Benefit
Description
Setting
Effect
82/184
Siemens Building Technologies
Landis & Staefa Division
2.22
Extra heating for the bathroom
Heating the bathroom by making use of the surplus heat obtained after d.h.w. heating.
This ancillary heating is provided in addition to normal bathroom heating. It is used
especially during intermediate seasons by supplying surplus heat to the bathroom on
completion of d.h.w. heating.
Setting range
0 / 1
The setting ensures that both the d.h.w. charging pump and heating circuit pump 2 will
overrun.
Entry:
0
OFF: D.h.w. pump overrun acts exclusively on the d.h.w. charging pump (Q3)
1
ON: D.h.w. pump overrun acts on both the d.h.w. charging pump (Q3) and
heating circuit pump 2 (Q6)
2.22.1
Extra heating for the bathroom
Extra heating for the bathroom makes use of the d.h.w. pump overrun. It is used
especially during intermediate seasons by supplying surplus heat to the bathroom, in
addition to normal bathroom heating.
Surplus boiler heat after a d.h.w. heating cycle is supplied to the pump heating circuit
via overrun of heating circuit pump 2. The pump overrun is fixed at 30 minutes.
This function is an uncontrolled fixed process, parallel to the actual operation of the
pump heating circuit.
When automatic summer / winter changeover of the pump heating circuit has
responded, extra heating for the bathroom will also be switched off.
Basic Dokumentation RVA63.280, RVA53.280
Unit
Increment
Factory setting
0
CE1P2374E
19.04.2001