Mitsubishi Electric GB-50ADA-A Installation Instructions Manual

Mitsubishi Electric GB-50ADA-A Installation Instructions Manual

Hide thumbs Also See for GB-50ADA-A:

Advertisement

Air-Conditioner Network System
Centralized Controller
GB-50ADA-A
GB-50ADA-J
Installation/Instructions Manual
• Safety notes are marked with
WARNING or
depending on the severity of possible
consequences that may result when the
instructions are not followed exactly as
stated.
Proper installation is important for your
safety and proper functioning of the units.
Thoroughly read the following safety
precautions prior to installation.
To ensure safety and proper operation of the
unit, the unit should only be installed by
qualified personnel.
After reading this manual, pass the manual on to the end
user to retain for future reference.
The users should keep this manual for future reference and
refer to it as necessary. This manual should be made
available to those who repair or relocate the units. Make
sure that the manual is passed on to any future air
condition system users.
CAUTION,
Contents
Safety Precautions............................................ 2
1.
Introduction ............................................... 5
conditioners...................................... 6
2.
Parts List ................................................... 6
3.
Specifications............................................ 7
3-1. Product Specifications ..................... 7
3-2. External dimensions......................... 7
transmission lines ............................ 8
4.
System configuration ................................ 9
various devices .............................. 10
5.
Installation............................................... 13
5-1. Field-supplied parts........................ 13
5-3. Installation...................................... 15
6.
Wiring connections.................................. 16
transmission line ............................ 17
7.
Initial settings .......................................... 19
8.
Product features...................................... 21
9.
Test run................................................... 23
switches ......................................... 23
9-2. Service LED display....................... 23
10. External input/output ............................... 24
memory ................................................... 26
11-1. Switch setting................................. 27
11-2. Operational data ............................ 28
12. 7-segment LED ....................................... 30
settings........................................... 31
13. Error code list .......................................... 32
Page

Advertisement

Table of Contents
loading

Summary of Contents for Mitsubishi Electric GB-50ADA-A

  • Page 1: Table Of Contents

    Air-Conditioner Network System Centralized Controller GB-50ADA-A GB-50ADA-J Installation/Instructions Manual Contents Page Safety Precautions..........2 Introduction ..........5 1-1. Parts names and functions ....5 1-2. Monitor and operation of the air conditioners........6 1-3. About “Group” and “Block” ....6 Parts List ...........
  • Page 2: Safety Precautions

    Safety Precautions • Thoroughly read the following safety precautions prior to installation. • Observe these precautions carefully to ensure safety. WARNING Indicates a risk of death or serious injury. CAUTION Indicates a risk of injury or structural damage. ● Nomenclature (Prohibited actions) (Do not touch) (No water)
  • Page 3 Precautions during installation WARNING Do not install the controller where there is a risk of Take appropriate safety measures against earthquakes leaking flammable gas. to prevent the controller from causing injury. If flammable gas accumulates around the controller, it To prevent injury, install the controller on a flat surface may ignite and cause a fire or explosion.
  • Page 4 This controller is designed for exclusive use with the Building To avoid damage to the controller, do not make holes on the Management System by Mitsubishi Electric. The use of this controller cover. controller for with other systems or for other purposes may To avoid deformation and malfunction, do not install the cause malfunctions.
  • Page 5: Introduction

    Any connected air conditioning systems can be operated or monitored over the Web using browser software. Refer to the Web browser operation manual (separate volume) for how to use this functions. This manual covers the settings that can be made or functions that can be displayed only on the body of GB-50ADA-A or GB50ADA-J.
  • Page 6: Monitor And Operation Of The Air Conditioners

    1-2. Monitor and operation of the air conditioners To monitor and operate the air conditioners, license for “GB-50ADA Basic License Pack” or “Web Monitor” must be purchased and registered. Purchase the license from the dealer, and register on the Initial Setting Web or on the Web for Monitor and Operation. Refer to Web Browser Operation Manual for monitor and operation of air conditioners.
  • Page 7: Specifications

    3 Specifications 3-1. Product Specifications Items Specifications Rated input 100-240VAC ±10% 0.4-0.3A 50/60Hz Power source Fuse 250VAC 3.15A Time-delay Type (IEC127-2.S.S.5) Rated output of the power supply 22-30VDC to M-NET transmission lines External input/output 12VDC or 24VDC (requires an external power supply) Interface 100BASE-TX/10BASE-T USB1.1 supported...
  • Page 8: Supplying Power To The M-Net Transmission Lines

    3-3. Supplying power to the M-NET transmission lines GB-50ADA has a built-in function to supply power to the M-NET transmission line. (power supply coefficient: 6) The total power consumption coefficient of the system controller and M-NET remote controller to which GB-50ADA supplies power (See table 1) should not exceed the power supply coefficient of GB-50ADA, which is six.
  • Page 9: System Configuration

