hit counter script
Honeywell ST 700 User Manual

Honeywell ST 700 User Manual

Smartline series
Hide thumbs Also See for ST 700:
Table of Contents

Advertisement

ST 700 SmartLine Series HART/DE
Option
User's Manual
34-ST-25-47
Revision 4.0
December 2016
Honeywell Process Solutions

Advertisement

Table of Contents
loading

Summary of Contents for Honeywell ST 700

  • Page 1 ST 700 SmartLine Series HART/DE Option User’s Manual 34-ST-25-47 Revision 4.0 December 2016 Honeywell Process Solutions...
  • Page 2 In no event is Honeywell liable to anyone for any indirect, special, or consequential damages. The information and specifications in this document are subject to change without notice.
  • Page 3: About This Manual

     The ST 700 SmartLine Pressure transmitter can be digitally integrated with one of two systems:Experion PKS: you will need to supplement the information in this document with the data and procedures in the Experion Knowledge Builder.
  • Page 4 Patent Notice The Honeywell ST 700 SmartLine Pressure Transmitter family is covered by one or more of the following U. S. Patents: 5,485,753; 5,811,690; 6,041,659; 6,055,633; 7,786,878; 8,073,098; and other patents pending. Support and Contact Information For Europe, Asia Pacific, North and South America contact details, refer to the appropriate...
  • Page 5: Table Of Contents

    Overview ..........................7 Digitally Enhanced (DE) Mode Communication ..............7 HART Mode Communication ....................8 Configuration Tools and Interfaces for ST 700 Standard Transmitter .......... 9 Overview ..........................9 Pre-requisites .......................... 9 Application Design, Installation, Startup, and Operation ............9 4.3.1...
  • Page 6 Correcting the Upper Range Value (URV) ..............71 8.3.3 Resetting Calibration....................72 8.3.4 Calibration Records...................... 72 HART Advanced Diagnostics for ST 700 Standard Transmitter ..........75 About This Section ......................75 Advanced Diagnostics......................75 9.2.1 Install Date ........................75 9.2.2 PV Tracking Diagnostics .....................
  • Page 7 Common setup: ....................... 107 11.20 Review ..........................108 11.21 ST 700 Offline Parameterization ..................109 . HART DD binary file format compatibility matrix for ST 700 Standard Transmitter ..110 ST 700 Series HART/DE Option User’s Manual Revision 4.0 Page vii...
  • Page 8 Integrated 2-Push Button Assembly (Standard Display) ........... 115 Communication Modes for ST 700 Basic Transmitter ............116 14.1 Overview ..........................116 14.2 HART Mode Communication .................... 116 Configuration Tools and Interfaces for ST 700 Basic Transmitter ........118 15.1 Overview ..........................118 15.2 Pre-requisites ........................118 15.3 Application Design, Installation, Startup and Operation ...........
  • Page 9 Correcting the Upper Range Value (URV) ..............149 17.3.3 Resetting Calibration ....................150 17.3.4 Calibration Records ....................150 HART Advanced Diagnostics for ST 700 Basic Transmitter ..........152 18.1 About This Section ......................152 18.2 Advanced Diagnostics ......................152 18.2.1 Install Date........................
  • Page 10 20.20 Review ........................... 181 20.21 ST 700 Offline Parameterization ................... 182 . HART DD binary file format compatibility matrix for ST 700 Standard Transmitter ..183 Glossary ............................. 184 INDEX ............................... 186 Sales and Service ..........................188 ST 700 Series HART/DE Option User’s Manual Page x Revision 4.0...
  • Page 11 Figure 20 – FDC Homepage....................... 122 Figure 21 – Device Homepage ......................127 List of Tables Table 1 - ST 700 Standard and Basic Transmitter Model Types ............2 Table 2 – Features and Options ......................1 Table 3 – Available Display Characteristics ..................5 Table 4 –...
  • Page 12 Table 49 – Minimum Sensor CPU Temperature Tracking ..............159 Table 50 – Power Up Diagnostics...................... 160 Table 51 – HART Diagnostic Messages .................... 162 Table 52 – HART Critical and Non-Critical Diagnostic Details ............163 ST 700 Series HART/DE Option User’s Manual Page xii Revision 4.0...
  • Page 13: Overview

    1 ST 700 Transmitter Series 1.1 Overview SmartLine Pressure Transmitter ST 700 family conists of a series of ST 700 Standard Transmitter models and a series of ST 700 Basic Transmitter models. The entire manual is broadly classified in two two sections.
  • Page 14: Table 1 - St 700 Standard And Basic Transmitter Model Types

    Table 1 - ST 700 Standard and Basic Transmitter Model Types Smart Line Pressure ST 700 Transmitter Configuration Standard Models Basic Models Dual head DP STD720/730/770 STD725/735/775 Dual head GP STG730/740/770 STG735/745/775 Inline GP STG73L/74L/77L/78L/79L STG73S/74S/77S/78S/79S Inline flush GP STG73P...
  • Page 15: St 700 Transmitter Series

    2 Introduction to the ST 700 Standard Transmitter This section is an introduction to the physical and functional characteristics of Honeywell’s ST 700 Standard SmartLine Pressure Transmitter. 2.1 Features and Options The ST 700 Standard SmartLine Pressure Transmitter is available in a variety of models for measuring Differential Pressure (DP), Gauge Pressure (GP), and Absolute Pressure (AP).
  • Page 16: Figure 1 - St 700 Standard Major Assemblies

    Figure 1 – ST 700 Standard Major Assemblies Figure 2 – Electronics Housing Components ST 700 Series HART/DE Option User’s Manual Page 2 Revision 4.0...
  • Page 17: Functional Characteristics

    Honeywell Multi-Communication (MC) Toolkit (not supplied with the Transmitter) can facilitate setup and adjustment procedures. Certain adjustments can be made through an Experion Station or a Universal Station if the Transmitter is digitally integrated with Honeywell’s Experion or TPS/TDC 3000 control system.
  • Page 18: Transmitter Adjustments

    Certain adjustments can also be made through the Experion or Universal Station if the Transmitter is digitally integrated with a Honeywell Experion or TPS system. ST 700 HART models can be configured using Honeywell tools such as Experion in conjunction with FDM, using DTMs running in FDM or Pactware, or Emerson 375 or 475.
  • Page 19: Display Options -Standard Display

    Potential savings on hand-held units  Suitable for all environments: hermetically sealed for long life in harsh environments  Suitable for use in all electrical classifications (flameproof, dustproof, and intrinsically safe) ST 700 Series HART/DE Option User’s Manual Revision 4.0 Page 5...
  • Page 20: Optional Integrated Two-Button Assembly (Standard Display)

    4mA. Upper range value (URV): A display parameter (Standard display), which allows users to enter the measuring value for which the analog output will be scaled to 20mA. ST 700 Series HART/DE Option User’s Manual Page 6 Revision 4.0...
  • Page 21: Communication Model For St 700 Standard Transmitter

    Transmitter 3.1 Overview The ST 700 Standard SmartLine Pressure Transmitter can be configured for operation with Honeywell’s Digitally Enhanced (DE) communication protocol, HART version 7, and Fieldbus communication. This manual addresses the processes to configure and calibrate a Transmitter for DE and HART communication.
  • Page 22: Hart Mode Communication

    HART communication will not bump process variables. In multi-drop mode, up to 16 transmitters in HART 5 (addresses 0-15) and up to 64 transmitters in HART6/7 (addresses 0-63) can exist on the two-conductor network. ST 700 Series HART/DE Option User’s Manual Page 8 Revision 4.0...
  • Page 23: Configuration Tools And Interfaces For St 700 Standard Transmitter

