System x PDU Technical Reference – International
v3.0.2
BASIC PDUS
Lenovo basic Power
Distribution Units (PDUs)
provide an economical, basic
power distribution capacity
for rack based systems.
MONITORED PDUS
Lenovo switched Power
Distribution Units (PDU)
provides outlet dense advanced
power distribution for efficient
energy monitoring to help
protect and manage your
System x® rack environment.
SWITCHED & MONITORED
PDUS
Lenovo switched and
monitored Power
Distribution Units (PDUs)
simplify deployment and
provide outlet-dense
advanced power
distribution for efficient
energy management to
protect and manage your
high-availability System x
rack environment.

Advertisement

Table of Contents
loading

Summary of Contents for Lenovo System x PDU

  • Page 1 System x PDU Technical Reference – International v3.0.2 BASIC PDUS MONITORED PDUS SWITCHED & MONITORED PDUS Lenovo basic Power Lenovo switched Power Lenovo switched and Distribution Units (PDUs) Distribution Units (PDU) monitored Power provide an economical, basic provides outlet dense advanced...
  • Page 2 Authors Rani Doughty rdoughty@lenovo.com Matthew Archibald marchibald@lenovo.com Questions / Comments: power@lenovo.com Data Center Services, Enterprise Business Group Revision History 1.0 – July 15, 2009 Initial Release. First published by William S Champion. 1.2.0 – February 17, 2010 Corrected Ultra Density PDU part numbers, update server label ratings.
  • Page 3: Table Of Contents

    Table of Contents INTRODUCTION..........................7 ...........................7 OW TO USE THIS GUIDE ..........................8 TYPES EXPLAINED Basic PDUs (non-Monitored)..................8 Monitored PDUs.....................8 Switched and Monitored PDUs................8 ..........................9 UMMARY OF ..........................13 PLUGS ..........................14 IRCUIT APACITIES BASIC PDUS (NON-MONITORED)....................15 PDU...........................18 NIVERSAL Quick Specs......................18 Front View and Outlets..................21 Input Line Cords....................22 Specifications –...
  • Page 4 Quick Specs......................64 Front and Back View and Outlets.................66 Input Line Cords....................69 Specifications.......................70 Accessory Kit......................72 Racking.........................74 Installation and Maintenance Guide..............78 0U 24 C13 PDU..........................79 Quick Specs......................79 Front View and Outlets..................80 Input Line Cords....................82 Specifications.......................82 Accessories......................84 Racking.........................86 Installation and Maintenance Guide..............89 0U 12 C19 / 12 C13 PDU........................90 Quick Specs......................90 Front View and Outlets..................90 Input Line Cords....................92...
  • Page 5 Single phase – 46M4004 ..................126 Input Line Cords....................127 Specifications.....................128 Accessory Kit......................129 Racking.......................131 Installation and Maintenance Guide..............134 1U 9 C19 / 3 C13 S PDU................135 WITCHED AND ONITORED Quick Specs......................135 Front and Back View and Outlets...............137 Input Line Cords....................140 Specifications.....................141 Accessory Kit......................143 Racking.......................145 Installation and Maintenance Guide..............148 0U 24 C13 S...
  • Page 6 40K9611 – DPI 32A Cord (IEC 309 3P+N+G)............178 40K9612 – DPI 32A Cord (IEC 309 P+N+G)............179 40K9613 – Lenovo DPI 63A Cord (IEC 309 P+N+G)..........180 40K9617 – Lenovo DPI 32A Cord (AUS/NZ 3112 32A)........181 40K9618 – DPI 30A Cord (KSC 8305 30A)............182 0U PDU A ....................183...
  • Page 7 16A Three Phase Delta Power Calculations............219 SUPPORT...........................220 ............................221 ELPFUL INKS...
  • Page 8: Introduction

    Introduction Only Lenovo System x Power Distribution Units (PDUs) that are currently marketed Internationally are included in this guide. The intent of this guide is to provide PDU information needed in planning power requirements. This guide is best used in softcopy form, since it contains hyperlinks for navigation.
  • Page 9: Pdu Types Explained

    Lenovo Systems Director, Active Energy Manager (AEM). A monitored PDU has the ability to control the outlets remotely (switch individual outlets on/off) via the PDUs web interface or via Lenovo Active Energy Manager (AEM). All monitored (and switched and monitored) PDUs collect the below data at a PDU...
  • Page 10: Summary Of Pdus

    Summary of PDUs This section is a quick summary and links to all of the available PDUs Internationally. Basic PDUs Option Phase Voltage (V) Line Cord Number Page Number (ph) (Derated) / Type Link Outlet Universal 39Y8952 1ph 230VAC 16A CEE7-VII Europe 7 / C13 Rack PDU*...
  • Page 11 Basic PDUs Continued Option Phase Voltage Line Cord Number Number (ph) (Derated) / Type of Outlet Link Ultra Density 71762NX 1ph 220- 32A IEC 309 P+N+G 9 / C19 Enterprise 240VAC 3 / C13 63A IEC 309 P+N+G 230- 32A AUS/NZ 3112 240VAC 220VAC 30A KSC 8305...
  • Page 12 Monitored PDUs Option Phase Voltage (V) Line Cord Number Page Number (ph) (Derated) / Type of Link Outlet 39M2816 220- 32A IEC 309 P+N+G 12 / C13 Enterprise 240VAC 63A IEC 309 P+N+G PDU+ C13 230- 32A AUS/NZ 3112 240VAC 220VAC 30A KSC 8305...
  • Page 13 Switched and Monitored PDUs Option Phase Voltage Line Cord Number / Page Number (ph) (Derated) Type of Link Outlet 1U 12 C13 46M4004 1ph 220- 32A IEC 309 P+N+G 12 / C13 240VAC Switched and 63A IEC 309 P+N+G Monitored 230- 32A AUS/NZ 3112 240VAC...
  • Page 14: C13 And C19 Plugs

    C13 to C14 plugs. These plugs are used for the following: Lenovo NeXtScale chassis's., • Lenovo System x Rack servers, • Lenovo System x Tower servers, and • Lenovo BladeCenter S (model dependent) • Hardware Figure 1: C13 to C14 plugs Figure s hows the C19 to C20 plugs.
  • Page 15: Circuit Capacities

    Circuit Capacities The following table represents the derated values/Watt capacities for power circuits running between 13A-63A@100V-415V for both single phase and three phase electrical circuits. Branch Circuit Rating Volt-ampere (VA) 13A / 230V 1ph 2990VA 15A / 230V 1ph 3450VA 15A/ 240V 1ph 3600VA 16A/ 220V 1ph...
  • Page 16: Basic Pdus (Non-Monitored)

    Basic PDUs (non-Monitored) The following section provides information and part numbering for Basic PDUs. Click on the description of each PDU to read more information. Option Phase Voltage Line Cord Number Page Number (ph) (Derated) / Type Link Outlet* Universal Rack 39Y8952 1ph 230VAC 16A CEE7-VII Europe...
  • Page 17 DPI Enterprise 39Y8948 1ph 220- 32A IEC 309 P+N+G 6 / C19 – C19 PDU 240VAC 63A IEC 309 P+N+G 230- 32AAUS/NZ 3112 240VAC 220VAC 30A KSC 8305 3ph Y 380- 32A (32A/ph) IEC 309 415VAC 3P+N+G Option Phase Voltage Line Cord Number Page...
  • Page 18: Universal Rack Pdu

