hit counter script
ABB COM600 Product Manual
ABB COM600 Product Manual

ABB COM600 Product Manual

Grid automation controller
Hide thumbs Also See for COM600:

Advertisement

Power Products
Grid Automation Controller COM600
Product Guide

Advertisement

Table of Contents
loading

Summary of Contents for ABB COM600

  • Page 1 Power Products Grid Automation Controller COM600 Product Guide...
  • Page 2: Table Of Contents

    © Copyright 2012 ABB All rights reserved. Trademarks ABB is a registered trademark of the ABB Group. All other brand or product names mentioned in this document may be trademarks or registered trademarks of their respective holders.
  • Page 3: Description

    COM600 a flexible implementation fault isolation and network restoration. platform for substation-level automation tasks. As a user interface solution COM600 The COM600 hardware platform is based on accommodates web technology based ruggedized mechanics with no moving parts functionalities providing access to substation subject to wear and tear.
  • Page 4: Application

    LAN 1 TCP/IP protocols (DNP3 or IEC 60870-5-104) Ethernet switch TCP/IP protocols (IEC 61850) Gateway RER601 RER601 TCP/IP protocols (DNP3 or IEC 60870-5-104) REF611 REF615 REF615 RIO600 RER620 RER620 Fig. 2 Overview of a utility substation using Grid Automation Controller COM600...
  • Page 5: Parameter Setting

    Ethernet switch REF615 REF615 REF615 Fig. 3 Overview of an industrial system using Grid Automation Controller COM600 The single line diagram can be configured COM600 can be equipped with an optional to include an indication for the local/remote Ethernet interface. The number of Ethernet selection switch.
  • Page 6: Event And Alarm Lists

    The user can export an event list to a .csv file for further analysis. COM600 supports printing of events to an Event Printer for long time archiving. 6. Data historian The COM600 data historian is a real-time 5.
  • Page 7 Grid Automation Controller 1MRS756764 D COM600 Product version: 4.0 Fig. 5 COM600 web HMI showing persisting and fleeting alarms Fig. 6 COM600 Data historian...
  • Page 8: Goose Analyzer

    Better understanding of the process behaviour by joining time-based process measurements with production The COM600 GOOSE Analyzer Tool (GAT) and maintenance events helps the user is a professional system-level tool for to understand the process dynamics. It...
  • Page 9: Logic Processor

    IEC 61131-3 protocol. standard for programmable logic controllers (PLC). The programmable logic processor in COM600 is offered as a selectable software option. The PLC programming system 10. Substation enables programming and execution of automation tasks. In addition, the IEC 61131-...
  • Page 10 Grid Automation Controller 1MRS756764 D COM600 Product version: 4.0 EMS/ ENGINEERING SCADA ELECTRONIC SECURITY PERIMETER Built-in firewall LAN 1 Ethernet switch REF 542plus REF611 REF630 REF615 REF615 REF615 REF615 Fig. 8 Substation security and secured Web HMI for remote access...
  • Page 11: Integration Of Abb Ieds

    Further, communication diagnostic events can integration, minimizing device configuration be enabled to track all messages being sent and set-up times. The engineering in COM600 by or received from the IEDs. is done by selecting the connectivity package for the IED version and configuration or by Using the Station Automation Builder importing the configuration file from the IED.
  • Page 12: Communication

    Grid Automation Controller 1MRS756764 D COM600 Product version: 4.0 13. Communication In addition, COM600 offers OPC client and server connectivity. This enables data access and data sharing between the non-electrical COM600 is designed to support the system and the electrical system supporting IEC 61850 standard, and can thereby...
  • Page 13: Smart Grid

    When a fault occurs in the network, the FDIR function locates the fault based on switch open and trip information received from the COM600 can be ordered with a fault detec- IED of the affected feeder. Further, the FDIR tion, fault isolation and load restoration...
  • Page 14: Technical Data

