1u c19 and c13 switched and monitored pdus (86 pages)
Summary of Contents for Lenovo System x PDU
Page 1
System x PDU Technical Reference – International v3.0.2 BASIC PDUS MONITORED PDUS SWITCHED & MONITORED PDUS Lenovo basic Power Lenovo switched Power Lenovo switched and Distribution Units (PDUs) Distribution Units (PDU) monitored Power provide an economical, basic provides outlet dense advanced...
Page 2
Authors Rani Doughty rdoughty@lenovo.com Matthew Archibald marchibald@lenovo.com Questions / Comments: power@lenovo.com Data Center Services, Enterprise Business Group Revision History 1.0 – July 15, 2009 Initial Release. First published by William S Champion. 1.2.0 – February 17, 2010 Corrected Ultra Density PDU part numbers, update server label ratings.
Table of Contents INTRODUCTION..........................7 ...........................7 OW TO USE THIS GUIDE ..........................8 TYPES EXPLAINED Basic PDUs (non-Monitored)..................8 Monitored PDUs.....................8 Switched and Monitored PDUs................8 ..........................9 UMMARY OF ..........................13 PLUGS ..........................14 IRCUIT APACITIES BASIC PDUS (NON-MONITORED)....................15 PDU...........................18 NIVERSAL Quick Specs......................18 Front View and Outlets..................21 Input Line Cords....................22 Specifications –...
Page 4
Quick Specs......................64 Front and Back View and Outlets.................66 Input Line Cords....................69 Specifications.......................70 Accessory Kit......................72 Racking.........................74 Installation and Maintenance Guide..............78 0U 24 C13 PDU..........................79 Quick Specs......................79 Front View and Outlets..................80 Input Line Cords....................82 Specifications.......................82 Accessories......................84 Racking.........................86 Installation and Maintenance Guide..............89 0U 12 C19 / 12 C13 PDU........................90 Quick Specs......................90 Front View and Outlets..................90 Input Line Cords....................92...
Page 5
Single phase – 46M4004 ..................126 Input Line Cords....................127 Specifications.....................128 Accessory Kit......................129 Racking.......................131 Installation and Maintenance Guide..............134 1U 9 C19 / 3 C13 S PDU................135 WITCHED AND ONITORED Quick Specs......................135 Front and Back View and Outlets...............137 Input Line Cords....................140 Specifications.....................141 Accessory Kit......................143 Racking.......................145 Installation and Maintenance Guide..............148 0U 24 C13 S...
Introduction Only Lenovo System x Power Distribution Units (PDUs) that are currently marketed Internationally are included in this guide. The intent of this guide is to provide PDU information needed in planning power requirements. This guide is best used in softcopy form, since it contains hyperlinks for navigation.
Lenovo Systems Director, Active Energy Manager (AEM). A monitored PDU has the ability to control the outlets remotely (switch individual outlets on/off) via the PDUs web interface or via Lenovo Active Energy Manager (AEM). All monitored (and switched and monitored) PDUs collect the below data at a PDU...
Summary of PDUs This section is a quick summary and links to all of the available PDUs Internationally. Basic PDUs Option Phase Voltage (V) Line Cord Number Page Number (ph) (Derated) / Type Link Outlet Universal 39Y8952 1ph 230VAC 16A CEE7-VII Europe 7 / C13 Rack PDU*...
Page 11
Basic PDUs Continued Option Phase Voltage Line Cord Number Number (ph) (Derated) / Type of Outlet Link Ultra Density 71762NX 1ph 220- 32A IEC 309 P+N+G 9 / C19 Enterprise 240VAC 3 / C13 63A IEC 309 P+N+G 230- 32A AUS/NZ 3112 240VAC 220VAC 30A KSC 8305...
Page 12
Monitored PDUs Option Phase Voltage (V) Line Cord Number Page Number (ph) (Derated) / Type of Link Outlet 39M2816 220- 32A IEC 309 P+N+G 12 / C13 Enterprise 240VAC 63A IEC 309 P+N+G PDU+ C13 230- 32A AUS/NZ 3112 240VAC 220VAC 30A KSC 8305...
Page 13
Switched and Monitored PDUs Option Phase Voltage Line Cord Number / Page Number (ph) (Derated) Type of Link Outlet 1U 12 C13 46M4004 1ph 220- 32A IEC 309 P+N+G 12 / C13 240VAC Switched and 63A IEC 309 P+N+G Monitored 230- 32A AUS/NZ 3112 240VAC...