    Universal Rack PDU This section discusses the Lenovo Universal Rack PDU. This section is broken up into the following sections. Quick Specs • Front View and Outlets • Input Line Cords • Specifications – Asia Pacific • Accessory Kit •...
  • Page 19 PDU 39Y8957 + Line Cord 4.3m BS 1363/A (HK/UK) Outlets types Seven IEC C13 Type 13A/230V Power Capacity 2990VA @ 230V Power Limit per PDU 15A (line cord 13A) Phase Single phase PDU 39Y8958 + Line Cord 4.3m AS/NZ 3112 (Aust/NZ) Outlets types Seven IEC C13 Type...
  • Page 20 PDU 39Y8962 + Line Cord 4.3m IRAM 2037 (Argentina) Outlets types Seven IEC C13 Type 16A/220V Power Capacity 3520VA @ 220V Power Limit per PDU Phase Single phase PDU 39Y8953 + Line Cord 4.3m IEC 309 P+N+G (Denmark/Switzerland) Outlets types Seven IEC C13 Type 16A/230V...
  • Page 21 All PDUs + Line Cord IEC320 C19 to C20 Outlets types Seven IEC C13 Type 16A/100-250VAC Power Capacity 3200VA @ 200V Power Limit per PDU Phase Single phase...
  • Page 22 Front View and Outlets Figure displays a front view of the DPI Universal Rack PDU. Figure 3: Front view of the DPI Universal PDU Figure displays the outlet numbering and amperage of the DPI Universal Rack PDU. The PDU has a 15A internal breaker and C13 outlets. See the Specifications –...
  • Page 23 Input Line Cords The following input line cords are for connecting the PDU to appropriate power circuits. This may include for example, the wall or floor outlets to provide power to the PDU. See the Universal Rack PDU line cord plugs section for pictures of the plugs.
  • Page 24 Specifications – Asia Pacific The following table are specifications for the Universal Rack PDU for AP. Asia Pacific - Universal Rack PDU – Specifications Input Line Cord* to PDU or Aus/NZ Honk Kong / Taiwan China (US LV) Outlets types seven IEC seven IEC seven IEC...
  • Page 25: Specifications - Emea

    Specifications – EMEA The following table are specifications for the Universal Rack PDU for EMEA. EMEA – Universal Rack PDU – Specifications Input Line to PDU or UPS 16A/230V United Kingdom Saudi Arabia (US Cord* Outlets types seven IEC C13 seven IEC seven IEC C13 seven IEC C13...
  • Page 26: Accessory Kit

    Accessory Kit The following items make up the accessory kit that contains miscellaneous hardware for installing the Rack PDU in a rack cabinet. These are shipped with the PDUs. Figure 5: Accessory kit These accessories are for supporting the racking of the DPI PDUs in either the side pocket of a rack or U space of a rack.
  • Page 27: Racking

    Racking This section discusses mounting the DPI PDU in the side pockets of a rack and EIA (U space) of a rack. Mounting in side pocket Mounting the DPI PDUs in the side pocket requires the use of the small vertical mounting plate, shipped as part of the PDU accessory kit, see the Accessory Kit section for additional information.
  • Page 28 Mounting In Lenovo Enterprise Rack (9308 & 1410) & Lenovo Enterprise V2 Rack (9363) Rear Zero Pocket Mounting the DPI PDU (39Y8951) in the side pocket of an enterprise rack requires the use of the horizontal mounting bracket, shipped as part of the PDU accessory kit,...
  • Page 29 Mounting in EIA (U space) of rack Mounting the DPI PDU (39Y8951) in the U space of a rack requires the use of the horizontal mounting bracket, shipped as part of the PDU accessory kit, see the Accessory Kit section for additional information. Two PDUs will fit in 1U of rack space as seen in figure 8.
  • Page 30: Installation And Maintenance Guide

    Installation and Maintenance Guide The following link is the installation and maintenance guide for the Lenovo Universal Rack PDU: ftp://ftp.software.ibm.com/systems/support/system_x_pdf/02r2738.pdf...
  • Page 31: Front End Pdu

    Racking • Installation and Maintenance Guide • Quick Specs The following tables are quick overviews of the Lenovo Front End PDUs. For additional information refer to the Specifications section. PDU 39Y8934 + Included Line Cord IEC 309 P+N+G Outlet Types...
  • Page 32 PDU 39Y8936 + Included Line Cord KSC 8305 Outlet Types three IEC C19 Type 30A/220V Power Capacity 6600VA @ 220V Power Limit per PDU Phase Single phase PDU 39Y8937 + Included Line Cord AS/NZS 3112 Outlet Types three IEC C19 Type 32A/230V Power Capacity...
  • Page 33: Front And Back View And Outlets

    Front and Back View and Outlets Figure displays the front and back view of the Front End PDU. Figure displays the outlets and amperage. Figure 9: Front and back view of the FE PDU Figure 11: Internal outlet and amperage Figure 10: Outlets and amperage...
  • Page 34: Input Line Cords

    PDU P/N FC Line Cords shipped with PDU 39Y8934 A11V Lenovo DPI IEC 309 P+N+G (2.5m) line cord 32A / 220-240VAC Single Phase 39Y8935 A11W Lenovo DPI IEC 309 P+N+G (2.5m) line cord 63A 220V-240VAC Single Phase 39Y8936 A11Y Lenovo DPI KSC 8305 30A (2.5m) line cord 30A 230VAC Single...
  • Page 35: Specifications

    Specifications The following table are specifications for the 39Y8934, 39Y8935, 39Y8936, and 39Y8937 Front End PDUs. Specifications PDU Part Number 39Y8934 39Y8935 39Y8936 39Y8937 PDU Feature A11V A11W A11Y A11X Code* Type 32A/220- 63A/220-240V 30A/220V 32A/230V 240V Phase Single Single Single Single Outlets types...
  • Page 36: Accessory Kit

    Accessory Kit The following is miscellaneous hardware for installing the Rack PDU in a rack cabinet. The large vertical mounting bracket is shipped standard with the PDU. Figure 12: Accessory kit Miscellaneous hardware kit also included for attaching the front-end PDU to the a mounting plate and installing in a rack cabinet.
  • Page 37: Racking

    Racking This section discusses mounting the Front-end PDUs (39Y8934, 39Y8935, 39Y8936, and 39Y8937) in the side pockets of a rack and EIA (U space) of a rack. Mounting in side pocket of rack Mounting the Front-end PDUs (39Y8934, 39Y8935, 39Y8936, and 39Y8937) in the side pocket requires the use of the large vertical mounting plate, shipped as part of the PDU accessory kit, see the Accessory Kit...
  • Page 38 Mounting In Lenovo Enterprise Rack (9308 & 1410) & Lenovo Enterprise V2 Rack (9363) Rear Zero Pocket Mounting the Front-end PDUs (39Y8934, 39Y8935, 39Y8936, and 39Y8937) in the side pocket of an Enterprise rack, requires the use of the large vertical mounting...
  • Page 39 Option 2 Mounting the Front-end PDUs (39Y8934, 39Y8935, 39Y8936, and 39Y8937) in the side pocket of an Enterprise rack, requires the use of the large vertical mounting plate, shipped as part of the PDU accessory kit, see the Accessory Kit section for additional information.
  • Page 40 Mounting in side pocket Mounting the Front-end PDUs (39Y8934, 39Y8935, 39Y8936, and 39Y8937) in 1U space of the rack requires a horizontal mounting plate. Note: The Front-end PDU is only shipped with the large vertical wall mounting plate. The PDU can be mounted in a 1U horizontal space of the rack if you have rack PDU hardware to mount it in.
  • Page 41: Installation And Maintenance Guide

    Installation and Maintenance Guide The following link is the installation and maintenance guide for the Lenovo Front End PDU: 39Y8934, 39Y8935, 39Y8936, and 39Y8937 ftp://ftp.software.ibm.com/systems/support/system_x_pdf/02r2739.pdf...
  • Page 42: Dpi® Enterprise - C13 Pdu