    MCT404/202 is the model name for the Honeywell MC Toolkit product. Furthermore, we assume that the reader is intimately familiar with the ST 700 family of SmartLine Pressure Transmitters and thoroughly experienced in the type of process application targeted for Transmitter deployment.
  • Page 24: Mc Toolkit Participation

    (i.e., trips) need to be disabled, as appropriate, before starting a procedure. 4.4.1 MC Toolkit Software Applications The MC Toolkit has two software applications to work with ST 700 Standard SmartLine Pressure Transmitters:  Field Device Configurator (FDC): This application is used for configuring, calibrating, monitoring, and diagnosing HART devices.
  • Page 25: Mc Toolkit-Transmitter Electrical/Signal Connections

    MC Toolkit directly to the terminals of a HART or DE Transmitter (top), and a HART-only Transmitter (bottom). Figure 6 – MC Toolkit-Transmitter Electrical/Signal Connections ST 700 Series HART/DE Option User’s Manual Revision 4.0 Page 11...
  • Page 26: De Transmitter Configuration For St 700 Standard Transmitter

    Toolkit (SCT 3000), Experion PKS, and Smart Field Communicator (SFC). 5.2 MC Toolkit Software Application Overview Each new ST 700 Standard SmartLine Pressure Transmitter is shipped from the factory with a basic configuration installed. This basic configuration must be edited or revised to meet the requirements of your process system.
  • Page 27: De Transmitter Online Configuration

    4. When the warning message for connecting to a DE device appears, click OK. 5. Process the three warning pop-ups as appropriate, and then click OK in the Put loop in Manual… pop-up. The DE QUICK MONITOR box will be displayed. ST 700 Series HART/DE Option User’s Manual Revision 4.0 Page 13...
  • Page 28 Output Mode during calibration, and was not subsequently cleared. If you confirm the message (Yes answer), the display will exit the DE MAIN MENU. ST 700 Series HART/DE Option User’s Manual Page 14 Revision 4.0...
  • Page 29: Device Information Configuration

    Manufacturer’s firmware version identifier Firmware Version PROM ID Number PROM ID Number Scratch Pad Up to 32 alphanumeric characters Click the Back button to return to the DE MAIN MENU. ST 700 Series HART/DE Option User’s Manual Revision 4.0 Page 15...
  • Page 30: General Configuration Parameters

    Communication Analog, DE 4-byte, or DE 6-byte Mode Failsafe (FS) direction: upscale or downscale, switch selectable on the electronics module. See the ST 700 FS Direction SmartLine Transmitter User Manual, 34-ST-25-44 for details. Click the Back button to return to the DE MAIN MENU.
  • Page 31: De-Specific Configuration Parameters

    Process Range: URV – LRV, Floating Point Span Conformity: for the output calculation. Linear (pressure) or Conformity Square Root (flow); (see note below) Click the Back button to return to the DE MAIN MENU. ST 700 Series HART/DE Option User’s Manual Revision 4.0 Page 17...
  • Page 32 (% Flow X 16) + 4 = mA DC Output To avoid unstable output at readings near zero, the ST 700 Transmitter automatically drops square root conformity and changes to linear conformity for low differential pressure readings. As shown in Figure 7, the dropout point is between 0.4% and 0.5% of differential pressure, depending on direction...
  • Page 33: Transmitter Display Configuration

    5.3.5 Transmitter Display Configuration From the DE MAIN MENU, click the Local Display button. The LOCAL DISPLAY box will be displayed. Click display parameters from the options listed in Table 8 ST 700 Series HART/DE Option User’s Manual Revision 4.0 Page 19...
  • Page 34: Table 8 - Local Display Configuration Parameters

    Flow EU Upper Value Floating point (for square root configurations) Flow EU Lower Value Floating point (for square root configurations) Click the Back button to return to the DE MAIN MENU. ST 700 Series HART/DE Option User’s Manual Page 20 Revision 4.0...
  • Page 35: Monitor Status Configuration

    Device Status button to display device status. Communication Refer to the Messages and Diagnostic Codes section Status of the MCT404/202 Toolkit manual. Click the Back button to return to the DE MAIN MENU. ST 700 Series HART/DE Option User’s Manual Revision 4.0 Page 21...
  • Page 36: Saving The Configuration To File

    New1. e. After entering the file name, click the Save button to display the DE MAIN MENU. ST 700 Series HART/DE Option User’s Manual Page 22 Revision 4.0...
  • Page 37: De Online Configuration Summary

    The MC Tookit can process more than one device type or model. For the purposes of this section, the term device refers to the SmartLine Pressure Transmitter ST 700 Standard, and/or one of its model variants. 5.4.2 DE Offline File Management Offline configuration allows you to click a basic template, edit its parameter content, and download it to a Transmitter after establishing communication.
  • Page 38: Save To A File

    5.4.5 DE Offline Parameterization. A table in Section 6, Offline Configuration, of the MC Tookit User Manual, Document #34-ST-25-80 contains a list of the basic ST 700 Standard SmartLine Pressure Transmitter parameters for DE operation. ST 700 Series HART/DE Option User’s Manual Page 24 Revision 4.0...
  • Page 39: Hart Transmitter Configuration For St 700 Standard Transmitter

    ST 700 Standard Transmitter 6.1 Overview Each new ST 700 Standard Pressure Transmitter configured for HART protocol is shipped from the factory with a basic configuration database installed. This basic configuration database must be edited or revised to meet the requirements of your process system. The process in this section assumes that you will use the Field Device Communicator (FDC) application for HART configuration tasks.
  • Page 40: Overview Of Fdc Homepage

    Tap to quit FDC. Note: To select a particular option in FDC you can either select the option and then tap Select or you can directly double-tap the option. ST 700 Series HART/DE Option User’s Manual Page 26 Revision 4.0...
  • Page 41: Settings

    With this option enabled, FDC creates necessary log files for troubleshooting and diagnostics. These files are stored in SD Card\FDC folder. Note: You must not enable this option unless suggested by Honeywell TAC because this may impact the application performance.
  • Page 42: Manage Dds

    If the DD file is added successfully, a success message appears. 6.2.2.3 Delete a DD file Using this option, you can delete a particular version of a DD file. ST 700 Series HART/DE Option User’s Manual Page 28 Revision 4.0...
  • Page 43: Online Configuration

    HART device with live communication. After making changes to the device you can also save a snapshot of the device data as history to later transfer it to FDM for record and audit purposes. ST 700 Series HART/DE Option User’s Manual Revision 4.0 Page 29...
  • Page 44: Offline Configuration

    The device detection and loading process automatically gets started. Depending upon the Device Detection and DD Selection settings you may have chosen, you may be prompted for certain inputs as described in the Settings section. ST 700 Series HART/DE Option User’s Manual Page 30 Revision 4.0...
  • Page 45: Overview Of Device Homepage

    It is advised that you use Device Status under Functions tab to further investigate the details. Indicates that the device has lost communication with MC Toolkit ST 700 Series HART/DE Option User’s Manual Revision 4.0 Page 31...
  • Page 46: Tabs On The Device Homepage

    FDC across all devices. For the sake of explanations, the right side options under this tab will be referred to as “Entry points” throughout the rest of the document. ST 700 Series HART/DE Option User’s Manual Page 32 Revision 4.0...
  • Page 47 Currently the only option it provides is called as Save History. Using this option you can save the snapshot of the device variables. This snapshot is saved in a format which can be later imported as a history record in FDM. ST 700 Series HART/DE Option User’s Manual Revision 4.0 Page 33...
  • Page 48: Using Fdc For Various Device Operations