C13 to C14 plugs. These plugs are used for the following: Lenovo NeXtScale chassis's., • Lenovo System x Rack servers, • Lenovo System x Tower servers, and • Lenovo BladeCenter S (model dependent) • Hardware Figure 1: C13 to C14 plugs Figure s hows the C19 to C20 plugs.
Circuit Capacities The following table represents the derated values/Watt capacities for power circuits running between 13A-63A@100V-415V for both single phase and three phase electrical circuits. Branch Circuit Rating Volt-ampere (VA) 13A / 230V 1ph 2990VA 15A / 230V 1ph 3450VA 15A/ 240V 1ph 3600VA 16A/ 220V 1ph...
Basic PDUs (non-Monitored) The following section provides information and part numbering for Basic PDUs. Click on the description of each PDU to read more information. Option Phase Voltage Line Cord Number Page Number (ph) (Derated) / Type Link Outlet* Universal Rack 39Y8952 1ph 230VAC 16A CEE7-VII Europe...
Universal Rack PDU This section discusses the Lenovo Universal Rack PDU. This section is broken up into the following sections. Quick Specs • Front View and Outlets • Input Line Cords • Specifications – Asia Pacific • Accessory Kit •...
Page 19
PDU 39Y8957 + Line Cord 4.3m BS 1363/A (HK/UK) Outlets types Seven IEC C13 Type 13A/230V Power Capacity 2990VA @ 230V Power Limit per PDU 15A (line cord 13A) Phase Single phase PDU 39Y8958 + Line Cord 4.3m AS/NZ 3112 (Aust/NZ) Outlets types Seven IEC C13 Type...
Page 20
PDU 39Y8962 + Line Cord 4.3m IRAM 2037 (Argentina) Outlets types Seven IEC C13 Type 16A/220V Power Capacity 3520VA @ 220V Power Limit per PDU Phase Single phase PDU 39Y8953 + Line Cord 4.3m IEC 309 P+N+G (Denmark/Switzerland) Outlets types Seven IEC C13 Type 16A/230V...
Page 21
All PDUs + Line Cord IEC320 C19 to C20 Outlets types Seven IEC C13 Type 16A/100-250VAC Power Capacity 3200VA @ 200V Power Limit per PDU Phase Single phase...
Page 22
Front View and Outlets Figure displays a front view of the DPI Universal Rack PDU. Figure 3: Front view of the DPI Universal PDU Figure displays the outlet numbering and amperage of the DPI Universal Rack PDU. The PDU has a 15A internal breaker and C13 outlets. See the Specifications –...
Page 23
Input Line Cords The following input line cords are for connecting the PDU to appropriate power circuits. This may include for example, the wall or floor outlets to provide power to the PDU. See the Universal Rack PDU line cord plugs section for pictures of the plugs.
Page 24
Specifications – Asia Pacific The following table are specifications for the Universal Rack PDU for AP. Asia Pacific - Universal Rack PDU – Specifications Input Line Cord* to PDU or Aus/NZ Honk Kong / Taiwan China (US LV) Outlets types seven IEC seven IEC seven IEC...
Specifications – EMEA The following table are specifications for the Universal Rack PDU for EMEA. EMEA – Universal Rack PDU – Specifications Input Line to PDU or UPS 16A/230V United Kingdom Saudi Arabia (US Cord* Outlets types seven IEC C13 seven IEC seven IEC C13 seven IEC C13...
Accessory Kit The following items make up the accessory kit that contains miscellaneous hardware for installing the Rack PDU in a rack cabinet. These are shipped with the PDUs. Figure 5: Accessory kit These accessories are for supporting the racking of the DPI PDUs in either the side pocket of a rack or U space of a rack.
Racking This section discusses mounting the DPI PDU in the side pockets of a rack and EIA (U space) of a rack. Mounting in side pocket Mounting the DPI PDUs in the side pocket requires the use of the small vertical mounting plate, shipped as part of the PDU accessory kit, see the Accessory Kit section for additional information.
Page 28
Mounting In Lenovo Enterprise Rack (9308 & 1410) & Lenovo Enterprise V2 Rack (9363) Rear Zero Pocket Mounting the DPI PDU (39Y8951) in the side pocket of an enterprise rack requires the use of the horizontal mounting bracket, shipped as part of the PDU accessory kit,...