    DPI® Enterprise – C13 PDU This section discusses the 39Y8941 DPI C13 PDU. This section is broken up into the following sections. Quick Specs • Front View and Outlets • Input Line Cords • Specifications • Accessory Kit • Racking •...
  • Page 43 PDU 39Y8941 + Line Cord 40K9613 Type 63A/220-240V Outlets types twelve IEC C13 Power Capacity 14490VA @ 230V Power Limit per PDU Phase Single phase PDU 39Y8941 + Line Cord 40K9617 Type 32A/230V Outlets types twelve IEC C13 Power Capacity 7360VA @ 230V Power Limit per PDU Phase...
  • Page 44 Front View and Outlets Figure displays a front view of the 39Y8941 PDU. Figure 17: Front and back view of the DPI Enterprise C13 PDU Single phase 39Y8941PDU Figure 18: Outlets and amperage...
  • Page 45 Three phase 39Y8941 PDU Figure 19: Outlet and amperage...
  • Page 46 32A (32A / Phase) 380-415VAC Three Phase Wye 96A Total Circuit Capacity 39Y8941 40K9612 6014 Lenovo DPI IEC 309 P+N+G (4.3m) line cord 32A / 220-240VAC Single Phase 39Y8941 40K9613 6015 Lenovo DPI IEC 309 P+N+G (4.3m) line cord...
  • Page 47 Specifications The following table are specifications for the 39Y8941 DPI C13 PDU. Specifications Line cord PN Line cord PN Line cord PN Line cord PN Line cord PN Input Line 40K9611 40K9612 40K9613 40K9617 40K9618 Cord Type* Type 32A/380- 32A / 220- 63A/220V- 32A / 230V 30A / 230V...
  • Page 48 Accessory Kit The following items make up the accessory kit that contains miscellaneous hardware for installing the Rack PDU in a rack cabinet. These are shipped with the PDU. Figure 20: Accessory kit Miscellaneous hardware kit for attaching the mounting brackets to the PDU and installing in a rack, and cable straps are also included.
  • Page 49 Racking This section discusses mounting the DPI C13 (39Y8941) in the side of a rack, the side pockets of a rack and EIA (U space) of a rack. Mounting in side pocket Mounting the DPI C13 PDUs in the side pocket requires the use of the vertical mounting bracket, shipped as part of the PDU accessory kit, see the Accessory Kit section for additional information.
  • Page 50 Mounting In Lenovo Enterprise Rack (9308 & 1410) & Lenovo Enterprise V2 Rack (9363) Rear Zero Pocket (side pocket) Mounting the DPI PDUs (39Y8941) in the side pocket of an enterprise rack requires the use of the horizontal mounting bracket, shipped as part of the PDU accessory kit,...
  • Page 51 Mounting in EIA (U space) of rack Mounting the DPI C13 PDUs (39Y8941) in the U space of a rack requires the use of the horizontal mounting bracket, shipped as part of the PDU accessory kit, see the Accessory Kit section for additional information.
  • Page 52 Installation and Maintenance Guide The following link is the installation and maintenance guide for the Lenovo DPI Enterprise – C13 PDU 39Y8941 ftp://ftp.software.ibm.com/systems/support/system_x_pdf/43v6030.pdf...
  • Page 53: Dpi Enterprise - C19 Pdu

    DPI Enterprise – C19 PDU This section discusses the 39Y8948 DPI Enterprise C19 PDU. This section is broken up into the following sections. Quick Specs • Front View and Outlets • Input Line Cords • Specifications • Accessory Kit • Racking •...
  • Page 54 PDU 39Y8948 + Line Cord 40K9613 Type 63A / 220V-240V Outlets types six IEC C19 Power Capacity 14490VA @ 230V Power Limit per PDU Phase Single phase PDU 39Y8948 + Line Cord 40K9617 Type 32A / 230V Outlets types six IEC C19 Power Capacity 7360VA @ 230V Power Limit per PDU...
  • Page 55 Front View and Outlets The 39Y8948 PDU has 5 optional line cords for use in different regions. The following figure displays a front view picture of the PDU. Figure 24: Front panel of the DPI Enterprise C19 PDU Figure shows the 39Y8948 PDU outlets and amperage.
  • Page 56 Outlet and amperage for the three and single phase 39Y8941 PDU. Figure 25: Lenovo DPI C19 PDU outlet and breaker amperage Note: Derated 16A MAX available per breaker/group.
  • Page 57 Lenovo DPI IEC-309 3P+N+G (4.3m) line cord 32A (32A / Phase) 380-415VAC Three Phase Wye 96A Total Circuit Capacity 39Y8948 40K9612 6064 Lenovo DPI IEC 309 P+N+G (4.3m) line cord 32A / 220-240VAC Single Phase 39Y8948 40K9613 6065 Lenovo DPI IEC 309 P+N+G (4.3m) line cord...
  • Page 58 Specifications The following table are specifications for the 39Y8948 DPI C19 PDU. Specifications Line cord PN Line cord PN Line cord PN Line cord PN Line cord PN Input Line 40K9611 40K9612 40K9613 40K9617 40K9618 Cord Type* Type 32A/380- 32A / 220- 63A/220V- 32A / 230V 30A / 230V...
  • Page 59 Accessory Kit The following items make up the accessory kit that contains miscellaneous hardware for installing the Rack PDU in a rack cabinet. These are shipped with the PDU. Figure 26: Accessory kit Miscellaneous hardware kit for attaching the mounting brackets to the PDU and installing in a rack, and cable straps are also included.
  • Page 60 Racking This section discusses mounting the DPI C19 (39Y8948) in the side of a rack, the side pockets of a rack and EIA (U space) of a rack. Mounting in side pocket Mounting the DPI C19 PDU in the side pocket requires the use of the vertical mounting bracket, shipped as part of the PDU accessory kit, see the Accessory Kit section for additional information.
  • Page 61 Mounting In Lenovo Enterprise Rack (9308 & 1410) & Lenovo Enterprise V2 Rack (9363) Rear Zero Pocket (side pocket) Mounting the DPI PDU (39Y8948) in the side pocket of an enterprise rack requires the use of the horizontal mounting bracket, shipped as part of the PDU accessory kit,...
  • Page 62 Mounting in EIA (U space) of rack Mounting the DPI C19 PDU (39Y8948) in the U space of a rack requires the use of the horizontal mounting bracket, shipped as part of the PDU accessory kit, see the Accessory Kit section for additional information.
  • Page 63 Installation and Maintenance Guide The following link is the installation and maintenance guide for the Lenovo DPI Enterprise – C19 PDU 39Y8948 ftp://ftp.software.ibm.com/systems/support/system_x_pdf/43v6030.pdf...
  • Page 64: Ultra Density Enterprise Pdu

    Ultra Density Enterprise PDU This section discusses the 71762NX Ultra Density Enterprise C19/C13 PDU. This section is broken up into the following sections. Quick Specs • Front and Back View and Outlets • Input Line Cords • Specifications • Accessory Kit •...
  • Page 65 PDU 71762NX + Line Cord 40K9613 Type 63A / 220V-240V Outlets types Nine IEC C19, and three IEC C13 Power Capacity 14490VA @ 230V Power Limit per PDU 63A Phase Single phase PDU 71762NX + Line Cord 40K9617 Type 32A / 230V Outlets types Nine IEC C19, and three IEC C13 Power Capacity...
  • Page 66 Front and Back View and Outlets The 71762NX has detachable single phase line cord options and three phase option. The following figures displays a front and back view of the PDU. Figure 30: Front and back panels of the Ultra Density Enterprise C19 PDU The following figures show the PDUs outlets and amperage for single phase and three phase.
  • Page 67 Three phase 71762NX PDU Figure 31: Outlets and amperage...
  • Page 68 Single phase model 71762NX PDU Figure 32: Outlets and amperage...
  • Page 69 32A (32A / Phase) 380-415VAC Three Phase Wye 96A Total Circuit Capacity 71762NX 40K9612 6502 Lenovo DPI IEC 309 P+N+G (4.3m) line cord 32A / 220-240VAC Single Phase 71762NX 40K9613 6503 Lenovo DPI IEC 309 P+N+G (4.3m) line cord...
  • Page 70 Specifications The following table are specifications for 71762NX DPI Ultra Density Enterprise PDU. Specifications Line cord PN Line cord PN Line cord PN Line cord PN Line cord PN Input Line 40K9611 40K9612 40K9613 40K9617 40K9618 Cord Type* Type 32A/380- 32A / 220- 63A/220V- 32A / 230V...
  • Page 71: Accessory Kit

    Accessory Kit The following items make up the accessory kit that contains miscellaneous hardware for installing the Rack PDU in a rack cabinet. These are shipped with the PDU. Figure 33: Accessory kit Misc hardware kit also included for attaching PDU to brackets and installing in a rack.
  • Page 72: Racking