    4 System configuration The figure below only shows the transmission line connections. Power supply lines are omitted. Do not connect directly to the Internet. When connecting to the Internet, use a security device such as a VPN router. Indoor unit Centralized controller Local remote controller GB-50ADA...
  • Page 10: Setting M-Net Address For Various Devices

    4-1. Setting M-NET address for various devices The same address cannot be used more than once within the same M-NET system of GB-50ADA. (K-control units and K-control remote control addresses are excluded.) M-NET Address setting method address Assign the lowest address to the main indoor unit in the group, and assign sequential Indoor unit 1 ~ 50 addresses to the rest of the indoor units in the same group.
  • Page 11 * Main and Sub system controllers (M-NET) GB-50ADA can be used only as the Main controller, not as a Sub controller. Main system controller (Main SC) Main SC refers to a controller that controls all other system controllers including the units they control. If a given system has only one system controller, that controller becomes a Main controller.
  • Page 12: M-Net System Setting Example

    4-2. M-NET system setting example 1 Connecting multiple M-NET system controllers M-NET GB-50ADA 50 indoor units “000” Group 1 - Group 20 (Main system controller) ON/OFF remote controller “201” (Sub system controller) Make the initial setting such as group setting or interlock setting using the Initial Setting Web on GB-50ADA. Designate a system controller within the system as the only controller from which operation prohibit setting can be made.
  • Page 13: Installation

    5 Installation 5-1. Field-supplied parts The following parts are required to install the unit. Required parts Specification Power cable/ Power supply cable of appliances shall not be lighter than design 245 IEC 57 or 227 IEC 57. protective earth cable Cable size: 0.75mm²...
  • Page 14: M-Net Transmission Line Length

    5-2. M-NET transmission line length • Connect the GB-50ADA to the transmission line for centralized control (TB7 on the outdoor unit). • There should only be one power supply source within a single M-NET transmission circuit. The factory setting is to supply power from GB-50ADA.
  • Page 15: Installation

    5-3. Installation • Leave enough space around the unit as shown in the figure below to allow for an installation/uninstalltaion of the cover and wiring. • Screw down the cover with M4 screws as shown in the figure below. Be sure to screw down the four corners to prevent it from falling. •...
  • Page 16: Wiring Connections

    6 Wiring connections WARNING • Electric work must be performed by an authorized technician. Improper wiring work may result in electric shock or fire. • Turn off the power supply before performing wiring work. CAUTION • To avoid damage to the terminal block, do not connect an AC power supply (100-240VAC) to the M-NET transmission terminal block.
  • Page 17: Connecting The M-Net Transmission Line

    6-3. Connecting the M-NET transmission line CAUTION • In an air conditioner system has more than 1 Outdoor units, System controller receiving transmission power through TB7 on one of the Outdoor unit would have a risk that the connected Outdoor units failure would stop power supply to System controller, and disrupt the whole system.
  • Page 18: Connecting The Lan Cable

    6-4. Connecting the LAN cable Connect the LAN cable to the LAN connector on the GB-50ADA. • The maximum distance between the HUB and GB-50ADA is 100 m (328 ft). • The LAN cable is field-supplied. Use a category 5 or above cable (straight cable). •...
  • Page 19: Initial Settings

    7 Initial settings Initial setting procedures setting : Settable Steps Setting items Switch on the GB-50ADA Web browser IP address of the GB-50ADA/Network Default settings: Refer to section 7-1 “IP address and Refer to section 7-1 “IP address and IP address 192.168.1.1 network settings”...
  • Page 20: Ip Address And Network Settings

    7-1. IP address and network settings When connecting GB-50ADA to a dedicated LAN system, set the IP address and network settings for GB-50ADA with “Quick IP address setting switch.” (Refer to section 7-1-1 “Quick IP address setting switch.”) When connecting to an existing LAN system or settings cannot be made with Quick IP address setting switch, set them with the detail setting switches.
  • Page 21: Product Features

    8 Product features GB-50ADA is a centralized controller that can be operated over the Web. Any connected air conditioning systems can be operated or monitored over the Web using browser software. Refer to the Web browser operation manual (separate volume) for how to use this functions. Function Description Indoor unit, independent OA...
  • Page 22 Function Description Operation of certain functions from the local remote controllers can be prohibited Prohibit local remote control collectively or for each group or blocks of indoor units. (Applicable functions: ON/OFF, operation mode, temperature setting, filter sign) Filter sign reset Filter sign can be reset for each group or block of indoor units.
  • Page 23: Test Run

    9 Test run 9-1. Batch operation/Stop (error reset) switches • Before performing a test run, check that the group setting and interlock settings have been properly made. • The batch operation function on the GB-50ADA switches cannot be used to change the operation mode of the connected indoor units (including the test run mode).
  • Page 24: External Input/Output