Page 29
Mounting in EIA (U space) of rack Mounting the DPI PDU (39Y8951) in the U space of a rack requires the use of the horizontal mounting bracket, shipped as part of the PDU accessory kit, see the Accessory Kit section for additional information. Two PDUs will fit in 1U of rack space as seen in figure 8.
Installation and Maintenance Guide The following link is the installation and maintenance guide for the Lenovo Universal Rack PDU: ftp://ftp.software.ibm.com/systems/support/system_x_pdf/02r2738.pdf...
Racking • Installation and Maintenance Guide • Quick Specs The following tables are quick overviews of the Lenovo Front End PDUs. For additional information refer to the Specifications section. PDU 39Y8934 + Included Line Cord IEC 309 P+N+G Outlet Types...
Page 32
PDU 39Y8936 + Included Line Cord KSC 8305 Outlet Types three IEC C19 Type 30A/220V Power Capacity 6600VA @ 220V Power Limit per PDU Phase Single phase PDU 39Y8937 + Included Line Cord AS/NZS 3112 Outlet Types three IEC C19 Type 32A/230V Power Capacity...
Front and Back View and Outlets Figure displays the front and back view of the Front End PDU. Figure displays the outlets and amperage. Figure 9: Front and back view of the FE PDU Figure 11: Internal outlet and amperage Figure 10: Outlets and amperage...
Specifications The following table are specifications for the 39Y8934, 39Y8935, 39Y8936, and 39Y8937 Front End PDUs. Specifications PDU Part Number 39Y8934 39Y8935 39Y8936 39Y8937 PDU Feature A11V A11W A11Y A11X Code* Type 32A/220- 63A/220-240V 30A/220V 32A/230V 240V Phase Single Single Single Single Outlets types...
Accessory Kit The following is miscellaneous hardware for installing the Rack PDU in a rack cabinet. The large vertical mounting bracket is shipped standard with the PDU. Figure 12: Accessory kit Miscellaneous hardware kit also included for attaching the front-end PDU to the a mounting plate and installing in a rack cabinet.
Racking This section discusses mounting the Front-end PDUs (39Y8934, 39Y8935, 39Y8936, and 39Y8937) in the side pockets of a rack and EIA (U space) of a rack. Mounting in side pocket of rack Mounting the Front-end PDUs (39Y8934, 39Y8935, 39Y8936, and 39Y8937) in the side pocket requires the use of the large vertical mounting plate, shipped as part of the PDU accessory kit, see the Accessory Kit...
Page 38
Mounting In Lenovo Enterprise Rack (9308 & 1410) & Lenovo Enterprise V2 Rack (9363) Rear Zero Pocket Mounting the Front-end PDUs (39Y8934, 39Y8935, 39Y8936, and 39Y8937) in the side pocket of an Enterprise rack, requires the use of the large vertical mounting...
Page 39
Option 2 Mounting the Front-end PDUs (39Y8934, 39Y8935, 39Y8936, and 39Y8937) in the side pocket of an Enterprise rack, requires the use of the large vertical mounting plate, shipped as part of the PDU accessory kit, see the Accessory Kit section for additional information.
Page 40
Mounting in side pocket Mounting the Front-end PDUs (39Y8934, 39Y8935, 39Y8936, and 39Y8937) in 1U space of the rack requires a horizontal mounting plate. Note: The Front-end PDU is only shipped with the large vertical wall mounting plate. The PDU can be mounted in a 1U horizontal space of the rack if you have rack PDU hardware to mount it in.
Installation and Maintenance Guide The following link is the installation and maintenance guide for the Lenovo Front End PDU: 39Y8934, 39Y8935, 39Y8936, and 39Y8937 ftp://ftp.software.ibm.com/systems/support/system_x_pdf/02r2739.pdf...
DPI® Enterprise – C13 PDU This section discusses the 39Y8941 DPI C13 PDU. This section is broken up into the following sections. Quick Specs • Front View and Outlets • Input Line Cords • Specifications • Accessory Kit • Racking •...
Page 43
PDU 39Y8941 + Line Cord 40K9613 Type 63A/220-240V Outlets types twelve IEC C13 Power Capacity 14490VA @ 230V Power Limit per PDU Phase Single phase PDU 39Y8941 + Line Cord 40K9617 Type 32A/230V Outlets types twelve IEC C13 Power Capacity 7360VA @ 230V Power Limit per PDU Phase...
Page 44
Front View and Outlets Figure displays a front view of the 39Y8941 PDU. Figure 17: Front and back view of the DPI Enterprise C13 PDU Single phase 39Y8941PDU Figure 18: Outlets and amperage...