    Grid Automation Controller 1MRS756764 D COM600 Product version: 4.0 16. Technical data Table 1. Dimensions Description Value Width 251.2 mm (284 mm with mounting kit) Height 103 mm (114 mm with mounting kit) Depth 313 mm Weight 7.7 kg Table 2. Power supply Description Value (Power supply “H”)
  • Page 15 Grid Automation Controller 1MRS756764 D COM600 Product version: 4.0 Table 5. Optional PCI extensions Description Value Serial interfaces 8 x RS-232/485 serial interfaces Ethernet interfaces 2 x 10BASE-T/100BASE-TX/1000BASE-T RJ-45 interfaces 1) Operating temperature 0° C - +55° C 2) Operating temperature 0° C - +55° C Table 6.
  • Page 16 Grid Automation Controller 1MRS756764 D COM600 Product version: 4.0 Table 9. Electromagnetic compatibility tests The EMC immunity test level meets the requirements listed below: Description Reference 1 MHz and 100 kHz burst disturbance test According to IEC 61000-4-18 and IEC 60255-22-1 • Common mode...
  • Page 17 Grid Automation Controller 1MRS756764 D COM600 Product version: 4.0 Table 11. Environmental tests Description Reference Dry heat test According to IEC 60068-2-2 Test values: • 96 h at +55ºC • 4 h at +70ºC Cold test According to IEC 60068-2-1 Test values: • 96 h at -10ºC • 4 h at -25ºC Damp heat test, cyclic...
  • Page 18 Grid Automation Controller 1MRS756764 D COM600 Product version: 4.0 Seismic test According to IEC 60255-21-3 test method B • biaxial multi-frequency random seismic test 2 x gn in horizontal direction, 1 x gn in vertical direction Table 13. EMC compliance Description Reference Complies with the EMC directive...
  • Page 19 Grid Automation Controller 1MRS756764 D COM600 Product version: 4.0 Table 17. IEDs with connectivity packages supporting COM600 (applies for the IEC 61850 and SPA protocols) 610 series IEDs Feeder Protection REF610 Motor Protection REM610 Voltage Protection REU610 611 series IEDs 615 series IEDs...
  • Page 20: Tools

    COM600 and the IEDs. The finalized projects are updated from SAB600 connectivity packages for ABB’s protection to COM600 at site or remotely provided that a and control IEDs enable an efficient configu- secure Ethernet connection is available. ration of COM600. The connectivity packages include descriptions of the data and signals Table 21.
  • Page 21: Mounting

    Product version: 4.0 18. Mounting fastened using the four holes on the unit and four screws. The COM600 computer is designed for mounting into a control panel by using the included wall-mount kit. The COM600 is Fig. 12 Top view...
  • Page 22: Selection And Ordering

    Fig. 14 to generate the order number when The type and serial number label identifies ordering. the COM600 units. The order number consists of a string of code generated from C O M 6 0 0 H R H 3 2 P P G N N N D...
  • Page 23 Requires Web HMI None Requires that at leat one slave protocol is chosen (digit #5=’’1” or “2”) Master protocols Fig. 14 Ordering key for Grid Automation Controller COM600 One master protocol Two master protocols Three master protocols C O M 6 0 0...
  • Page 24: References

    You will find the latest relevant information on the COM600 unit on the product page. The download area on the right hand side of the web page contains...
  • Page 25: Document Revision History

    Grid Automation Controller 1MRS756764 D COM600 Product version: 4.0 21. Document revision history Document Product History revision/date version A/19. Feb. 2009 Document was created B/26. Nov. 2009 Content updated to correspond to the product version C/5. Sep. 2011 Content updated to correspond to the product version D/31.
  • Page 28 Contact us ABB Oy Distribution Automation P.O. Box 699 FI-65101 VAASA, Finland Phone +358 10 22 11 +358 10 22 41094 www.abb.com/substationautomation ABB Inc. Distribution Automation 655 Century Point Lake Mary, Florida, U.S.A. Phone 407-732-2000 407-732-2335 www.abb.com/substationautomation...

Table of Contents