    However it must be noted that this does not prohibit you from performing other device operations as explained above.  Online Device Entry Point: When you tap on to open the Online tab, the device configuration screen appears as shown below. ST 700 Series HART/DE Option User’s Manual Page 34 Revision 4.0...
  • Page 49: Device Configuration And Parameter Descriptions

    Online/Overall Status Displays a pictorial representation of the current device status Online/Honeywell Photograph of an ST 700 Pressure Transmitter along with the official “Honeywell” logo Logo Online/PV Meter Displays a gauge meter representation of the current value of the Primary Variable (pressure input)
  • Page 50 Diagram representing typical connections for power Setup/Basic Setup/ and communications for the ST 700 Pressure System Connections Transmitter Online/Device Parts assembly diagram of an ST 700 Pressure Setup/Basic Setup/ Transmitter ST 700 Assembly Online/Device Photograph of an ST 700 Pressure Transmitter along Honeywell Logo with the official “Honeywell”...
  • Page 51 MB Type  AP: Absolute Pressure  GP: Gauge Pressure Displays the Meter Body ID number of the ST 700 MB ID Pressure Transmitter Enter tag identification up to eight alphanumeric characters. Enter a long tag name up to 32 alphanumeric Long Tag characters.
  • Page 52 AUTO / SUB or the transmitter is power cycled. For more information, refer to the Experion Knowledge Builder Displays the HART unique long address of the ST 700 Device ID Pressure Transmitter Displays the final assembly number of the ST 700...
  • Page 53 ON position or the firmware write protect has been enabled. Displays a graphic representation of all PV ranges PV Levels and limits for the ST 700 Pressure Transmitter The following calibration methods are available:  Apply Values: Performs a Set LRV and/or Set URV to configure the LRV/URV to applied inputs.
  • Page 54 Displays all possible Extended Device Status faults and Ext dev status indicates OFF for inactive faults or ON for active faults. Displays an advanced diagnostic detailed breakdown of Additional Status all Critical and Non-Critical faults ST 700 Series HART/DE Option User’s Manual Page 40 Revision 4.0...
  • Page 55 When Tamper Mode is configured. During the configuration, if the Tamper Mode is Enabled and the other Tamper parameters are configured, then that is also considered as a Tamper Attempt. ST 700 Series HART/DE Option User’s Manual Revision 4.0 Page 41...
  • Page 56 Master Reset of the device. If Yes is selected to unlock the device, the lock state will be cleared. ST 700 Series HART/DE Option User’s Manual Page 42 Revision 4.0...
  • Page 57 Square Root (output scaled as square root conversion per configured range - for flow measurements)  PV % range: Displays the current value of AO (analog output) in % ST 700 Series HART/DE Option User’s Manual Revision 4.0 Page 43...
  • Page 58  Poll Address: Click HART short address 0 to 63.  Num req preams: Displays the number of required request preambles for the ST 700 HART communications  PV AO: Displays the current value of AO (analog output) in milliamps ...
  • Page 59: Table 13 - Tamper Reporting Logic Implementation With Write Protect

    Table 13 – Tamper Reporting Logic Implementation with Write Protect Write Protect Write Protect Tamper Tamper Alerted Configuration Jumper Status Software Status Reporting Status Posted? Change Allowed? Jumper Moved Jumper Moved ST 700 Series HART/DE Option User’s Manual Revision 4.0 Page 45...
  • Page 60: Procedure To Enter The Transmitter Tag

    Shortcuts > Device Setup > Basic Setup > Device Information > Tag. 2. Click Edit. The Tag screen will be displayed. 3. Key in the tag name (for example: ST 700) which can be a maximum of eight characters. 4. Click OK. The Send to Device screen will be displayed.
  • Page 61: Setting Pv Urv, And Lrv Range Values

    6.2.12 Setting PV URV, and LRV Range Values ST 700 Transmitters are calibrated at the factory with ranges using inH O at 39.2 F (4 For a reverse range, enter the upper range value as the LRV and the lower range value as the URV.
  • Page 62: Setting Range Values For Applied Pressure

    To save device history: On the Device homepage, tap Tools. Click Save History and tap Select The Save History page appears. ST 700 Series HART/DE Option User’s Manual Page 48 Revision 4.0...
  • Page 63: Exporting Device History Records To Fdm

    The history snapshot saved in FDC can be imported into FDM for record and audit purposes. This is enabled by the standard Import/Export wizard in FDM. This way FDM allows synchronizing the device configuration data through the MC Toolkit handheld. ST 700 Series HART/DE Option User’s Manual Revision 4.0 Page 49...
  • Page 64: Exporting Device History Records To Documint

    You can create two views per device type with maximum of 10 variables selected for each custom view. To create/modify the custom views: ST 700 Series HART/DE Option User’s Manual Page 50 Revision 4.0...
  • Page 65 Edit the parameters that are Read / Write and click Send. For more details on any of the FDC features, refer the MC Tookit User Manual, Document # 34-ST- 25-20 (MCT202) or #34-ST-25-50 (MCT404). ST 700 Series HART/DE Option User’s Manual Revision 4.0 Page 51...
  • Page 66: Offline Configuration

    Note: In case if the offline configuration template is already imported, an overwrite message appears. Tap OK to return to the Offline Configurations page. The device details appear on the bottom of the page. ST 700 Series HART/DE Option User’s Manual Page 52 Revision 4.0...
  • Page 67 Tap OK to return to the offline wizard. Tap Next. The Offline – Review and Send page appears with the list of selected variables. ST 700 Series HART/DE Option User’s Manual Revision 4.0 Page 53...
  • Page 68 Note: If the variables are downloaded successfully, status appears as SUCCESS in green color; and if failed, status appears as FAILED in red color. Tap Finish to return to FDC Homepage. ST 700 Series HART/DE Option User’s Manual Page 54 Revision 4.0...
  • Page 69: De Calibration For St 700 Standard Transmitter

    7.2 Calibration Recommendations If the Transmitter is digitally integrated with a Honeywell Total Plant Solution (TPS) system, you can initiate range calibration and associated reset functions through displays at the Universal Station, Global User Station (GUS), and Allen-Bradley Programmable Logic Controllers (PLCs). However, a range calibration using the MC Toolkit with the Transmitter removed from service is recommended.
  • Page 70: Figure 10 - Analog Output Calibration Test Setup

    5. Click the desired constant-level Output: 0 %, 100 %, or Other (any of 0 % - 100 %). 6. Click the Set button. You will be prompted to confirm that you want to put the Transmitter in output mode. ST 700 Series HART/DE Option User’s Manual Page 56 Revision 4.0...
  • Page 71: Calibrating Range Using The Mc Toolkit

    The procedure needs a precision pressure source with an accuracy of 0.04% or better to do a range calibration. Factory calibration of the ST 700 Pressure Transmitter is accomplished with inches-of- water ranges referenced to a temperature of 39.2°F (4°C).
  • Page 72: Input Calibration Procedures Description

    Transmitter and the MC Toolkit. However, the Transmitter must be level, because the meter body contains fluids that can affect zero sensing. For leveling proceures. Refer to the ST 700 SmartLine Transmitter User’s Manual, Document # 34-ST-25-44, Mounting Transmitters with Small Absolutge or Differential Pressure Spans for information on Transmitter leveling.
  • Page 73: Input Calibration Procedure