Page 45
Three phase 39Y8941 PDU Figure 19: Outlet and amperage...
Page 46
32A (32A / Phase) 380-415VAC Three Phase Wye 96A Total Circuit Capacity 39Y8941 40K9612 6014 Lenovo DPI IEC 309 P+N+G (4.3m) line cord 32A / 220-240VAC Single Phase 39Y8941 40K9613 6015 Lenovo DPI IEC 309 P+N+G (4.3m) line cord...
Page 47
Specifications The following table are specifications for the 39Y8941 DPI C13 PDU. Specifications Line cord PN Line cord PN Line cord PN Line cord PN Line cord PN Input Line 40K9611 40K9612 40K9613 40K9617 40K9618 Cord Type* Type 32A/380- 32A / 220- 63A/220V- 32A / 230V 30A / 230V...
Page 48
Accessory Kit The following items make up the accessory kit that contains miscellaneous hardware for installing the Rack PDU in a rack cabinet. These are shipped with the PDU. Figure 20: Accessory kit Miscellaneous hardware kit for attaching the mounting brackets to the PDU and installing in a rack, and cable straps are also included.
Page 49
Racking This section discusses mounting the DPI C13 (39Y8941) in the side of a rack, the side pockets of a rack and EIA (U space) of a rack. Mounting in side pocket Mounting the DPI C13 PDUs in the side pocket requires the use of the vertical mounting bracket, shipped as part of the PDU accessory kit, see the Accessory Kit section for additional information.
Page 50
Mounting In Lenovo Enterprise Rack (9308 & 1410) & Lenovo Enterprise V2 Rack (9363) Rear Zero Pocket (side pocket) Mounting the DPI PDUs (39Y8941) in the side pocket of an enterprise rack requires the use of the horizontal mounting bracket, shipped as part of the PDU accessory kit,...
Page 51
Mounting in EIA (U space) of rack Mounting the DPI C13 PDUs (39Y8941) in the U space of a rack requires the use of the horizontal mounting bracket, shipped as part of the PDU accessory kit, see the Accessory Kit section for additional information.
Page 52
Installation and Maintenance Guide The following link is the installation and maintenance guide for the Lenovo DPI Enterprise – C13 PDU 39Y8941 ftp://ftp.software.ibm.com/systems/support/system_x_pdf/43v6030.pdf...
DPI Enterprise – C19 PDU This section discusses the 39Y8948 DPI Enterprise C19 PDU. This section is broken up into the following sections. Quick Specs • Front View and Outlets • Input Line Cords • Specifications • Accessory Kit • Racking •...
Page 54
PDU 39Y8948 + Line Cord 40K9613 Type 63A / 220V-240V Outlets types six IEC C19 Power Capacity 14490VA @ 230V Power Limit per PDU Phase Single phase PDU 39Y8948 + Line Cord 40K9617 Type 32A / 230V Outlets types six IEC C19 Power Capacity 7360VA @ 230V Power Limit per PDU...
Page 55
Front View and Outlets The 39Y8948 PDU has 5 optional line cords for use in different regions. The following figure displays a front view picture of the PDU. Figure 24: Front panel of the DPI Enterprise C19 PDU Figure shows the 39Y8948 PDU outlets and amperage.
Page 56
Outlet and amperage for the three and single phase 39Y8941 PDU. Figure 25: Lenovo DPI C19 PDU outlet and breaker amperage Note: Derated 16A MAX available per breaker/group.
Page 57
Lenovo DPI IEC-309 3P+N+G (4.3m) line cord 32A (32A / Phase) 380-415VAC Three Phase Wye 96A Total Circuit Capacity 39Y8948 40K9612 6064 Lenovo DPI IEC 309 P+N+G (4.3m) line cord 32A / 220-240VAC Single Phase 39Y8948 40K9613 6065 Lenovo DPI IEC 309 P+N+G (4.3m) line cord...
Page 58
Specifications The following table are specifications for the 39Y8948 DPI C19 PDU. Specifications Line cord PN Line cord PN Line cord PN Line cord PN Line cord PN Input Line 40K9611 40K9612 40K9613 40K9617 40K9618 Cord Type* Type 32A/380- 32A / 220- 63A/220V- 32A / 230V 30A / 230V...