    10 External input/output 10-1. External signal input function * To use the external signal input, a separately-sold external input/output adapter (PAC-YG10HA) and external power supply are required. External input/output terminal (CN5) MODEL : Serial number : 10-1-1. External input signal function setting (to be set from the web browser for Initial settings) External contact signal (12VDC or 24VDC) can be used to send signals indicating the following status of all air conditioning units that are controlled by the controller: Emergency stop/Normal, Run/Stop, and local remote controller operation Prohibit/Permit.
  • Page 25: External Signal Output Function

    (B) Pulse signals 1 If pulse signals to operate the units are received while the units are in operation, the units will continue their operation (same with the Stop, Prohibit, and Permit signals). 2 When operation from the local remote controllers is prohibited, Run/Stop mode, operation mode, temperature setting, and filter reset settings cannot be changed from the local remote controller.
  • Page 26: Copy To Usb Memory And Read From Usb Memory

    11 Copy to USB memory and read from USB memory To copy the data to USB memory and to read the dada from USB memory, refer to the table below and section 11-1 “switch setting”. SW601 Item [0: OFF, 1: ON] Setting items Explanation Notes...
  • Page 27: Switch Setting

    11-1. Switch setting How to set the switches is explained below, using an example of how to set the item No. 250 “(0) Initial setting data and User info data ”. Steps Setting item Setting method 7-segment LED display Select the item No. Set SW601 to [1111 1010]. [ _ 250] will appear for one second, and the SW606 and SW607 preset values will appear.
  • Page 28: Operational Data

    11-2. Operational data 11-2-1. Charge parameter data The format of the CSV file that is output when the charge parameter is saved is as follows: Note: Dates in the folder name, the file name,and the file contents are displayed in the format selected on the Initial Setting Web.
  • Page 29 11-2-2. Power consumption data The format of the CSV file that is output when the power consumption data is saved is as follows: Note: Dates in the folder name, the file name,and the file contents are displayed in the format selected on the Initial Setting Web.
  • Page 30: Segment Led

    12 7-segment LED The settings for switches SW601, SW606, and SW607 on the GB-50ADA can be verified on the 7-segment LED. Numerical display (Example: 18.8) Flag display (Example: LD1, LD2, LD5, and LD7 are on.) 7-segment LED SW601 Detail setting switch (Use to select items) SW606, SW607 Detail setting switch...
  • Page 31: 7-Segment Led Display And Switch Settings

    12-1. 7-segment LED display and switch settings SW601 Display Item Notes SW606 SW607 1234 5678 0000 0000 status Normal Error Starting Refer to section 9 “Test run.” status operation 0: OFF Error detection [Error code] and [Error source address] appear alternately. The latest error appears if multiple [----] appears when there are 1: ON...
  • Page 32: Error Code List

    13 Error code list Notes The list below contains all error codes. Some of these error codes may not be applicable to the system to which the GB-50ADA is connected. The following is a list of the error codes and their meaning. (A) indicates A-control units 0100 “Blanket unit error”...
  • Page 33 2500 “Water system not operate due to water leak” 2501 “Water system not operate due to water supply suspension” 2502 “Water system not operate due to drain pump abnormality” 2503 “Water system not operate due to drain sensor abnormality/float switch function” 2504 “Water system not operate due to liquid level abnormality”...
  • Page 34 423* “Inverter radiating thermostat abnormality - Inverter No.: *” 4240 “Inverter overcurrent (overload) protection” 424* “Inverter overcurrent protection - Inverter No.: *” 4250 “Inverter IPM/bus voltage abnormality” /Power module abnormality (A) 425* “Inverter IPM abnormality *” 4260 “Inverter cooling fan trouble” 426* “Inverter cooling fan trouble - Inverter No.: *”...
  • Page 35 6754 “K abnormality - Drain sensor abnormality, Float switch function” 6755 “K abnormality - Drain pump abnormality” 6756 “K abnormality - Coil frost/overheat protection” 6757 “K abnormality - System error” 6758 “K abnormality - Outdoor unit trouble, Indoor/outdoor communication error” 6761 “K abnormality - Room temperature thermistor abnormality”...
  • Page 36 7116 “System abnormality - Replace non-wash setting error” 7117 “System abnormality- Model identification setting error” 7130 “System abnormality - Different unit model error” 7131 “System abnormality- Mixed cooling only H/P connection error (Facility PAC)” 7132 “System abnormality - Multiple entries of operation performance (Facility PAC)” 7200 “System abnormality - Numeric values unsettled”...
  • Page 40 Please be sure to put the contact address/telephone number on this manual before handing it to the customer. HEAD OFFICE: TOKYO BLDG. , 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN Authorized representative in EU: MITSUBISHI ELECTRIC EUROPE B.V. HARMAN HOUSE, 1 GEORGE STREET, UXBRIDGE, MIDDLESEX UB8 1QQ, U.K. WT05866X03...