    4. Click the Back button to go to the DE MAIN MENU; then click the Calibration button. The CALIBRATION box will be displayed. 5. Click the Back button to go to the DE MAIN MENU; then click the Calibration button. The CALIBRATION box will be displayed. ST 700 Series HART/DE Option User’s Manual Revision 4.0 Page 59...
  • Page 74 9. Wait for the message Sensor input has stabilized, then click OK. 10. When the zero correction is complete, the message Sensor zero succeeded! is displayed; click the OK button. ST 700 Series HART/DE Option User’s Manual Page 60 Revision 4.0...
  • Page 75 5. Observe the input pressure at the applied value; when it is stable, click the OK button. 6. When the Transmitter has completed the LRV correction, this message appears: 7. Click OK to acknowledge. ST 700 Series HART/DE Option User’s Manual Revision 4.0 Page 61...
  • Page 76 2. Adjust the PV input pressure to the exact value of the URV entered in the DE CONFIGURE display. 3. Click the OK button. 4. When the transmitter has completed the URV correction, the following message appears: 5. Click OK to acknowledge. ST 700 Series HART/DE Option User’s Manual Page 62 Revision 4.0...
  • Page 77: De Output Calibration

    Variable (PV) input range such that 4 mA corresponds to the LRV of 0% and 20mA corresponds to the URV of 100%. Figure shows the PV scale and representative process system connections. Figure 13 – DE Analog Mode Scaling and Test Connections ST 700 Series HART/DE Option User’s Manual Revision 4.0 Page 63...
  • Page 78 Use the Increment or Decrement button, as necessary to adjust the output current to 20mA. When the current reaches the 20mA level, click Clear Output; the button will change to half-intensity. ST 700 Series HART/DE Option User’s Manual Page 64 Revision 4.0...
  • Page 79: Manually Setting The Process Variable Range

    1. Establish the test connections shown below. Then start the MC Toolkit application to display the DE MAIN MENU. Figure 14 – Setup to Manually Set the PV LRV and URV ST 700 Series HART/DE Option User’s Manual Revision 4.0 Page 65...
  • Page 80 (0 %) level, and then click Set LRV. b. If the displayed value is satisfactory, click Yes to copy the Input Value to the LRV in the Transmitter. If not, click NO and repeat this step. ST 700 Series HART/DE Option User’s Manual Page 66 Revision 4.0...
  • Page 81 Open the DE CONFIGURE display, and observe that the settings are established in Steps 4 and 5. b. This concludes the procedure to manually set the operating range. ST 700 Series HART/DE Option User’s Manual Revision 4.0 Page 67...
  • Page 82: Procedure To Reset Calibration

    (characterization) values. It is intended for use only when excessive corrections render the transmitter inaccurate. It is highly recommended that input calibration procedure be performed after calibration reset. ST 700 Series HART/DE Option User’s Manual Page 68 Revision 4.0...
  • Page 83: Hart Calibration For St 700 Standard Transmitter

    8 HART Calibration for ST 700 Standard Transmitter 8.1 About This Section This section provides information about calibrating an ST 700 Standard Transmitter’s analog output and measurement range. It also covers the procedure to reset calibration to the default values as a quick alternative to measurement range calibration.
  • Page 84: Analog Output Signal Calibration

    Return to the Enter Meter Value prompt until the field device output equals the reference meter. d. Click Yes and press Enter. 8. The prompt notifies you that the field device will be returned to its original output ST 700 Series HART/DE Option User’s Manual Page 70 Revision 4.0...
  • Page 85: Calibrating Range

    IMPORTANT! You must have a precision pressure source with an accuracy of 0.02% or better to do a range calibration. Note that the factory calibrates ST 700 Standard SmartLine Pressure Transmitters using inches of water pressure reference to a temperature of 39.2 8.3.1 Correcting the Lower Range Value (LRV)
  • Page 86: Resetting Calibration

    14. When prompted, return the loop to automatic control, and click Enter. 8.3.3 Resetting Calibration ST 700 Standard SmartLine HART Pressure Transmitter can erase incorrect calibration data by resetting the device back to final factory calibration, which is performed per the ordered range.
  • Page 87: Table 14 - Calibration Records

    Last Corrects Rec Date and Time of last Reset corrects done displayed in mm/dd/yyyy format Prev Corrects Rec2 Date and Time of current Reset corrects done displayed in mm/dd/yyyy format ST 700 Series HART/DE Option User’s Manual Revision 4.0 Page 73...
  • Page 88 This page has been intentionally left blank. ST 700 Series HART/DE Option User’s Manual Page 74 Revision 4.0...
  • Page 89: Hart Advanced Diagnostics For St 700 Standard Transmitter

    9 HART Advanced Diagnostics for ST 700 Standard Transmitter 9.1 About This Section This section provides information about the Advanced Diagnostic features in the ST 700 Standard SmartLine Pressure Transmitter. 9.2 Advanced Diagnostics Table 15 – Viewing Advanced Diagnostics What you want to view What to do ...
  • Page 90: Pv Tracking Diagnostics

    PV passed above “PV Upper Last PV Up Stress Limit” (in days, hours and minutes). Set-up None: initialized to zero prior to leaving the factory. Backup once each 8 hour period ST 700 Series HART/DE Option User’s Manual Page 76 Revision 4.0...
  • Page 91: Table 17 - Minimum Pv Tracking

    Last PV Down value of “PV Lower Stress Limit” (in days, hours and minutes). None: initialized to zero prior to Set-up leaving the factory. Backup once each 8 hour period ST 700 Series HART/DE Option User’s Manual Revision 4.0 Page 77...
  • Page 92: Sv Tracking

    Meterbody Temperature has passed Last SV below the value of “SV Lower Stress Limit” (in Down days, hours, and minutes). Set-up None. Backup once each 8 hour period ST 700 Series HART/DE Option User’s Manual Page 78 Revision 4.0...
  • Page 93: Tv Tracking Diagnostics

    Accumulation of minutes that device’s Time Above Parameter Description Upper Stress Electronics Temperature has been above the value of “ET Upper Stress Limit”. Limit Set-up None. Backup once each 8 hour period ST 700 Series HART/DE Option User’s Manual Revision 4.0 Page 79...
  • Page 94: Table 22 - Minimum Et Diagnostics

    Electronics Temperature has Last ET Down passed below the value of “ET Lower Stress Limit” (in days, hours, and minutes). Set-up None. Backup once each 8 hour period ST 700 Series HART/DE Option User’s Manual Page 80 Revision 4.0...
  • Page 95: Stress Life

    Time Since Last Event to be reset to zero. Within a short period of time Min Op Voltage Voltage will assume operating voltage value. Parameters Set-up User actuates as required. ST 700 Series HART/DE Option User’s Manual Revision 4.0 Page 81...
  • Page 96: Avdd Tracking Diagnostics

    Sensor CPU time Sensor CPU Temperature has passed below the value of “Min Temp. Down Sensor CPU Temp” (in days, hours and minutes). Set-up None. Update every 8 hours. ST 700 Series HART/DE Option User’s Manual Page 82 Revision 4.0...
  • Page 97: Power Up Diagnostics

    Only one power failure in each 8 hour period is counted. Time since Method Description Displays time since last power-up in last power fail minutes. Set-up None. Update every 8 hours. ST 700 Series HART/DE Option User’s Manual Revision 4.0 Page 83...
  • Page 98 This page intentionally left blank. ST 700 Series HART/DE Option User’s Manual Page 84 Revision 4.0...
  • Page 99: Troubleshooting And Maintenance For St 700 Standard Transmitter

    Low Supply Voltage No DAC Calibration Tamper Alarm Meter Body Unreliable Comm Loop Current Noise AO Out of Range URV Set Err. Span Config Button LRV Set Err. Zero Config Button ST 700 Series HART/DE Option User’s Manual Revision 4.0 Page 85...
  • Page 100: Hart Diagnostic Details