Page 59
Accessory Kit The following items make up the accessory kit that contains miscellaneous hardware for installing the Rack PDU in a rack cabinet. These are shipped with the PDU. Figure 26: Accessory kit Miscellaneous hardware kit for attaching the mounting brackets to the PDU and installing in a rack, and cable straps are also included.
Page 60
Racking This section discusses mounting the DPI C19 (39Y8948) in the side of a rack, the side pockets of a rack and EIA (U space) of a rack. Mounting in side pocket Mounting the DPI C19 PDU in the side pocket requires the use of the vertical mounting bracket, shipped as part of the PDU accessory kit, see the Accessory Kit section for additional information.
Page 61
Mounting In Lenovo Enterprise Rack (9308 & 1410) & Lenovo Enterprise V2 Rack (9363) Rear Zero Pocket (side pocket) Mounting the DPI PDU (39Y8948) in the side pocket of an enterprise rack requires the use of the horizontal mounting bracket, shipped as part of the PDU accessory kit,...
Page 62
Mounting in EIA (U space) of rack Mounting the DPI C19 PDU (39Y8948) in the U space of a rack requires the use of the horizontal mounting bracket, shipped as part of the PDU accessory kit, see the Accessory Kit section for additional information.
Page 63
Installation and Maintenance Guide The following link is the installation and maintenance guide for the Lenovo DPI Enterprise – C19 PDU 39Y8948 ftp://ftp.software.ibm.com/systems/support/system_x_pdf/43v6030.pdf...
Ultra Density Enterprise PDU This section discusses the 71762NX Ultra Density Enterprise C19/C13 PDU. This section is broken up into the following sections. Quick Specs • Front and Back View and Outlets • Input Line Cords • Specifications • Accessory Kit •...
Page 65
PDU 71762NX + Line Cord 40K9613 Type 63A / 220V-240V Outlets types Nine IEC C19, and three IEC C13 Power Capacity 14490VA @ 230V Power Limit per PDU 63A Phase Single phase PDU 71762NX + Line Cord 40K9617 Type 32A / 230V Outlets types Nine IEC C19, and three IEC C13 Power Capacity...
Page 66
Front and Back View and Outlets The 71762NX has detachable single phase line cord options and three phase option. The following figures displays a front and back view of the PDU. Figure 30: Front and back panels of the Ultra Density Enterprise C19 PDU The following figures show the PDUs outlets and amperage for single phase and three phase.
Page 67
Three phase 71762NX PDU Figure 31: Outlets and amperage...
Page 68
Single phase model 71762NX PDU Figure 32: Outlets and amperage...
Page 69
32A (32A / Phase) 380-415VAC Three Phase Wye 96A Total Circuit Capacity 71762NX 40K9612 6502 Lenovo DPI IEC 309 P+N+G (4.3m) line cord 32A / 220-240VAC Single Phase 71762NX 40K9613 6503 Lenovo DPI IEC 309 P+N+G (4.3m) line cord...
Page 70
Specifications The following table are specifications for 71762NX DPI Ultra Density Enterprise PDU. Specifications Line cord PN Line cord PN Line cord PN Line cord PN Line cord PN Input Line 40K9611 40K9612 40K9613 40K9617 40K9618 Cord Type* Type 32A/380- 32A / 220- 63A/220V- 32A / 230V...
Accessory Kit The following items make up the accessory kit that contains miscellaneous hardware for installing the Rack PDU in a rack cabinet. These are shipped with the PDU. Figure 33: Accessory kit Misc hardware kit also included for attaching PDU to brackets and installing in a rack.
Racking This section discusses mounting for the 71762NX Ultra Density C19/C13 PDU in the side of a rack, the side pockets of an Enterprise rack (0U space) and EIA (U space) of a rack. Mounting in side pocket Mounting the Ultra Density C19/C13 PDU in the side pocket requires the use of the vertical mounting bracket, shipped as part of the PDU accessory kit, see the Accessory Kit section for additional information.
Page 73
Mounting In Lenovo Enterprise Rack (9308 & 1410) & Lenovo Enterprise V2 Rack (9363) Rear Zero Pocket (side pocket) Mounting the 71762NX Ultra Density C19/C13 PDU in the side pocket of an enterprise rack requires the use of the horizontal mounting bracket, shipped as part...
Page 74
Mounting in EIA (U space) of rack Mounting the 71762NX Ultra Density C19/C13 PDU in the U space of a rack requires the use of the horizontal mounting bracket, shipped as part of the PDU accessory kit, see the Accessory Kit section for additional information.
