports you during network optimization and helps you to exploit network resources optimally and to plan reserves.
  • Page 12: Product Overview

    Product overview Properties Part number 6ES7131-6BF61-0AA0 View of the module ① ⑦ Module type and name Function class ② ⑧ LED for diagnostics Color coding module type ③ ⑨ 2D matrix code Function and firmware version ④ ⑩ Wiring diagram Color code for selecting the color identification labels ⑤...
  • Page 13 ● Color identification labels ● Reference identification label ● Shield connector See also You can find additional information on the accessories in the ET 200SP distributed I/O system (http://support.automation.siemens.com/WW/view/en/58649293) system manual. Digital output module DI 8x24VDC SRC BA (6ES7131-6BF61-0AA0) Manual, 09/2017, A5E32855511-AC...
  • Page 14: Wiring

    1-wire, 2-wire and 3-wire connection. Information about wiring of the BaseUnit is available in the system manual ET 200SP distributed I/O system (http://support.automation.siemens.com/WW/view/en/58649293). Note You may use and combine the different wiring options for all channels.
  • Page 15 Wiring 3.1 Wiring and block diagram Connection: 1-wire and 2-wire connection The following figure shows the block diagram and an example of the terminal assignment of the digital input module DI 8x24VDC SRC BA on the BaseUnit BU type A0 without AUX terminals (1-wire and 2-wire connection).
  • Page 16 Wiring 3.1 Wiring and block diagram Connection: 3-wire connection The following figure shows the block diagram and an example of the terminal assignment of the digital input DI 8x24VDC SRC BA on the BaseUnit BU type A0 with AUX terminals (3- wire connection).
  • Page 17: Parameters/Address Space

    Parameters/address space Parameters DI 8×24VDC SRC BA parameters Specify the module properties with the various parameters in the course of your STEP 7 configuration. The following table lists the configurable parameters. The effective range of the configurable parameters depends on the type of configuration. The following configurations are possible: ●...
  • Page 18 Parameters/address space 4.1 Parameters Parameter Value range Default Reconfig- Scope with configuration software, uration in e.g. STEP 7 (TIA Portal) GSD file GSD file PROFINET IO PROFIBUS DP Input delay 3.2 ms Channel Module None • 0.05 ms • 0.1 ms •...
  • Page 19: Explanation Of Parameters

    Parameters/address space 4.2 Explanation of parameters Explanation of parameters Diagnostics: No supply voltage L+ Enabling of the diagnostics for no or insufficient supply voltage L+. Channel activated Determines whether a channel is activated or deactivated. Input delay This parameter can be used to suppress signal interference. Changes to the signal are only detected if they are constantly pending longer than the set input delay time.
  • Page 20: Address Space

    Parameters/address space 4.3 Address space Address space The module can be configured differently in STEP 7; see following table. Depending on the configuration, additional/different addresses are assigned in the process image of the inputs. Configuration options of DI 8x24VDC SRC BA You can configure the module with STEP 7 (TIA Portal) or with a GSD file.
  • Page 21: Interrupts/Diagnostics Alarms

    Interrupts/diagnostics alarms Status and error displays LED displays The figure below shows the LED displays (status and error displays) of the DI 8x24VDC SRC BA. ① DIAG (green/red) ② Channel status (green) ③ PWR (green) Figure 5-1 LED display Digital output module DI 8x24VDC SRC BA (6ES7131-6BF61-0AA0) Manual, 09/2017, A5E32855511-AC...
  • Page 22 Interrupts/diagnostics alarms 5.1 Status and error displays Meaning of the LED displays The tables below explain the meaning of the Status and error displays. Remedial measures for diagnostics alarms can be found in section Diagnostics alarms (Page 23). LED DIAG Table 5- 1 Error display of the LED DIAG LED DIAG...
  • Page 23: Interrupts

    Interrupts/diagnostics alarms 5.2 Interrupts Interrupts The DI 8×24VDC SRC BA digital input module supports diagnostics interrupts. Diagnostics interrupts The module generates a diagnostic interrupt at the following event: ● Parameter assignment error ● No supply voltage Detailed information on the event is available in the STEP 7 online help. Diagnostics alarms Diagnostics alarms A diagnostic alarm is generated and the DIAG-LED flashes on the module for each...
  • Page 24: Technical Specifications

    Technical specifications Technical specifications Technical specifications of the DI 8×24VDC SRC BA Article number 6ES7131-6BF61-0AA0 General information Product type designation DI 8x24 VDC SRC BA Firmware version V0.0 FW update possible • usable BaseUnits BU type A0 Color code for module-specific color identifica- CC02 tion plate Product function...
  • Page 25 Technical specifications 6.1 Technical specifications Article number 6ES7131-6BF61-0AA0 Address area Address space per module 1 byte Inputs • Hardware configuration Automatic encoding Selection of BaseUnit for connection variants BU type A0 1-wire connection • BU type A0 2-wire connection • BU type A0 with AUX terminals 3-wire connection •...
  • Page 26 Technical specifications 6.1 Technical specifications Article number 6ES7131-6BF61-0AA0 Encoder Connectable encoders 2-wire sensor • 1.5 mA – permissible quiescent current (2-wire sensor), max. Isochronous mode Isochronous operation (application synchro- nized up to terminal) Interrupts/diagnostics/status information Diagnostics function Alarms Diagnostic alarm •...
  • Page 27 6.1 Technical specifications Article number 6ES7131-6BF61-0AA0 Dimensions Width 15 mm Height 73 mm Depth 58 mm Weights Weight, approx. 28 g Dimensional drawing See the manual ET 200SP BaseUnits (http://support.automation.siemens.com/WW/view/en/58532597/133300) Digital output module DI 8x24VDC SRC BA (6ES7131-6BF61-0AA0) Manual, 09/2017, A5E32855511-AC...
  • Page 28: Parameter Data Record

    Parameter data record Parameter assignment and structure of parameter data record The data record of the module has an identical structure, regardless of whether you configure the module with PROFIBUS DP or PROFINET IO. With data record 128, you can reconfigure the module in your user program regardless of your programming.
  • Page 29 Parameter data record A.1 Parameter assignment and structure of parameter data record Structure of data record 128 Note Channel 0 includes the diagnostics for the entire module. Figure A-1 Structure of data record 128 Header information The figure below shows the structure of the header information. Figure A-2 Header information Digital output module DI 8x24VDC SRC BA (6ES7131-6BF61-0AA0)
  • Page 30 Parameter data record A.1 Parameter assignment and structure of parameter data record Parameters The figure below shows the structure of the parameters for channels 0 to 7. Enable a parameter by setting the corresponding bit to "1". Figure A-3 Structure byte x to x+1 for the channels 0 to 7 Digital output module DI 8x24VDC SRC BA (6ES7131-6BF61-0AA0) Manual, 09/2017, A5E32855511-AC...
  • Page 31 Parameter data record A.1 Parameter assignment and structure of parameter data record Error transferring the data record The module always checks all the values of the transferred data record. Only if all the values were transferred without errors does the module apply the values from the data record. The WRREC instruction for writing data records returns corresponding error codes when errors occur in the STATUS parameter, see also the description of the "STATUS"...