Terminal Connection Diagram; Control Circuit - Mitsubishi Electric FR-E720-0.1K Instruction Manual

Fr-e700 series
Hide thumbs Also See for FR-E720-0.1K:
Table of Contents

Advertisement

Wiring
2.3
Wiring
2.3.1

Terminal connection diagram

Sink logic
Main circuit terminal
Control circuit terminal
Single-phase power input
MCCB
Single-phase
AC power
supply
MCCB
Three-phase
AC power
supply
Control input signals (No voltage input allowed)
Forward
Terminal functions vary
rotation start
with the input terminal
Reverse
assignment (Pr. 178 to
rotation start
Pr. 184)
Multi-speed selection
*2 When using terminals PC
and SD as a 24VDC
power supply, take care
not to short across
terminals PC and SD.
Contact input common
24VDC power supply
(Common for external power supply transistor)
Frequency setting signals (Analog)
*3 Terminal input specifications
can be changed by analog
input specifications
switchover (Pr. 73).
*4 It is recommended to use 2W1kΩ
when the frequency setting signal
is changed frequently.
Terminal 4 input
(Current input)
*5 Terminal input specifications can be changed by analog
input specifications switchover (Pr. 267). Set the
voltage/current input switch in the "V" position to select
voltage input (0 to 5V/0 to10V) and "I" (initial value) to
select current input (4 to 20mA).
To use terminal 4 (initial setting is current input), set "4"
in any of Pr.178 to Pr.184 (input terminal function selection)
to assign the function, and turn ON AU signal.
NOTE
 To prevent a malfunction caused by noise, separate the signal cables more than 10cm from the power cables. Also
separate the main circuit wire of the input side and the output side.
 After wiring, wire offcuts must not be left in the inverter.
Wire offcuts can cause an alarm, failure or malfunction. Always keep the inverter clean. When drilling mounting holes
in an enclosure etc., take care not to allow chips and other foreign matter to enter the inverter.
 The output of the single-phase power input model is three-phase 200V.
9
*1. DC reactor (FR-HEL)
When connecting a DC reactor, remove the
jumper across P1-P/+.
MC
R/L1
Earth
S/L2
(Ground)
MC
R/L1
S/L2
T/L3
Earth
(Ground)
STF
STR
RH
High
speed
RM
Middle
speed
RL
Low
speed
MRS
Output
stop
RES
Reset
SD
PC
10(+5V)
3
Frequency
setting
2 0 to 5VDC
2
potentiometer
(0 to 10VDC)
1/2W1kΩ
*4
5(Analog common)
1
(+)
4 4 to 20mADC
(-)
0 to 5VDC
0 to 10VDC
I
Voltage/current
input switch
Brake unit
(Option)
*1
R
*7
Jumper
PR N/-
*6
P1
P/+
Main circuit

Control circuit

RUN
*2
*3
PU
connector
*9
*5
V
USB
*5
connector
*10
Ethernet
connector
*6 A brake transistor is not built-in to the
0.1K and 0.2K.
*7 Brake resistor (FR-ABR, MRS, MYS type)
Install a thermal relay to prevent an
overheat and burnout of the brake resistor.
(The brake resistor cannot be connected
to the 0.1K and 0.2K.)
V
W
Standard control terminal block
Relay output
C
Terminal functions vary
B
by Pr. 192 A,B,C terminal
Relay output
function selection
(Fault output)
A
Open collector output
Terminal functions vary with
the output terminal assignment
Running
(Pr. 190 and Pr. 191)
FU
Frequency detection
Open collector output common
SE
Sink/source common
Calibration resistor
Indicator
+
-
(Frequency meter, etc.)
Moving-coil type
FM
1mA full-scale
*8
SD
*8 It is not necessary when calibrating the
indicator from the operation panel.
*9 Operation and parameter setting can be
done from the parameter unit (FR-PU07)
and the enclosure surface operation panel
(FR-PA07).
(Use the option cable (FR-CB2
RS-485 communication can be utilized from
a personal computer and other devices.
*10 A personal computer and an inverter can be
connected with a USB (Ver1.1) cable.
You can perform parameter setting and
monitoring with the FR Configurator2
(SW1DND-FRC2- ).
Motor
IM
Earth (Ground)
).)