Installation and Maintenance Guide The following link is the installation and user guide for the Lenovo Ultra Density Enterprise PDU 71762NX http://www.ibm.com/support/entry/portal/docdisplay?lndocid=MIGR-5076527...
0U 24 C13 PDU This section discusses the 46M4131 and 46M4122 0U 24 C13 PDU. This section is broken up into the following sections. Quick Specs • Front View and Outlets • Input Line Cords • Specifications • Accessories • Racking •...
Page 77
Front View and Outlets There are 2 type of 0U 24 C13 PDU's. The 46M4122 and 46M4131. The PDUs are identical except for the line cord. The line cord determines single phase or three phase operation. The 46M4131 has an attached single phase line cord. The 46M4122 has an attached 3 phase line cord.
Page 78
Three phase 46M4122 PDU Figure 39: Outlets and amperage Each phase has eight 10A outlets. For derated, 16A max is available per breaker. Refer to the Specifications for additional information.
Page 79
Input Line Cords The following input line cords are for connecting the PDU to appropriate power circuits. This may include for example, the wall or floor outlets to provide power to the PDU. See page 0U PDU Attached line cord and plugs for a picture of the line cord plugs.
Page 80
Specifications The following table are specifications for the 46M4131 and 46M4122 0U C13 PDUs. Specifications PDU Part Number 46M4131 46M4122 Feature Code 5925 5922 Input Line Cord Attached Attached Type* Phase Single phase Three phase Type 32A / 220V-240V 16A / 220V-240V Outlets types twenty four IEC C13 twenty four IEC C13...
Accessories The following items make up the accessory kit that contains miscellaneous hardware for installing the Rack PDU in a rack cabinet. These are shipped with the PDU. Figure 40: Accessory kit for PDUs 46M4128, 46M4125, and 46M4140 Miscellaneous hard ware kit for attaching the mounting brackets to the PDU and installing in a rack cabinet.
Racking This section discusses mounting for the Lenovo 0U PDUs in the back of the Lenovo Standard racks (9307 and 9956), mounting in the back of the Lenovo Enterprise racks (9308 and 1410), and the Lenovo Enterprise rack v2 (9363), and the mounting in Lenovo racks with integrated PDU mounting keyholes (9362, 9361, and 9360).
Page 83
Mounting the 0U PDUs at the back of an Enterprise Rack Cabinet (9308 and 1410) and the Lenovo Enterprise V2 Rack (9363) requires the use of the two upper and two lower mounting brackets, shipped as part of the PDU accessory kit, see the Accessories section for additional information.
Page 84
Mounting In the Back of Lenovo Racks with Integrated PDU Mounting Keyholes (9362, 9361, and 9360) Mounting the 0U PDUs at the back of a rack with mounting key holes is displayed in Figure Figure 43: Rack with mounting keyholes at the rear...
Installation and Maintenance Guide The following link is the installation and user guide for the Lenovo 0U 24 C13 PDU 46M4122, and 46M4131 http://www.ibm.com/support/entry/portal/docdisplay?lndocid=MIGR-5085549...
0U 12 C19 / 12 C13 PDU This section discusses the 46M4143 0U 12 C19 / 12 C13 PDU. This section is broken up into the following sections. Quick Specs • Front View and Outlets • Input Line Cords • Specifications •...
Page 87
Figure 45: Outlets and amperage Each phase has four 10A outlets and four 16A outlets. For derated, 16A max is available per breaker. Refer to the Specifications for additional information.
Page 88
Input Line Cords The following input line cords are for connecting the PDU to appropriate power circuits. This may include for example, the wall or floor outlets to provide power to the PDU. See the 0U PDU Attached line cord and plugs section for a picture of the line cord plug.
Accessories The following items make up the accessory kit that contains miscellaneous hardware for installing the Rack PDU in a rack cabinet. These are shipped with the PDU. Figure 46: Accessory kit Miscellaneous hardware kit for attaching the PDU to the mounting brackets and installing the PDU in a rack cabinet.
Racking This section discusses mounting for the Lenovo 0U PDU (46M4143) in the back of the Lenovo Standard racks (9307 and 9956), mounting in the back of the Lenovo Enterprise racks (9308 and 1410), and the Lenovo Enterprise rack v2 (9363), and the mounting in Lenovo racks with integrated PDU mounting keyholes (9362, 9361, and 9360).