    Racking This section discusses mounting for the 71762NX Ultra Density C19/C13 PDU in the side of a rack, the side pockets of an Enterprise rack (0U space) and EIA (U space) of a rack. Mounting in side pocket Mounting the Ultra Density C19/C13 PDU in the side pocket requires the use of the vertical mounting bracket, shipped as part of the PDU accessory kit, see the Accessory Kit section for additional information.
  • Page 73 Mounting In Lenovo Enterprise Rack (9308 & 1410) & Lenovo Enterprise V2 Rack (9363) Rear Zero Pocket (side pocket) Mounting the 71762NX Ultra Density C19/C13 PDU in the side pocket of an enterprise rack requires the use of the horizontal mounting bracket, shipped as part...
  • Page 74 Mounting in EIA (U space) of rack Mounting the 71762NX Ultra Density C19/C13 PDU in the U space of a rack requires the use of the horizontal mounting bracket, shipped as part of the PDU accessory kit, see the Accessory Kit section for additional information.
  • Page 75: Installation And Maintenance Guide

    Installation and Maintenance Guide The following link is the installation and user guide for the Lenovo Ultra Density Enterprise PDU 71762NX http://www.ibm.com/support/entry/portal/docdisplay?lndocid=MIGR-5076527...
  • Page 76: 0U 24 C13 Pdu

    0U 24 C13 PDU This section discusses the 46M4131 and 46M4122 0U 24 C13 PDU. This section is broken up into the following sections. Quick Specs • Front View and Outlets • Input Line Cords • Specifications • Accessories • Racking •...
  • Page 77 Front View and Outlets There are 2 type of 0U 24 C13 PDU's. The 46M4122 and 46M4131. The PDUs are identical except for the line cord. The line cord determines single phase or three phase operation. The 46M4131 has an attached single phase line cord. The 46M4122 has an attached 3 phase line cord.
  • Page 78 Three phase 46M4122 PDU Figure 39: Outlets and amperage Each phase has eight 10A outlets. For derated, 16A max is available per breaker. Refer to the Specifications for additional information.
  • Page 79 Input Line Cords The following input line cords are for connecting the PDU to appropriate power circuits. This may include for example, the wall or floor outlets to provide power to the PDU. See page 0U PDU Attached line cord and plugs for a picture of the line cord plugs.
  • Page 80 Specifications The following table are specifications for the 46M4131 and 46M4122 0U C13 PDUs. Specifications PDU Part Number 46M4131 46M4122 Feature Code 5925 5922 Input Line Cord Attached Attached Type* Phase Single phase Three phase Type 32A / 220V-240V 16A / 220V-240V Outlets types twenty four IEC C13 twenty four IEC C13...
  • Page 81: Accessories

    Accessories The following items make up the accessory kit that contains miscellaneous hardware for installing the Rack PDU in a rack cabinet. These are shipped with the PDU. Figure 40: Accessory kit for PDUs 46M4128, 46M4125, and 46M4140 Miscellaneous hard ware kit for attaching the mounting brackets to the PDU and installing in a rack cabinet.
  • Page 82: Racking

    Racking This section discusses mounting for the Lenovo 0U PDUs in the back of the Lenovo Standard racks (9307 and 9956), mounting in the back of the Lenovo Enterprise racks (9308 and 1410), and the Lenovo Enterprise rack v2 (9363), and the mounting in Lenovo racks with integrated PDU mounting keyholes (9362, 9361, and 9360).
  • Page 83 Mounting the 0U PDUs at the back of an Enterprise Rack Cabinet (9308 and 1410) and the Lenovo Enterprise V2 Rack (9363) requires the use of the two upper and two lower mounting brackets, shipped as part of the PDU accessory kit, see the Accessories section for additional information.
  • Page 84 Mounting In the Back of Lenovo Racks with Integrated PDU Mounting Keyholes (9362, 9361, and 9360) Mounting the 0U PDUs at the back of a rack with mounting key holes is displayed in Figure Figure 43: Rack with mounting keyholes at the rear...
  • Page 85: Installation And Maintenance Guide

    Installation and Maintenance Guide The following link is the installation and user guide for the Lenovo 0U 24 C13 PDU 46M4122, and 46M4131 http://www.ibm.com/support/entry/portal/docdisplay?lndocid=MIGR-5085549...
  • Page 86: 0U 12 C19 / 12 C13 Pdu

    0U 12 C19 / 12 C13 PDU This section discusses the 46M4143 0U 12 C19 / 12 C13 PDU. This section is broken up into the following sections. Quick Specs • Front View and Outlets • Input Line Cords • Specifications •...
  • Page 87 Figure 45: Outlets and amperage Each phase has four 10A outlets and four 16A outlets. For derated, 16A max is available per breaker. Refer to the Specifications for additional information.
  • Page 88 Input Line Cords The following input line cords are for connecting the PDU to appropriate power circuits. This may include for example, the wall or floor outlets to provide power to the PDU. See the 0U PDU Attached line cord and plugs section for a picture of the line cord plug.
  • Page 89: Accessories

    Accessories The following items make up the accessory kit that contains miscellaneous hardware for installing the Rack PDU in a rack cabinet. These are shipped with the PDU. Figure 46: Accessory kit Miscellaneous hardware kit for attaching the PDU to the mounting brackets and installing the PDU in a rack cabinet.
  • Page 90: Racking

    Racking This section discusses mounting for the Lenovo 0U PDU (46M4143) in the back of the Lenovo Standard racks (9307 and 9956), mounting in the back of the Lenovo Enterprise racks (9308 and 1410), and the Lenovo Enterprise rack v2 (9363), and the mounting in Lenovo racks with integrated PDU mounting keyholes (9362, 9361, and 9360).
  • Page 91 Mounting the 0U PDU at the back of an Enterprise Rack Cabinet (9308 and 1410) and the Lenovo Enterprise V2 Rack (9363) requires the use of the two upper and two lower mounting brackets, shipped as part of the PDU accessory kit, see the Accessories section for additional information.
  • Page 92 Mounting In the Back of Lenovo Racks with Integrated PDU Mounting Keyholes (9362, 9361, and 9360) Mounting the 0U PDU at the back of a rack with mounting key holes is displayed in Figure Figure 49: Rack with mounting keyholes at the rear...
  • Page 93: Installation And Maintenance Guide

    Installation and Maintenance Guide The following link is the installation and user guide for the 0U 12 C19 / 12 C13 PDU 46M4143 http://www.ibm.com/support/entry/portal/docdisplay?lndocid=MIGR-5085549...
  • Page 94: 1U Higher Voltage Pdu

    1U Higher Voltage PDU This section discusses the 44T0966 1U Higher Voltage PDU. This section is broken up into the following sections. Quick Specs • Front View and Outlets • Input Line Cords • Specifications • Accessory Kit • Racking •...
  • Page 95 The following figures show the PDU outlets and amperage. Figure 51: Outlets and amperage...
  • Page 96 Input Line Cords The following input line cords are for connecting the PDU to appropriate power circuits. This may include for example, the wall or floor outlets to provide power to the PDU. This PDU will need to be hardwired and has no plug. Refer to the Higher Voltage DC PDU Line cord and hard wiring section for additional information.
  • Page 97: Accessory Kit

    Accessory Kit The following items make up the accessory kit that contains miscellaneous hardware for installing the Rack PDU in a rack cabinet. These are shipped with the PDU. Figure 52: Accessory kit Misc hardware kit also included for attaching PDU to brackets and installing in a rack.
  • Page 98: Racking

    Racking This section discusses mounting for the 44T0966 PDU in the side of a rack, the side pockets of an Enterprise rack (0U space) and EIA (U space) of a rack. Mounting in side pocket Mounting the Higher Voltage DC PDU in the side pocket requires the use of the vertical mounting bracket, shipped as part of the PDU accessory kit, see the Accessory Kit section for additional information.
  • Page 99 Mounting In Lenovo Enterprise Rack (9308 & 1410) & Lenovo Enterprise V2 Rack (9363) Rear Zero Pocket (side pocket) Mounting the 44T0966 PDU in the side pocket of an enterprise rack requires the use of the horizontal mounting bracket, shipped as part of the PDU accessory kit, see the Accessory Kit section for additional information.
  • Page 100 Mounting in EIA (U space) of rack Mounting the 44T0966 PDU in the U space of a rack requires the use of the horizontal mounting bracket, shipped as part of the PDU accessory kit, see the Accessory Kit section for additional information. 1 PDU will fit in 1U of rack space see figure 55.
  • Page 101: Installation And Maintenance Guide