    Under-current or Over-current Status  Packet Error, SPI Fault or Control Word Write Fault Resolution: Verify the environment temperature is within spec. Reset the device. If problem persists, replace the Electronics Module. ST 700 Series HART/DE Option User’s Manual Page 86 Revision 4.0...
  • Page 101 Body from temperature source. Meter Body Excess Possible Causes: Correct ZERO or SPAN correction factor is outside acceptable limits. INPUT may have been incorrect during calibration or transmitter was ST 700 Series HART/DE Option User’s Manual Revision 4.0 Page 87...
  • Page 102 Mode is enabled, or Tamper Alarm alone is enabled, and outside attempts to change device configuration exceeded the set Tamper limit Resolution: Identify source of tampering. If configuration changes are required, contact a qualified ST 700 Series HART/DE Option User’s Manual Page 88 Revision 4.0...
  • Page 103 Verify the inputs are valid for the intended operation. LRV Set Err. Zero Config Possible causes: Button SET LRV operation using external Zero button was rejected. Resolution: Verify the inputs are valid for the intended operation. ST 700 Series HART/DE Option User’s Manual Revision 4.0 Page 89...
  • Page 104: De Diagnostic Messages

    Reset the device. If the problem persists, replace the Meter Body. Meter body failure Possible causes:  Meter body failure  Sensor communication timeout  Sensor firmware flow failure ST 700 Series HART/DE Option User’s Manual Page 90 Revision 4.0...
  • Page 105 Replace Meter Body and recalibrate if needed. Current Fixed Possible causes: Output current is fixed and not varying with applied input. Output Mode is active. Resolution: Exit Output mode if active. ST 700 Series HART/DE Option User’s Manual Revision 4.0 Page 91...
  • Page 106 Meter Body temperature is too high. Accuracy and life span may decrease if it remains high. Resolution: Verify the environment temperature is within specification. Take steps to insulate Meter Body from temperature source. ST 700 Series HART/DE Option User’s Manual Page 92 Revision 4.0...
  • Page 107: Using Dtms

    7. Right-click HART DTM, click Connect. 8. Right-click HART Comm DTM and click Add device. 9. Add the Device DTM from for your device from the list (for example: ST 700 DevRev 1). 10. Right-click Device DTM, and click Connect.
  • Page 108: St 700 Online Parameterization

    11.5 ST 700 Online Parameterization On selecting Parameter/Online Parameterization, the DTM homepage is displayed: ST 700 Series HART/DE Option User’s Manual Page 94 Revision 4.0...
  • Page 109: Device Health

    Basic Setup:  Provides Device Setup information (Tag, Device Type, MB Type etc.) Calibration:  Provides access to all the Calibration functions Refer to Table 12 for more details ST 700 Series HART/DE Option User’s Manual Revision 4.0 Page 95...
  • Page 110: Basic Setup Page

    Refer to Table 12 for more details 11.6.3 Device Information Allows access to both read-only parameters and read/write parameters. Provides access to Message, Clear Message and Maint Mode. ST 700 Series HART/DE Option User’s Manual Page 96 Revision 4.0...
  • Page 111: Model Number

    Refer to Table 12 for more details 11.6.4 Model Number: Shows the Model number. 11.6.5 Device Assembly: Shows the Blow out Image of ST 700 11.6.6 System Setup: Shows the Image how to connect the Transmitter ST 700 Series HART/DE Option User’s Manual Revision 4.0...
  • Page 112: Calibration Page

    The Calibration Page provides access to all of the calibration methods and records. 11.7.1 Calibration Methods Apply Values Enter Values D/A Trim Zero Trim URV Correct LRV Correct Reset Corrects Refer to Table 12 for more details ST 700 Series HART/DE Option User’s Manual Page 98 Revision 4.0...
  • Page 113: Calibration Records

    Refer to the Calibration Records in for more details Reset Corrects Records  Prev Corrects Resets  Last Corrects Resets  Curr Corrects Resets Refer to the Calibration Records in for more details ST 700 Series HART/DE Option User’s Manual Revision 4.0 Page 99...
  • Page 114: Process Variables

    11.8 Process Variables All the Process Variables are graphically represented in this screen. Click Trend Charts to see the Trending Charts ST 700 Series HART/DE Option User’s Manual Page 100 Revision 4.0...
  • Page 115: Trend Charts

    11.9 Trend Charts ST 700 Series HART/DE Option User’s Manual Revision 4.0 Page 101...
  • Page 116: Device Status

    Shows Critical and Non-Critical status and context-sensitive help when gliding the mouse over an individual status. Refer to section 10 Troubleshooting and Maintenance for additional details on individual status details ST 700 Series HART/DE Option User’s Manual Page 102 Revision 4.0...
  • Page 117: Critical And Non-Critical Help Display

    Shows Help on Critical, Non-Critical when you click Help – Critical Diag or Help –Non- Critical Diag buttons. The extended status can be seen by clicking the Additional Status button. ST 700 Series HART/DE Option User’s Manual Revision 4.0 Page 103...
  • Page 118: Diagnostics

    Sensor CPU Temp. Tracking  Power Up Diagnostics Access the relevant tab to read the Diagnostic parameters or run the Diagnostics Methods Refer to the ”HART Advanced Diagnostics” section for more details. ST 700 Series HART/DE Option User’s Manual Page 104 Revision 4.0...
  • Page 119: Services

    11.13 Services This allows the configuration of Tamper Alarm and Write Protect mode. Refer to the Device Configuration and Parameter Descriptions section for more details. ST 700 Series HART/DE Option User’s Manual Revision 4.0 Page 105...
  • Page 120: Detailed Setup

    Shows Sensor Limits, Output Condition, Signal Condition and Burnout level selections. Refer to the Device Configuration and Parameter Descriptions section for more details. Section 5 for DE configuration and section 6 for HART configuration. ST 700 Series HART/DE Option User’s Manual Page 106 Revision 4.0...
  • Page 121: Meterbody Selection

    11.19 Common setup: This lists the Common setup for all the screens Refer to the ST 700 SmartLine Pressure Transmitter User’s Manual, Documents # 34-ST- 25-44, Basic Display Menu sections” for more details. ST 700 Series HART/DE Option User’s Manual Revision 4.0...
  • Page 122: Review

    Summary screen showing all the parameters. Refer to the Device Configuration and Parameter Descriptions section for more details. Section 5 for DE configuration and section 6 for HART configuration. ST 700 Series HART/DE Option User’s Manual Page 108 Revision 4.0...
  • Page 123: St 700 Offline Parameterization

    11.21 ST 700 Offline Parameterization Click Parameter/ Parameterization, to open the Offline parameter configuration page. Click Device / Load to Device to download the Offline Configuration to the connected device. ST 700 Series HART/DE Option User’s Manual Revision 4.0 Page 109...
  • Page 124: Hart Dd Binary File Format Compatibility Matrix For St 700 Standard Transmitter

    12 . HART DD binary file format compatibility matrix for ST 700 Standard Transmitter "Host - ST 700 - HART DD binary file format" compatibility matrix Host DD file format to be used Experion R410 Experion R400 to R300 Experion below R300 FDM R430 FDM R410 –...
  • Page 125: Introduction For St 700 Basic Transmitter

    This section is an introduction to the physical and functional characteristics Honeywell’s family of the ST 700 Basic SmartLine Pressure Transmitters. If you are not sure which type of ST 700 you have, Standard or Basic, please refer to Section Error! eference source not found.
  • Page 126: Figure 15 - St 700 Basic Major Assemblies