Page 91
Mounting the 0U PDU at the back of an Enterprise Rack Cabinet (9308 and 1410) and the Lenovo Enterprise V2 Rack (9363) requires the use of the two upper and two lower mounting brackets, shipped as part of the PDU accessory kit, see the Accessories section for additional information.
Page 92
Mounting In the Back of Lenovo Racks with Integrated PDU Mounting Keyholes (9362, 9361, and 9360) Mounting the 0U PDU at the back of a rack with mounting key holes is displayed in Figure Figure 49: Rack with mounting keyholes at the rear...
Installation and Maintenance Guide The following link is the installation and user guide for the 0U 12 C19 / 12 C13 PDU 46M4143 http://www.ibm.com/support/entry/portal/docdisplay?lndocid=MIGR-5085549...
1U Higher Voltage PDU This section discusses the 44T0966 1U Higher Voltage PDU. This section is broken up into the following sections. Quick Specs • Front View and Outlets • Input Line Cords • Specifications • Accessory Kit • Racking •...
Page 95
The following figures show the PDU outlets and amperage. Figure 51: Outlets and amperage...
Page 96
Input Line Cords The following input line cords are for connecting the PDU to appropriate power circuits. This may include for example, the wall or floor outlets to provide power to the PDU. This PDU will need to be hardwired and has no plug. Refer to the Higher Voltage DC PDU Line cord and hard wiring section for additional information.
Accessory Kit The following items make up the accessory kit that contains miscellaneous hardware for installing the Rack PDU in a rack cabinet. These are shipped with the PDU. Figure 52: Accessory kit Misc hardware kit also included for attaching PDU to brackets and installing in a rack.
Racking This section discusses mounting for the 44T0966 PDU in the side of a rack, the side pockets of an Enterprise rack (0U space) and EIA (U space) of a rack. Mounting in side pocket Mounting the Higher Voltage DC PDU in the side pocket requires the use of the vertical mounting bracket, shipped as part of the PDU accessory kit, see the Accessory Kit section for additional information.
Page 99
Mounting In Lenovo Enterprise Rack (9308 & 1410) & Lenovo Enterprise V2 Rack (9363) Rear Zero Pocket (side pocket) Mounting the 44T0966 PDU in the side pocket of an enterprise rack requires the use of the horizontal mounting bracket, shipped as part of the PDU accessory kit, see the Accessory Kit section for additional information.
Page 100
Mounting in EIA (U space) of rack Mounting the 44T0966 PDU in the U space of a rack requires the use of the horizontal mounting bracket, shipped as part of the PDU accessory kit, see the Accessory Kit section for additional information. 1 PDU will fit in 1U of rack space see figure 55.
Installation and Maintenance Guide The following link is the installation and user guide for the 1U Higher Voltage DC PDU 44T0966 http://www-947.Lenovo.com/support/entry/portal/docdisplay?lndocid=migr- 5095319...
PDU types explained section. Note: These PDUs can be monitored remotely, but do not have the ability to control the outlets remotely. For Lenovo PDUs that have the ability to control outlets remotely see the Switched and Monitored PDUs section on page...
DPI Enterprise PDU+ C13 This section discusses the 39M2816 DPI Enterprise PDU+ C13. This section is broken up into the following sections. Quick Specs • Front and Back View and Outlets • Input Line Cords • Specifications • Accessories kit •...
Page 104
PDU 39M2816 + Line Cord 40K9613 Type 63A / 220V-240V Outlets types twelve IEC C13 Power Capacity 14490VA @ 230V Power Limit per PDU 63A Phase Single phase PDU 39M2816 + Line Cord 40K9617 Type 32A / 230V Outlets types six IEC C19 Power Capacity 7360VA @ 230V...
Page 105
The 39M2816 has 12 C13 outlets on the front of the PDU. The following figure displays a front and back view picture of the PDU. Figure 56: Front and back panel of the Lenovo DPI Enterprise PDU+ C13 Figure on page...
Page 106
Three phase – 39M2816 Figure 57: Outlets and amperage...
Specifications The following table are specifications for the 39M2816 DPI C13 PDU+. Specifications Line cord PN Line cord PN Line cord PN Line cord PN Line cord PN Input Line 40K9611 40K9612 40K9613 40K9617 40K9618 Cord Type* Type 32A/380- 32A / 220- 63A/220V- 32A / 230V 30A / 230V...
Also included: 1 x EMP (see below), 1 x DB9 to RJ-45 cable, 1 x CAT5 6ft/1.8m cable, cable straps. These accessories are for supporting the racking of the Lenovo DPI Enterprise PDU+ in an Lenovo rack. Some parts may be unused, depending on how and where the PDU is installed. Refer to the...