    Installation and Maintenance Guide The following link is the installation and user guide for the 1U Higher Voltage DC PDU 44T0966 http://www-947.Lenovo.com/support/entry/portal/docdisplay?lndocid=migr- 5095319...
  • Page 102: Monitored Pdus

    PDU types explained section. Note: These PDUs can be monitored remotely, but do not have the ability to control the outlets remotely. For Lenovo PDUs that have the ability to control outlets remotely see the Switched and Monitored PDUs section on page...
  • Page 103: Dpi Enterprise Pdu+ C13

    DPI Enterprise PDU+ C13 This section discusses the 39M2816 DPI Enterprise PDU+ C13. This section is broken up into the following sections. Quick Specs • Front and Back View and Outlets • Input Line Cords • Specifications • Accessories kit •...
  • Page 104 PDU 39M2816 + Line Cord 40K9613 Type 63A / 220V-240V Outlets types twelve IEC C13 Power Capacity 14490VA @ 230V Power Limit per PDU 63A Phase Single phase PDU 39M2816 + Line Cord 40K9617 Type 32A / 230V Outlets types six IEC C19 Power Capacity 7360VA @ 230V...
  • Page 105 The 39M2816 has 12 C13 outlets on the front of the PDU. The following figure displays a front and back view picture of the PDU. Figure 56: Front and back panel of the Lenovo DPI Enterprise PDU+ C13 Figure on page...
  • Page 106 Three phase – 39M2816 Figure 57: Outlets and amperage...
  • Page 107: Single Phase - 39M2816

    Single phase – 39M2816 Figure 58: Outlets and amperage...
  • Page 108: Input Line Cords

    32A (32A / Phase) 380-415VAC Three Phase Wye 96A Total Circuit Capacity 39M2816 40K9612 6034 Lenovo DPI IEC 309 P+N+G (4.3m) line cord 32A / 220-240VAC Single Phase 39M2816 40K9613 6035 Lenovo DPI IEC 309 P+N+G (4.3m) line cord...
  • Page 109: Specifications

    Specifications The following table are specifications for the 39M2816 DPI C13 PDU+. Specifications Line cord PN Line cord PN Line cord PN Line cord PN Line cord PN Input Line 40K9611 40K9612 40K9613 40K9617 40K9618 Cord Type* Type 32A/380- 32A / 220- 63A/220V- 32A / 230V 30A / 230V...
  • Page 110: Accessories Kit

    Also included: 1 x EMP (see below), 1 x DB9 to RJ-45 cable, 1 x CAT5 6ft/1.8m cable, cable straps. These accessories are for supporting the racking of the Lenovo DPI Enterprise PDU+ in an Lenovo rack. Some parts may be unused, depending on how and where the PDU is installed. Refer to the...
  • Page 111: Racking

    Racking This section discusses mounting the 39M2816 DPI Enterprise C13 PDU+ in the side of a rack, the side pockets of an Enterprise rack (0U space) and EIA (U space) of a rack. Mounting in side pocket Mounting the 39M2816 DPI Enterprise C13 PDU+ in the side pocket requires the use of the vertical mounting bracket, shipped as part of the PDU accessory kit, see the Accessories kit section for additional information.
  • Page 112 Mounting In Lenovo Enterprise Rack (9308 & 1410) & Lenovo Enterprise V2 Rack (9363) Rear Zero Pocket (side pocket) Mounting the 39M2816 DPI Enterprise C13 PDU+ in the side pocket of an enterprise rack requires the use of the horizontal mounting bracket, shipped as part of the PDU...
  • Page 113 Mounting in EIA (U space) of rack Mounting the 39M2816 DPI Enterprise C13 PDU+ in the U space of a rack requires the use of the horizontal mounting bracket, shipped as part of the PDU accessory kit, see the Accessories kit section for additional information.
  • Page 114: Installation And Maintenance Guide

    Installation and Maintenance Guide The following link is the installation and user guide for the Lenovo DPI Enterprise PDU+ C13 39M2816 ftp://ftp.software.ibm.com/systems/support/system_x_pdf/43v6030.pdf...
  • Page 115: Switched And Monitored Pdus

    Page Number e (ph) (Derated) / Type of Link Outlet^ Lenovo Switched and Monitored PDUs 1U 12 C13 46M4004 1ph 220-240VAC 32A IEC 309 P+N+G 12 / C13 Switched and 63A IEC 309 P+N+G Monitored PDU 230-240VAC 32A AUS/NZ 3112...
  • Page 116: 1U 12 C13 Switched And Monitored Pdu

    1U 12 C13 Switched and Monitored PDU This section discusses the 46M4004 Lenovo 1U 12 C13 Switched and Monitored PDU. This section is broken up into the following sections. Quick Specs • Front and Back View and Outlets • Input Line Cords •...
  • Page 117 PDU 46M4004 + Line Cord 40K9613 Type 63A/220-240V Outlets types twelve IEC C13 Power Capacity 14490VA @ 230V Power Limit per PDU Phase Single phase PDU 46M4004 + Line Cord 40K9617 Type 32A/230V Outlets types twelve IEC C13 Power Capacity 7360VA @ 230V Power Limit per PDU Phase...
  • Page 118 Front and Back View and Outlets The 46M4004 has detachable single phase and three phase line cord options. The following figure displays a front and back view of the PDU. Figure 63: Front and back view Figure on page displays the 1U 12 C13 Switched and Monitored PDU outlets and amperage.
  • Page 119 Three phase – 46M4004...
  • Page 120: Single Phase - 46M4004

    Single phase – 46M4004 Figure 64: Outlets and amperage...
  • Page 121: Input Line Cords

    32A (32A / Phase) 380-415VAC Three Phase Wye 96A Total Circuit Capacity 46M4004 40K9612 5910 Lenovo DPI IEC 309 P+N+G (4.3m) line cord 32A / 220-240VAC Single Phase 46M4004 40K9613 5911 Lenovo DPI IEC 309 P+N+G (4.3m) line cord...
  • Page 122: Specifications

    Specifications The following table are specifications for the 46M4004 C13 Switched and Monitored PDU. Specifications Line cord PN Line cord PN Line cord PN Line cord PN Line cord PN Input Line 40K9611 40K9612 40K9613 40K9617 40K9618 Cord Type* Type 32A/380- 32A / 220- 63A/220V-...
  • Page 123: Accessory Kit

    Accessory Kit These accessories are for supporting the racking of the Lenovo Switched and Monitored C13 PDU in an Lenovo rack. Some parts may be unused, depending on how and where the PDU is installed. Refer to th e Racking section for information on racking the Lenovo C13 PDU.
  • Page 124: Racking

    Racking This section discusses mounting the 46M4004 1U C13 PDU in the side of a rack, the side pockets of an Enterprise rack (0U space) and EIA (U space) of a rack. Mounting in side of a rack Mounting the 46M4004 in the side pocket requires the use of the vertical mounting brackets, shipped as part of the PDU accessory kit, see the Accessory Kit section for...
  • Page 125 Mounting In Lenovo Enterprise Rack (9308 & 1410) & Lenovo Enterprise V2 Rack (9363) Rear Zero Pocket (side pocket) Mounting the 46M4004 in the side pocket of an enterprise rack requires the use of the horizontal mounting bracket, shipped as part of the PDU accessory kit, see the s ection for additional information.
  • Page 126 Mounting in EIA (U space) of rack Mounting the 46M4004 in the U space of a rack requires the use of the 2 horizontal mounting rails and small brackets, shipped as part of the PDU accessory kit, see the Accessory Kit section for additional information.
  • Page 127: Installation And Maintenance Guide

    Installation and Maintenance Guide The following are the Installation and Maintenance manuals for the Lenovo 1U 12 C13 Switched and Monitored PDU. 46M4004 http://www.ibm.com/support/entry/portal/docdisplay?lndocid=MIGR-5084069...
  • Page 128: C19 / 3 C13 Switched And Onitored Pdu