    The Meter Body provides connection to a process system. Several physical interface configurations are available, as determined by the mounting and mechanical connections. Refer to the ST 700 SmartLine User’s Manual, Document# 34-ST-25-44 for installation and wiring details. Figure 15 – ST 700 Basic Major Assemblies Figure 16 - Electronics Housing Components ST 700 Series HART/DE Option User’s Manual...
  • Page 127: Functional Characteristics

    Transmitter. In addition, a Honeywell Multi-Communication (MC) Toolkit (not supplied with the Transmitter) can facilitate setup and adjustment procedures. Certain adjustments can be made through an Experion Station if the Transmitter is digitally integrated with Honeywell’s Experion. An optional external 2-button assembly is also available for configuring / adjusting the Transmitter.
  • Page 128: Safety Certification Information

    Experion Station if the Transmitter is digitally integrated with a Honeywell Experion system. ST 700 HART models can be configured using Honeywell tools such as Experion in conjunction with FDM, using DTMs running in FDM or Pactware, or Emerson 375 or 475.
  • Page 129: Local Display Options

    13.5 Local Display Options The ST 700 Basic SmartLine Pressure Transmitter offers a standard display, see Table 32 Table 32 – Available Display Characteristics  Has a limited character display  rotation in 90 Increments  2 lines, 6 characters Standard Display ...
  • Page 130: Communication Modes For St 700 Basic Transmitter

    Point-to-Point Mode: Where one Transmitter is connected via a two-conductor, 4-20mA current loop to one receiver.  Multi-Drop Mode: Where several Transmitters are connected through a two-conductor network to a multiplexed receiver device. ST 700 Series HART/DE Option User’s Manual Page 116 Revision 4.0...
  • Page 131 In multi-drop mode, up to 16 transmitters in HART 5 (addresses 0-15) and up to 64 transmitters in HART6/7 (addresses 0-63) can exist on the two-conductor network. Refer to the Transmitter user’s manual for wiring diagram of mulidrop mode, #34-ST-25-44. ST 700 Series HART/DE Option User’s Manual Revision 4.0 Page 117...
  • Page 132: Configuration Tools And Interfaces For St 700 Basic Transmitter

    ST 700 Basic Transmitter 15.1 Overview This section describes the tools and interfaces involved in configuring a new ST 700 Basic SmartLine Pressure Transmitter for HART operation. The information in this section also applies to adjusting the configuration of a Transmitter that has been in operation and updating one that is currently in operation.
  • Page 133: Mc Toolkit Participation

    (i.e., trips) need to be disabled, as appropriate, before starting a procedure. 15.4.1 MC Toolkit Software Applications The MC Toolkit has a software applications to work with ST 700 Basic SmartLine Pressure Transmitters:  Field Device Configurator (FDC): This application is used for configuring, calibrating, monitoring, and diagnosing HART devices.
  • Page 134: Mc Toolkit-Transmitter Electrical/Signal Connections

    15.4.4 MC Toolkit–Transmitter Electrical/Signal Connections Figure 19 displays how to connect the MC Toolkit directly to the terminals of a HART Transmitter. Figure 19 – MC Toolkit-Transmitter Electrical/Signal Connections ST 700 Series HART/DE Option User’s Manual Page 120 Revision 4.0...
  • Page 135: Hart Transmitter Configuration For St 700 Basic Transmitter

    ST 700 Basic Transmitter 16.1 Overview Each new ST 700 Basic SmartLine Pressure Transmitter configured for HART protocol is shipped from the factory with a basic configuration database installed. This basic configuration database must be edited or revised to meet the requirements of your process system. The process in this section assumes that you will use the Field Device Communicator (FDC) application for HART configuration tasks.
  • Page 136: Overview Of Fdc Homepage

    Tap to quit FDC. Note: To select a particular option in FDC you can either select the option and then tap Select or you can directly double-tap the option. ST 700 Series HART/DE Option User’s Manual Page 122 Revision 4.0...
  • Page 137: Settings

    With this option enabled, FDC creates necessary log files for troubleshooting and diagnostics. These files are stored in SD Card\FDC folder. Note: You must not enable this option unless suggested by Honeywell TAC because this may impact the application performance.
  • Page 138: Manage Dds

    If the DD file already exists, then the following message appears. Tap Yes to overwrite the existing DD files. If the DD file is added successfully, a success message appears. ST 700 Series HART/DE Option User’s Manual Page 124 Revision 4.0...
  • Page 139: Online Configuration

    HART device with live communication. After making changes to the device you can also save a snapshot of the device data as history to later transfer it to FDM for record and audit purposes. ST 700 Series HART/DE Option User’s Manual Revision 4.0 Page 125...
  • Page 140: Offline Configuration

    The device detection and loading process automatically gets started. Depending upon the Device Detection and DD Selection settings you may have chosen, you may be prompted for certain inputs as described in the Settings section. ST 700 Series HART/DE Option User’s Manual Page 126 Revision 4.0...
  • Page 141: Overview Of Device Homepage

    It is advised that you use Device Status under Functions tab to further investigate the details. Indicates that the device has lost communication with MC Toolkit ST 700 Series HART/DE Option User’s Manual Revision 4.0 Page 127...
  • Page 142: Tabs On The Device Homepage

    FDC across all devices. For the sake of explanations, the right side options under this tab will be referred to as “Entry points” throughout the rest of the document. ST 700 Series HART/DE Option User’s Manual Page 128 Revision 4.0...
  • Page 143 Currently the only option it provides is called as Save History. Using this option you can save the snapshot of the device variables. This snapshot is saved in a format which can be later imported as a history record in FDM. ST 700 Series HART/DE Option User’s Manual Revision 4.0 Page 129...
  • Page 144: Using Fdc For Various Device Operations

    However it must be noted that this does not prohibit you from performing other device operations as explained above.  Online Device Entry Point: When you tap on to open the Online tab, the device configuration screen appears as shown below. ST 700 Series HART/DE Option User’s Manual Page 130 Revision 4.0...
  • Page 145: Device Configuration And Parameter Descriptions

    Displays a ga value of the S temperature) Online/SV Displays the (meter body t engineering u Online/AO Meter Displays a ga value of the A Online/PV AO Displays the ST 700 Series HART/DE Option User’s Manual Revision 4.0 Page 131...
  • Page 146 Online/Device Parts assembly d Transmitter Setup/Basic Setup/ ST 700 Assembly Photograph of an Online/Device Honeywell Logo with the official “H Setup/Basic Setup/ Device Information Displays Manufac Manufacturer Transmitter: Hon ST 700 Series HART/DE Option User’s Manual Page 132 Revision 4.0...
  • Page 147 Displays all o The following     Range values The following span ranging   Valid configu LTL to UTL. Displays the Model Number Pressure Tra ST 700 Series HART/DE Option User’s Manual Revision 4.0 Page 133...
  • Page 148 Displays the HART unique long address of the ST Device ID 700 Pressure Transmitter Displays the final assembly number of the ST 700 Final Asmbly num Pressure Transmitter Displays the HART Universal Revision of the ST Universal rev 700 Pressure Transmitter...
  • Page 149 Displays a graphic representation of all PV ranges PV Levels and limits for the ST 700 Pressure Transmitter The following calibration methods are available:  Apply Values: Performs a Set LRV and/or Set URV to configure the LRV/URV to applied inputs.
  • Page 150 Displays all possible Extended Device Status faults and Ext dev status indicates OFF for inactive faults or ON for active faults. Displays an advanced diagnostic detailed breakdown of Additional Status all Critical and Non-Critical faults ST 700 Series HART/DE Option User’s Manual Page 136 Revision 4.0...
  • Page 151 Master Reset of the device. If Yes is selected to unlock the device, the lock state will be cleared. ST 700 Series HART/DE Option User’s Manual Revision 4.0 Page 137...
  • Page 152 Square Root (output scaled as square root conversion per configured range - for flow measurements)  PV % range: Displays the current value of AO (analog output) in % ST 700 Series HART/DE Option User’s Manual Page 138 Revision 4.0...
  • Page 153  Poll Address: Click HART short address 0 to 63.  Num req preams: Displays the number of required request preambles for the ST 700 HART communications  PV AO: Displays the current value of AO (analog output) in milliamps ...
  • Page 154: Procedure To Enter The Transmitter Tag

