Safety with Electricity
High leakage current – earth connection essential before connection to system power supply. Statement
Warning
342
Warning
Avoid using or servicing any equipment that has outdoor connections during an electrical storm. There
may be a risk of electric shock from lightning. Statement 1088
Warning
Before performing any of the following procedures, ensure that power is removed from the DC circuit.
Statement 1003
Warning
Read the installation instructions before connecting the system to the power source. Statement 1004
Warning
This product relies on the building's installation for short-circuit (overcurrent) protection. Ensure that the
protective device is rated: For a -48/-60 VDC installation, the wire shall be 12 AWG minimum with a 20
A branch circuit breaker. For a 24 VDC installation, the wire shall be 8 AWG minimum with a 40 A
branch circuit breaker. Statement 1005
Warning
This product relies on the building's installation for short-circuit (overcurrent) protection. For an AC
installation, ensure that the branch circuit breaker is rated a maximum 20A. Statement 1005
There is the danger of explosion if the battery is replaced incorrectly. Replace the battery only with the
Warning
same or equivalent type recommended by the manufacturer. Dispose of used batteries according to the
manufacturer's instructions. Statement 1015
This unit is intended for installation in restricted access areas. A restricted access area can be accessed
Warning
only through the use of a special tool, lock and key, or other means of security. Statement 1017
Take care when connecting units to the supply circuit so that wiring is not overloaded. Statement 1018
Warning
The plug-socket combination must be accessible at all times, because it serves as the main disconnecting
Warning
device. Statement 1019
Cisco ASR 902 and ASR 902U Aggregation Services Router Hardware Installation Guide
44
Preparing for Installation