    1U 9 C19 / 3 C13 Switched and Monitored PDU This section discusses the 46M4002 1U 9 C19 / 3 C13 Switched and Monitored PDU. This section is broken up into the following sections. Quick Specs • Front and Back View and Outlets •...
  • Page 129 PDU 46M4002 + Line Cord 40K9617 Type 32A/230V Outlets types nine IEC C19, three IEC C13 Power Capacity 7360VA @ 230V Power Limit per PDU Phase Single phase PDU 46M4002 + Line Cord 40K9618 Type 30A/220V Outlets types nine IEC C19, three IEC C13 Power Capacity 6600VA @ 220V Power Limit per PDU...
  • Page 130 Three phase operation Figure 70: Outlets and amperage Each phase has three IEC C19 and one IEC C13 outlets.
  • Page 131 Single phase operation Figure 71: Outlets and amperage...
  • Page 132 32A (32A / Phase) 380-415VAC Three Phase Wye 96A Total Circuit Capacity 46M4002 40K9612 5903 Lenovo DPI IEC 309 P+N+G (4.3m) line cord 32A / 220-240VAC Single Phase 46M4002 40K9613 5904 Lenovo DPI IEC 309 P+N+G (4.3m) line cord...
  • Page 133 Specifications The following table are specifications for the 46M4002 1U C19/C13 PDU. Specifications Line cord PN Line cord PN Line cord PN Line cord PN Line cord PN Input Line 40K9611 40K9612 40K9613 40K9617 40K9618 Cord Type* Type 32A/380- 32A / 220- 63A/220V- 32A / 230V 30A / 230V...
  • Page 134 Accessory Kit These accessories are for supporting the racking of the Lenovo Switched and Monitored C19/C13 PDU in an Lenovo rack. Some parts may be unused, depending on how and where the PDU is installed. Refer to th e Racking section for information on racking the Lenovo C19/C13 PDU.
  • Page 135 Racking This section discusses mounting the 46M4002 1U C19/C13 PDU in the side of a rack, the side pockets of an Enterprise rack (0U space) and EIA (U space) of a rack. Mounting in side of a rack Mounting the 46M4002 in the side pocket requires the use of the vertical mounting brackets, shipped as part of the PDU accessory kit, see the Accessory Kit section for...
  • Page 136 Mounting In Lenovo Enterprise Rack (9308 & 1410) & Lenovo Enterprise V2 Rack (9363) Rear Zero Pocket (side pocket) Mounting the 46M4002 in the side pocket of an enterprise rack requires the use of the horizontal mounting bracket, shipped as part of the PDU accessory kit, see the s ection for additional information.
  • Page 137 Mounting in EIA (U space) of rack Mounting the 46M4002 in the U space of a rack requires the use of the 2 horizontal mounting rails and small brackets, shipped as part of the PDU accessory kit, see the Accessory Kit section for additional information.
  • Page 138 Installation and Maintenance Guide The following are the Installation and Maintenance manuals for the 1U 9 C19 / 3 C13 Switched and Monitored PDU 46M4002 http://www.ibm.com/support/entry/portal/docdisplay?lndocid=MIGR-5084069...
  • Page 139: Input Line Cords

    0U 24 C13 Switched and Monitored PDU This section discusses the 46M4119 0U 24 C13 Switched and Monitored PDU. This section is broken up into the following sections. Quick Specs • Front View and Outlets • Input Line Cord • Specifications •...
  • Page 140 Figure 77: Outlets and amperage The outlets are broken up into three groups, each group represents a group: A1 – A8, B1 – B8, and C1 – C8.
  • Page 141: Input Line Cord

    Input Line Cord The following input line cord is for connecting the PDU to an appropriate power circuits. This may include for example, the wall or floor outlets to provide power to the PDU. Refer to the 0U PDU Attached line cord and plugs section for a picture of the line cord plugs.
  • Page 142: Accessories

    Accessories The following items make up the accessory kit that contains miscellaneous hardware for installing the Rack PDU in a rack cabinet. These are shipped with the PDU. Figure 78: Accessory kit Also included: 1 x DB9 to RJ-45 cable, and miscellaneous hardware kit for attaching the PDU and installing in a rack cabinet.
  • Page 143: Racking

    Racking This section discusses mounting for all Lenovo 0U PDU in the back of the Lenovo Standard racks (9307 and 9956), mounting in the back of the Lenovo Enterprise racks (9308 and 1410), and the Lenovo Enterprise rack v2 (9363), and the mounting in Lenovo racks with integrated PDU mounting keyholes (9362, 9361, and 9360).
  • Page 144 Mounting the 0U PDUs at the back of an Enterprise Rack Cabinet (9308 and 1410) and the Lenovo Enterprise V2 Rack (9363) requires the use of the two upper and two lower mounting brackets, shipped as part of the PDU accessory kit, see the Accessories section for additional information.
  • Page 145 Mounting In the Back of Lenovo Racks with Integrated PDU Mounting Keyholes (9362, 9361, and 9360) Mounting the 0U PDUs at the back of a rack with mounting key holes is displayed in Figure Figure 81: Rack with mounting keyholes at the rear...
  • Page 146: Installation And Maintenance Guide

    Installation and Maintenance Guide The following are the Installation and Maintenance manuals for the 0U 24 C13 Switched and Monitored PDU 46M4119 http://www.ibm.com/support/entry/portal/docdisplay?lndocid=MIGR-5086798...
  • Page 147: 0U 12 C13 / 12 C19 Switched And Monitored Pdu

    Three Phase Front View and Outlets The 46M4137 Lenovo 0U 12 C13 / 12 C19 Switched and Monitored PDU. This PDU comes with an attached line cord for three phase operation. The following figure displays the front view of the PDU.
  • Page 148 Figure 83: Outlets and amperage Note: Derated 16A MAX available per breaker. The outlets are broken up into 6 groups across 3 phases, A1-A4 and B1-B4 represent phase 1, C1-C4 and D1-D4 represent phase 2, and E1-E4 and F1-F4 represent phase 3. Refer to the Specifications section for additional information.
  • Page 149: Input Line Cord

    Input Line Cord The following input line cord is for connecting the PDU to an appropriate power circuits. This may include for example, the wall or floor outlets to provide power to the PDU. Refer to the 0U PDU Attached line cord and plugs section for a picture of the line cord plug.
  • Page 150: Accessories

    Accessories The following items make up the accessory kit that contains miscellaneous hardware for installing the Rack PDU in a rack cabinet. These are shipped with the PDU. Figure 84: Accessory kit Also included: 1 x DB9 to RJ-45 cable, and miscellaneous hardware kit for attaching the PDU and installing in a rack cabinet.
  • Page 151: Racking

    Racking This section discusses mounting for the Lenovo 0U PDU in the back of the Lenovo Standard racks (9307 and 9956), mounting in the back of the Lenovo Enterprise racks (9308 and 1410), and the Lenovo Enterprise rack v2 (9363), and the mounting in Lenovo racks with integrated PDU mounting keyholes (9362, 9361, and 9360).
  • Page 152 Mounting the 0U PDUs at the back of an Enterprise Rack Cabinet (9308 and 1410) and the Lenovo Enterprise V2 Rack (9363) requires the use of the two upper and two lower mounting brackets, shipped as part of the PDU accessory kit, see the Accessories section for additional information.
  • Page 153: Installation And Maintenance Guide

    Installation and Maintenance Guide The following are the Installation and Maintenance manuals for the Lenovo 0U 12 C13 / 12 C19 Switched and Monitored PDU. 46M4137 http://www.ibm.com/support/entry/portal/docdisplay?lndocid=MIGR-5086798...
  • Page 154: Line Cords And Plugs

    Line Cords and Plugs The following section displays the plugs used on each PDU line cord. The following sections are covered. Universal Rack PDU line cord plugs • Front End PDU Line cord plugs • 1U PDU Detached line cord plugs •...
  • Page 155: 39Y8953 Universal Rack Pdu 230Vac (Denmark/Switz. Iec 309 P+N+G)

    39Y8953 Universal Rack PDU 230VAC (Denmark/Switz. IEC 309 P+N+G) 39M5321 – C19 to Denmark IEC 309 P+N+G (1.8m) @ 230VAC Single Phase 39M5322 – C19 to Denmark IEC 309 P+N+G (2.5m) @ 230VAC Single Phase 39M5323 – C19 to Denmark IEC 309 P+N+G (4.3m) @ 230VAC Single Phase Used with: 39Y8953 –...
  • Page 156: 39Y8955 Universal Rack Pdu 230Vac (Italy Cei 23-16)