    Shortcuts > Device Setup > Basic Setup > Device Information > Tag. 2. Click Edit. The Tag screen will be displayed. 3. Key in the tag name (for example: ST 700) which can be a maximum of eight characters. 4. Click OK. The Send to Device screen will be displayed.
  • Page 155: Setting Pv Urv, And Lrv Range Values

    16.2.12 Setting PV URV, and LRV Range Values ST 700 Basic Transmitters are calibrated at the factory with ranges using inH O at 39.2 C). For a reverse range, enter the upper range value as the LRV and the lower range value as the URV.
  • Page 156: Setting Range Values For Applied Pressure

    Only one snapshot per device instance is allowed to be saved and you can save the snapshot of a device any number of times overwriting the existing one. To save device history: On the Device homepage, tap Tools. Click Save History and tap Select ST 700 Series HART/DE Option User’s Manual Page 142 Revision 4.0...
  • Page 157 If a history record for this device already exists, the following warning message appears. Tap Yes to overwrite the existing name. A overwrite success message appears. Tap OK to return to Device Homepage. ST 700 Series HART/DE Option User’s Manual Revision 4.0 Page 143...
  • Page 158: Exporting Device History Records To Fdm

    For Importing in DocuMint: Click Procedures > Import or the Import option in the tool bar. Note: For more details on using DocuMint Import feature, refer to section importing from XML File in Document Help. ST 700 Series HART/DE Option User’s Manual Page 144 Revision 4.0...
  • Page 159: Custom Views

    Tap Return to return to My Views page. You would see two options with the names you gave to the newly created views. Note: To view the custom views, tap My View 1 > Select. The My View 1 page appears. ST 700 Series HART/DE Option User’s Manual Revision 4.0 Page 145...
  • Page 160: Offline Configuration

    Currently, FDC does not support creating offline configuration. ST 700 Series HART/DE Option User’s Manual Page 146 Revision 4.0...
  • Page 161: Hart Calibration For St 700 Basic Transmitter

    How to perform a correct reset to return a Transmitter calibration to its default values. 17.1.1 About Calibration The ST 700 Basic SmartLine Pressure Transmitter does not require calibration at periodic intervals to maintain accuracy. If a recalibration is required, we recommend that perform a bench calibration with the Transmitter removed from the process and located in a controlled environment to get the best accuracy.
  • Page 162: Analog Output Signal Calibration

    Return to the Enter Meter Value prompt until the field device output equals the reference meter. h. Click Yes and press Enter. 9. The prompt notifies you that the field device will be returned to its original output ST 700 Series HART/DE Option User’s Manual Page 148 Revision 4.0...
  • Page 163: Calibrating Range

    IMPORTANT! You must have a precision pressure source with an accuracy of 0.02% or better to do a range calibration. Note that the factory calibrates SmartLine Pressure Transmitter ST 700 Basic using inches of water pressure reference to a temperature of 39.2 F (4 17.3.1 Correcting the Lower Range Value (LRV)
  • Page 164: Resetting Calibration

    14. When prompted, return the loop to automatic control, and click Enter. 17.3.3 Resetting Calibration ST 700 Basic SmartLine Pressure Transmitter can erase incorrect calibration data by resetting the device back to final factory calibration, which is performed per the ordered range. The Corrects Reset command returns the zero and span calibration factors to the original precise factory calibration.
  • Page 165: Table 37 - Calibration Records

    Last Corrects Rec Date and Time of last Reset corrects done displayed in mm/dd/yyyy format Prev Corrects Rec2 Date and Time of current Reset corrects done displayed in mm/dd/yyyy format ST 700 Series HART/DE Option User’s Manual Revision 4.0 Page 151...
  • Page 166: Hart Advanced Diagnostics For St 700 Basic Transmitter

    18 HART Advanced Diagnostics for ST 700 Basic Transmitter 18.1 About This Section This section provides information about the Advanced Diagnostic features in the ST 700 Basic SmartLine Pressure Transmitter. 18.2 Advanced Diagnostics Table 38 – Viewing Advanced Diagnostics What you want to view What to do ...
  • Page 167: Pv Tracking Diagnostics

    PV passed above “PV Upper Last PV Up Stress Limit” (in days, hours and minutes). Set-up None: initialized to zero prior to leaving the factory. Backup once each 8 hour period ST 700 Series HART/DE Option User’s Manual Revision 4.0 Page 153...
  • Page 168: Table 40 - Minimum Pv Tracking

    Last PV Down value of “PV Lower Stress Limit” (in days, hours and minutes). None: initialized to zero prior to Set-up leaving the factory. Backup once each 8 hour period ST 700 Series HART/DE Option User’s Manual Page 154 Revision 4.0...
  • Page 169: Sv Tracking

    Meterbody Temperature has Last SV passed below the value of “SV Lower Down Stress Limit” (in days, hours, and minutes). Set-up None. Backup once each 8 hour period ST 700 Series HART/DE Option User’s Manual Revision 4.0 Page 155...
  • Page 170: Tv Tracking Diagnostics

    Accumulation of minutes that device’s Time Above Parameter Description Upper Stress Electronics Temperature has been above the value of “ET Upper Stress Limit”. Limit Set-up None. Backup once each 8 hour period ST 700 Series HART/DE Option User’s Manual Page 156 Revision 4.0...
  • Page 171: Table 45 - Minimum Et Diagnostics

    Electronics Temperature has Last ET Down passed below the value of “ET Lower Stress Limit” (in days, hours, and minutes). Set-up None. Backup once each 8 hour period ST 700 Series HART/DE Option User’s Manual Revision 4.0 Page 157...
  • Page 172: Stress Life

    Time Since Last Event to be Parameters reset to zero. Within a short period of time Min Op Voltage will assume operating voltage value. Set-up User actuates as required. ST 700 Series HART/DE Option User’s Manual Page 158 Revision 4.0...
  • Page 173: Avdd Tracking Diagnostics

    Sensor CPU time Sensor CPU Temperature has passed below the value of “Min Temp. Down Sensor CPU Temp” (in days, hours and minutes). Set-up None. Update every 8 hours. ST 700 Series HART/DE Option User’s Manual Revision 4.0 Page 159...
  • Page 174: Power Up Diagnostics

    Only one power failure in each 8 hour period is counted. Time since Method Description Displays time since last power-up in last power fail minutes. Set-up None. Update every 8 hours. ST 700 Series HART/DE Option User’s Manual Page 160 Revision 4.0...
  • Page 175 This page intentionally left blank. ST 700 Series HART/DE Option User’s Manual Revision 4.0 Page 161...
  • Page 176: Troubleshooting And Maintenance For St 700 Basic Transmitter

    Low Supply Voltage No DAC Calibration Meter Body Unreliable Comm Loop Current Noise AO Out of Range URV Set Err. Span Config Button LRV Set Err. Zero Config Button ST 700 Series HART/DE Option User’s Manual Page 162 Revision 4.0...
  • Page 177: Hart Diagnostic Details