    39Y8955 Universal Rack PDU 230VAC (Italy CEI 23-16) 39M5297 – C19 to Italy CEI 23-16 (1.8m) @ 230VAC Single Phase 39M5298 – C19 to Italy CEI 23-16 (2.5m) @ 230VAC Single Phase 39M5299 – C19 to Italy CEI 23-16 (4.3m) @ 230VAC Single Phase Used with: 39Y8955 –...
  • Page 157: 39Y8957 Universal Rack Pdu 230Vac (Uk Bs 1363/A)

    39Y8957 Universal Rack PDU 230VAC (UK BS 1363/A) 39M5293 – C19 to UK BS 1363/A (1.8m) @ 230VAC Single Phase 39M5294 – C19 to UK BS 1363/A (2.5m) @ 230VAC Single Phase 39M5295 – C19 to UK BS 1363/A (4.3m) @ 230VAC Single Phase Used with: 39Y8957 –...
  • Page 158: 39Y8960 Universal Rack Pdu 220-240Vac (Brazil Nbr 14136)

    39Y8960 Universal Rack PDU 220-240VAC (Brazil NBR 14136) 39M5357 – C19 to Brazil NBR 14136 (1.8m) @ 220-240VAC Single Phase 39M5358 – C19 to Brazil NBR 14136 (2.5m) @ 220-240VAC Single Phase 39M5359 – C19 to Brazil NBR 14136 (4.3m) @ 220-240VAC Single Phase Used with: 39Y8960 –...
  • Page 159: 39Y8962 Universal Rack Pdu 220Vac (Argentina Iram 2073)

    39Y8962 Universal Rack PDU 220VAC (Argentina IRAM 2073) 39M5341 – C19 to Argentina IRAM 2073 (1.8m) @ 220VAC Single Phase 39M5342 – C19 to Argentina IRAM 2073 (2.5m) @ 220VAC Single Phase 39M5343 – C19 to Argentina IRAM 2073 (4.3m) @ 220VAC Single Phase Used with: 39Y8962 –...
  • Page 160: Front End Pdu Line Cord Plugs

    Front End PDU Line cord plugs This section covers all the plugs on each line cord for the Front End PDU which includes: 39Y8934 Front End 220-240VAC / 32A Cord (IEC 309 P+N+G) • 39Y8935 Front End 220-240VAC / 63A Cord (IEC 309 P+N+G) •...
  • Page 161 39Y8935 Front End 220-240VAC / 63A Cord (IEC 309 P+N+G) IEC 309 P+N+G (2.5m) - 63A 220- 240VAC Single Phase Only a receptacle or a connector is needed to mate with the plug on the PDU input line cord. See the Additional Plug Information on page in this document for...
  • Page 162 39Y8936 Front End 220VAC / 30A Cord (KSC 8305 30A) P+N+G (Shin Ju P/N SJ-P3302) Korea connector Note: Note that this is not the same cord as the 40K9618 cord. PDU line cord connector pin out is different. Used with: 39Y8936 –...
  • Page 163 39Y8937 Front End 230VAC / 32A Cord (AUS/NZ 3112 32A) P+N+G (PDL P/N 56P332) Australia/New Zealand connector Note: Note that this is not the same cord as the 40K9617 cord. PDU line cord connector pin out is different. Used with: 39Y8937–...
  • Page 164: 1U Pdu Detached Line Cord Plugs

    40K9611 – DPI 32A Cord (IEC 309 3P+N+G) • 40K9612 – DPI 32A Cord (IEC 309 P+N+G) • 40K9613 – Lenovo DPI 63A Cord (IEC 309 P+N+G) • 40K9617 – Lenovo DPI 32A Cord (AUS/NZ 3112 32A) • 40K9618 – DPI 30A Cord (KSC 8305 30A)
  • Page 165 40K9611 – DPI 32A Cord (IEC 309 3P+N+G) IEC-309 3P+N+G (4.3m) 32A, 3P5W plug (Type 532P6W) 32A (32A / Phase) 380-415VAC Three Phase Wye 96A Total Circuit Capacity Only a receptacle or a connector is needed to mate with the plug on the PDU input line cord.
  • Page 166: 40K9612 - Dpi 32A Cord (Iec 309 P+N+G)

    40K9612 – DPI 32A Cord (IEC 309 P+N+G) IEC 309 P+N+G (4.3m) - 32A / 220-240VAC Single Phase Only a receptacle or a connector is needed to mate with the plug on the PDU input line cord. See the Additional Plug Information on page in this document for further details on IEC309.
  • Page 167: 40K9613 - Lenovo Dpi 63A Cord (Iec 309 P+N+G)

    40K9613 – Lenovo DPI 63A Cord (IEC 309 P+N+G) IEC 309 P+N+G (4.3m) - 63A / 220-240VAC Single Phase Only a receptacle or a connector is needed to mate with the plug on the PDU input line cord. See the...
  • Page 168: 40K9617 - Lenovo Dpi 32A Cord (Aus/Nz 3112 32A)

    40K9617 – Lenovo DPI 32A Cord (AUS/NZ 3112 32A) P+N+G (PDL P/N 56P332) Australia/New Zealand connector Used with: Basic PDUs: 39Y8941 – DPI® Enterprise – C13 PDU 39Y8948 – DPI Enterprise – C19 PDU 71762NX – Ultra Density Enterprise PDU...
  • Page 169: 40K9618 - Dpi 30A Cord (Ksc 8305 30A)

    40K9618 – DPI 30A Cord (KSC 8305 30A) P+N+G (Shin Ju P/N SJ-P3302) Korea connector Used with: Basic PDUs: 39Y8941 – DPI® Enterprise – C13 PDU 39Y8948 – DPI Enterprise – C19 PDU 71762NX – Ultra Density Enterprise PDU Monitored PDU: 39M2816 –DPI Enterprise PDU+ C13 71762MX –...
  • Page 170: 0U Pdu Attached Line Cord And Plugs

    0U PDU Attached line cord and plugs This section covers all the plugs on each line cord for the 1U Rack PDUs which include line cords: Attached 16A 3ph Cord (IEC309 3P+N+G) • Attached 32A 1ph Cord (IEC309 P+N+G) • Attached 32A 3ph Cord (IEC309 3P+N+G) •...
  • Page 171 Figure 107: IEC309 3P+N+G 16A plug...
  • Page 172: Attached 32A 1Ph Cord (Iec309 P+N+G)

    Attached 32A 1ph Cord (IEC309 P+N+G) IEC 309 P+N+G 3.0 meter (4.3m) - 32A / 220-240VAC Single Phase Only a receptacle or a connector is needed to mate with the plug on the PDU input line cord. See the Additional Plug Information on page in this document for further details on IEC309.
  • Page 173: Attached 32A 3Ph Cord (Iec309 3P+N+G)

    Attached 32A 3ph Cord (IEC309 3P+N+G) IEC-309 3P+N+G 3.0 meter 32A , 3P5W plug (Type 532P6W) 32A (32A / Phase) 380-415VAC Three Phase Wye 96A Total Circuit Capacity Only a receptacle or a connector is needed to mate with the plug on the PDU input line cord.
  • Page 174: Higher Voltage Dc Pdu Line Cord And Hard Wiring

    Higher Voltage DC PDU Line cord and hard wiring The following section discusses the Higher Voltage DC (HVDC) line cord and hard wiring. HVDC Line cord and plug 90A@240-380VDC cable 4.3 meter Pig-tail termination (hardwired, no plug). Three stranded copper conductors, each with a cross section of 25 sq. mm. Used with: HVDC PDU: 44T0966 –...
  • Page 175: Re-Termination For A/Nz

    Re-termination for A/NZ When using the 40K9611 in Australia or New Zealand, a licensed electrician will be required to re-wire the plug. The IEC-309 3P+N+G will need to be replaced with a Clipsal 5 Round Pin, 32A, Three Phase Wye plug (P/N 56PA532). The following pictures depict the rewired plug on 40K9611 for A/NZ.
  • Page 176: Environmental Monitoring Probe For Monitored Pdus

    The EMP reports the local temperature and humidity values to management tools such as Lenovo Systems Director Active Energy Manager (AEM) or to the PDU web interface. The following image shows an example of the EMP connected to an Lenovo Monitored PDU communication port via a CAT5 cable.
  • Page 177: Emp Shipment Matrix

    Part Number Description 46M4113 Optional Lenovo Environmental Monitoring Probe (EMP) Kit You can install the device anywhere on the rack by using either the screws or the self-adhesive hook-and-loop fasteners. Once attached to the rack, connect the CAT5 cable to the PDU Sensor connector (1U PDU) or the Ethernet connector (0U PDU) as seen below.
  • Page 178: Reference

    For these reasons, if you are running a system with 95W CPUs for example, it is not realistic to provide the rating number as an accurate guide for your systems power load. Use the Lenovo Power Configurator tool to better define your hardware's power draw. The tool is available for download from: http://www.ibm.com/systems/bladecenter/resources/powerconfig.htm...
  • Page 179: Nextscale System Chassis Label Rating

    NeXtScale System Chassis Label Rating The following table represents the label rating numbers for the NeXtScale System Chassis. Chassis Power Power Power 100-127V 200-240V Supply Supplies Supplies Max Rating Rating Wattage Standard n1200 900W 6.8A / 5A / Supply Supply n1200 1300W 6.9A /...
  • Page 180: System X Tower Server Label Rating

    System x Tower Server Label Rating The following table represents the label rating numbers for System x Tower Servers. Server Power Power Server Ratings Redundant Supply Supplies Wattag 100-127V Standar Max 100- 200- 220- 127V 208V 240V x3100 x3100 (4348) 310W 4.5A 2.25A...
  • Page 181 x3400 x3400 (7973, 670W 2.5A 7974) x3400 (7975, 835W 6.5A 3.25A 7976) x3400 M2 (7836, 670W 7837) x3400 M2 (7836, 920W 7837) x3400 M3 (7378, 670W 7379) Server Power Power Server Ratings Redundant Supply Supplies Wattag 100-127V Standar Max 100- 200- 220- 127V...
  • Page 182: System X Rack Server Label Rating

    System x Rack Server Label Rating The following table represents the label rating numbers for System x Rack Servers. Server Power Power Server Ratings Redundant Supply Supplies Wattag 100-127V Standar Max 100- 200- 220- 127V 208V 240V x3250 x3250 (4364, 350W 4365) x3250 M2 (4190,...
  • Page 183 x3620 x3620 M3 (7376) 460W 5.3A 2.6A x3620 M3 (7376) 675W 7.8A 3.8A x3630 x3630 M3 (7377) 675W 7.8A 3.8A Server Power Power Server Ratings Redundant Supply Supplies Wattag 100-127V Standar Max 100- 200- 220- 127V 208V 240V x3630 M4 (7158) 550W 6.5A 3.3A x3630 M4 (7158) 750W...
  • Page 184 x3690 X5 (7147, 675W 7148) Server Rating 15.6A 7.6A Power Supply Rating (per plug) 7.8A 3.8A x3750 x3750 M4 (8722) 900W x3750 M4 (8722) 1400W 1 x3755 x3755 (8877, 1500W 1 17.6A 8.8A 7163) x3755 M3 (7164) 1100W 1 6.7A x3755 M3 (7164) 1100W 2 Server Rating 11.6A...
  • Page 185: Ds Storage Label Rating

    DS Storage Label Rating The following table represents the label rating numbers for the DS Storage Units. Storage Power Supply 100-127V Rating 200-240V Rating Device Wattage DS3200 515W 3.9A 1.95A DS3300 515W 3.9A 1.95A DS3400 515W 3.9A 1.95A DS3512 385W 3.8A 1.9A DS3524...
  • Page 186: Storwize Label Rating

    Storwize Label Rating The following table represents the label rating numbers for the Storwize Storage Units. Storage Device Power Supply 100-127V Rating 200-240V Wattage Rating Storwize V3500 735W 3.93A 1.96A Storwize V3700 735W 3.93A 1.96A Storwize V3700 DC 800W 9.89A 4.89A Storwize V3700 EXP 735W...
  • Page 187: Idataplex Chassis Label Rating

    iDataPlex Chassis Label Rating The following table represents the label rating numbers for the Storwize Storage Units. Chassis Slot Power Supply Number of Power Chassis Rating Configuration Wattage Supplies Standard Max 2U Flex Chassis 2 Planars 900W High 100V – 8.62A (7831, 6385) Efficiency 110V –...
  • Page 188 Chassis Slot Power Supply Number of Power Chassis Configuration Wattage Supplies Rating Standard 3U Storage 900W High 100V – 7.61A Chassis Efficiency 110V – 6.90A (7834, 6386) 115V – 6.52A 120V – 6.28A 127V – 5.90A 200V – 3.73A 208V – 3.59A 220V –...
  • Page 189: System X Top Of Rack (Tor) Ethernet Switch Label Rating

    2.75A 1.25A IEC320 C14 Lenovo G8264 750W 3.75A 1.875A IEC320 C14 Lenovo G8316 750W 3.95A 1.95A IEC320 C14 Lenovo J48E (4273- 320W 3.75A 2.0A IEC320 C14 48E) Lenovo J48E (4273- 600W 6.75A 3.25A IEC320 C14 48E) Lenovo J48E (4273- 930W 5.5A...
  • Page 190: Xseries Server Label Rating

    Server Label Rating The following table represents the label rating numbers for Lenovo xSeries Servers. Server Power Power Server Ratings Redundant Supply Supplies Wattage 100-127V Standard Max 100- 200- 220- 127V 208V 240V x100 310W 4.5A 2.25A x206 400W 5.5A...
  • Page 191: Additional Plug Information

    Additional Plug Information The following section discusses more details on the PDU plugs. IEC 320 Connectors The following table displays the plug types for different hardware such as monitors, switches, servers, high-end servers, power distribution units (PDUs), and Uninterruptable Power Supplies (UPSs). Name Amp Rating (A) Connector...
  • Page 192: Rong Fend Rf-203P Connector

    Rong Fend RF-203P Connector The following table displays the plug type for the Higher Voltage DC PDU. Name Connector AMP Rating For systems requiring DC power from a DC RF-203P 10/15A power source. IEC 309 Plug Sleeve Ratings The color of the sleeve around a plug indicates its voltage rating. The colors and ratings are listed below.
  • Page 193: Iec 309 Pin Decode

    IEC 309 Pin Decode The following table is a break down of the Hubbell (HBL) part number.
  • Page 196 The numbers and letters circled in red below is an example HBL part number: HBL460R9W. The P/N: HBL460R9W plug description is listed below: HBL460R9W = 4 pin (3ph), 60A, Receptacle, 9 ground (G) clock face pin position, Watertight. Note: The number of pins indicates the phase: 3 pins = 1ph, 4 pins = 3ph and 5 pins Δ, = 3 ph Y...
  • Page 197: Ingress Protection (Ip) Decode

    Ingress Protection (IP) Decode Example: IP67 = Ingress Protection / Dust-Tight / Temporary Immersion Three Phase Power Calculation Diagrams The following figures explain three phase power values for various amperage. 60A Three Phase Delta Power Calculations...
  • Page 198: 30A Three Phase Delta Power Calculations

    50A Three Phase Delta Power Calculations 30A Three Phase Delta Power Calculations...
  • Page 199: 32A Three Phase Delta Power Calculations

    32A Three Phase Delta Power Calculations 16A Three Phase Delta Power Calculations...
  • Page 200 Support...
  • Page 201 Hubbell - Pin & Sleeve Plug/Outlet Catalog (Includes IEC309 Outlets) http://www.hubbellcatalog.com/wiring/catalogpages/section-E.pdf Configuration and Options Guide (COG) – System x, BladeCenter, Flex System, and NeXtScale System http://www.ibm.com/support/entry/portal/docdisplay? brand=5000008&lndocid=SCOD-3ZVQ5W Lenovo BladeCenter and System x Reference Sheets http://www.redbooks.Lenovo.com/abstracts/redpxref.html Official Lenovo Visio Stencils http://www.visiocafe.com/Lenovo.htm...