    Under-current or Over-current Status  Packet Error, SPI Fault or Control Word Write Fault Resolution: Verify the environment temperature is within spec. Reset the device. If problem persists, replace the Electronics Module. ST 700 Series HART/DE Option User’s Manual Revision 4.0 Page 163...
  • Page 178 Body from temperature source. Meter Body Excess Possible Causes: Correct ZERO or SPAN correction factor is outside acceptable limits. INPUT may have been incorrect during calibration or transmitter was ST 700 Series HART/DE Option User’s Manual Page 164 Revision 4.0...
  • Page 179 No DAC calibration has been performed on the device. Resolution: Perform DAC calibration for precise analog output measurement. Tamper Alarm This feature is not applibacle for ST 700 Basic Model. ST 700 Series HART/DE Option User’s Manual Revision 4.0 Page 165...
  • Page 180 Verify the inputs are valid for the intended operation. LRV Set Err. Zero Config Possible causes: Button SET LRV operation using external Zero button was rejected. Resolution: Verify the inputs are valid for the intended operation. ST 700 Series HART/DE Option User’s Manual Page 166 Revision 4.0...
  • Page 181: Using Dtms For St 700 Basic Transmitter

    19. Right-click HART DTM, click Connect. 20. Right-click HART Comm DTM and click Add device. 21. Add the Device DTM from for your device from the list (for example: ST 700 DevRev 1). 22. Right-click Device DTM, and click Connect.
  • Page 182: St 700 Online Parameterization

    20.5 ST 700 Online Parameterization On selecting Parameter/Online Parameterization, the DTM homepage is displayed: ST 700 Series HART/DE Option User’s Manual Page 168 Revision 4.0...
  • Page 183: Device Health

    Basic Setup:  Provides Device Setup information (Tag, Device Type, MB Type etc.) Calibration:  Provides access to all the Calibration functions Refer to Table 36 for more details ST 700 Series HART/DE Option User’s Manual Revision 4.0 Page 169...
  • Page 184: Basic Setup Page

    20.6.4 Model Number: Shows the Model number. 20.6.5 Device Assembly: Shows the Blow out Image of ST 700 20.6.6 System Setup: Shows the Image how to connect the Transmitter ST 700 Series HART/DE Option User’s Manual Page 170...
  • Page 185: Calibration Page

    The Calibration Page provides access to all of the calibration methods and records. 20.7.1 Calibration Methods Apply Values Enter Values D/A Trim Zero Trim URV Correct LRV Correct Reset Corrects Refer to for more details Table 36 ST 700 Series HART/DE Option User’s Manual Revision 4.0 Page 171...
  • Page 186: Calibration Records

    Refer to the Calibration Records for more details Reset Corrects Records  Prev Corrects Resets  Last Corrects Resets  Curr Corrects Resets Refer to the Calibration Records for more details ST 700 Series HART/DE Option User’s Manual Page 172 Revision 4.0...
  • Page 187: Process Variables

    20.8 Process Variables All the Process Variables are graphically represented in this screen. Click Trend Charts to see the Trending Charts ST 700 Series HART/DE Option User’s Manual Revision 4.0 Page 173...
  • Page 188: Trend Charts

    20.9 Trend Charts ST 700 Series HART/DE Option User’s Manual Page 174 Revision 4.0...
  • Page 189: Device Status

    Shows Critical and Non-Critical status and context-sensitive help when gliding the mouse over an individual status. Refer to section 19 Troubleshooting and Maintenance for additional details on individual status details ST 700 Series HART/DE Option User’s Manual Revision 4.0 Page 175...
  • Page 190: Critical And Non-Critical Help Display

    Shows Help on Critical, Non-Critical when you click Help – Critical Diag or Help –Non- Critical Diag buttons. The extended status can be seen by clicking the Additional Status button. ST 700 Series HART/DE Option User’s Manual Page 176 Revision 4.0...
  • Page 191: Diagnostics

    Sensor CPU Temp. Tracking  Power Up Diagnostics Access the relevant tab to read the Diagnostic parameters or run the Diagnostics Methods Refer to the ”HART Advanced Diagnostics” section for more details. ST 700 Series HART/DE Option User’s Manual Revision 4.0 Page 177...
  • Page 192: Services

    20.13 Services This allows the configuration of Tamper Alarm and Write Protect mode. Refer to the Device Configuration and Parameter Descriptions section for more details. ST 700 Series HART/DE Option User’s Manual Page 178 Revision 4.0...
  • Page 193: Detailed Setup

    20.14 Detailed Setup Shows Sensor Limits, Output Condition, Signal Condition and Burnout level selections. Refer to the Device Configuration and Parameter Descriptions section for more details. Section 16 for HART configuration. ST 700 Series HART/DE Option User’s Manual Revision 4.0 Page 179...
  • Page 194: Meterbody Selection

    20.19 Common setup: This lists the Common setup for all the screens Refer to the ST 700 SmartLine Pressure Transmitter User’s Manual, Documents # 34-ST- 25-44, Basic Display Menu sections” for more details. ST 700 Series HART/DE Option User’s Manual Page 180 Revision 4.0...
  • Page 195: Review

    Summary screen showing all the parameters. Refer to the Device Configuration and Parameter Descriptions section for more details. Section 5 for DE configuration and section 6 for HART configuration. ST 700 Series HART/DE Option User’s Manual Revision 4.0 Page 181...
  • Page 196: St 700 Offline Parameterization

    20.21 ST 700 Offline Parameterization Click Parameter/ Parameterization, to open the Offline parameter configuration page. Click Device / Load to Device to download the Offline Configuration to the connected device. ST 700 Series HART/DE Option User’s Manual Page 182 Revision 4.0...
  • Page 197: Hart Dd Binary File Format Compatibility Matrix For St 700 Standard Transmitter

    21 . HART DD binary file format compatibility matrix for ST 700 Standard Transmitter "Host - ST 700 - HART DD binary file format" compatibility matrix Host DD file format to be used Experion R410 Experion R400 to R300 Experion below R300 FDM R430 FDM R410 –...
  • Page 198: Glossary

    Absolute critical pressure of the gas Static pressure at downstream point Measured differential pressure in Pascals in PV4 algorithm Absolute pressure of flowing gas Reduced pressure Static pressure at upstream point Process Manger ST 700 Series HART/DE Option User’s Manual Page 184 Revision 4.0...
  • Page 199 Smart Field Communicator STIM Pressure Transmitter Interface Module STIMV IOP Pressure Transmitter Interface Multivariable Input/Output Processor Upper Range Limit Upper Range Value Universal Station Volts Alternating Current Volts Direct Current ST 700 Series HART/DE Option User’s Manual Revision 4.0 Page 185...
  • Page 200: Index

    DTMs Display Setup Introduction ST 700 Basic Transmitter ........181 ST 700 Standard Transmitter ........1 DTMs Review ST 700 Basic Transmitter ........182 ST 700 Standard Transmitter ......... 108 ST 700 Series HART/DE Option User’s Manual Page 186 Revision 4.0...
  • Page 201 ST 700 Standard Transmitter ........10 ST 700 Basic Transmitter ........177 MC Toolkit Software ST 700 Standard Transmitter ......103 ST 700 Standard Transmitter ......12, 25 Detailed Setup ST 700 Basic Transmitter ........180 ST 700 Standard Transmitter ......106...
  • Page 202: Sales And Service

    Phone: +(822) 799 6114 Fax: +(822) 792 9015 For more information To learn more about SmartLine Transmitters, visit www.honeywellprocess.com Or contact your Honeywell Account Manager Process Solutions Honeywell 1250 W Sam Houston Pkwy S Houston, TX 77042 Honeywell Control Systems Ltd...

Table of Contents