Racking This section discusses mounting the 39M2816 DPI Enterprise C13 PDU+ in the side of a rack, the side pockets of an Enterprise rack (0U space) and EIA (U space) of a rack. Mounting in side pocket Mounting the 39M2816 DPI Enterprise C13 PDU+ in the side pocket requires the use of the vertical mounting bracket, shipped as part of the PDU accessory kit, see the Accessories kit section for additional information.
Page 112
Mounting In Lenovo Enterprise Rack (9308 & 1410) & Lenovo Enterprise V2 Rack (9363) Rear Zero Pocket (side pocket) Mounting the 39M2816 DPI Enterprise C13 PDU+ in the side pocket of an enterprise rack requires the use of the horizontal mounting bracket, shipped as part of the PDU...
Page 113
Mounting in EIA (U space) of rack Mounting the 39M2816 DPI Enterprise C13 PDU+ in the U space of a rack requires the use of the horizontal mounting bracket, shipped as part of the PDU accessory kit, see the Accessories kit section for additional information.
Installation and Maintenance Guide The following link is the installation and user guide for the Lenovo DPI Enterprise PDU+ C13 39M2816 ftp://ftp.software.ibm.com/systems/support/system_x_pdf/43v6030.pdf...
1U 12 C13 Switched and Monitored PDU This section discusses the 46M4004 Lenovo 1U 12 C13 Switched and Monitored PDU. This section is broken up into the following sections. Quick Specs • Front and Back View and Outlets • Input Line Cords •...
Page 117
PDU 46M4004 + Line Cord 40K9613 Type 63A/220-240V Outlets types twelve IEC C13 Power Capacity 14490VA @ 230V Power Limit per PDU Phase Single phase PDU 46M4004 + Line Cord 40K9617 Type 32A/230V Outlets types twelve IEC C13 Power Capacity 7360VA @ 230V Power Limit per PDU Phase...
Page 118
Front and Back View and Outlets The 46M4004 has detachable single phase and three phase line cord options. The following figure displays a front and back view of the PDU. Figure 63: Front and back view Figure on page displays the 1U 12 C13 Switched and Monitored PDU outlets and amperage.
Specifications The following table are specifications for the 46M4004 C13 Switched and Monitored PDU. Specifications Line cord PN Line cord PN Line cord PN Line cord PN Line cord PN Input Line 40K9611 40K9612 40K9613 40K9617 40K9618 Cord Type* Type 32A/380- 32A / 220- 63A/220V-...
Accessory Kit These accessories are for supporting the racking of the Lenovo Switched and Monitored C13 PDU in an Lenovo rack. Some parts may be unused, depending on how and where the PDU is installed. Refer to th e Racking section for information on racking the Lenovo C13 PDU.
Racking This section discusses mounting the 46M4004 1U C13 PDU in the side of a rack, the side pockets of an Enterprise rack (0U space) and EIA (U space) of a rack. Mounting in side of a rack Mounting the 46M4004 in the side pocket requires the use of the vertical mounting brackets, shipped as part of the PDU accessory kit, see the Accessory Kit section for...
Page 125
Mounting In Lenovo Enterprise Rack (9308 & 1410) & Lenovo Enterprise V2 Rack (9363) Rear Zero Pocket (side pocket) Mounting the 46M4004 in the side pocket of an enterprise rack requires the use of the horizontal mounting bracket, shipped as part of the PDU accessory kit, see the s ection for additional information.
Page 126
Mounting in EIA (U space) of rack Mounting the 46M4004 in the U space of a rack requires the use of the 2 horizontal mounting rails and small brackets, shipped as part of the PDU accessory kit, see the Accessory Kit section for additional information.
Installation and Maintenance Guide The following are the Installation and Maintenance manuals for the Lenovo 1U 12 C13 Switched and Monitored PDU. 46M4004 http://www.ibm.com/support/entry/portal/docdisplay?lndocid=MIGR-5084069...
1U 9 C19 / 3 C13 Switched and Monitored PDU This section discusses the 46M4002 1U 9 C19 / 3 C13 Switched and Monitored PDU. This section is broken up into the following sections. Quick Specs • Front and Back View and Outlets •...
Page 129
PDU 46M4002 + Line Cord 40K9617 Type 32A/230V Outlets types nine IEC C19, three IEC C13 Power Capacity 7360VA @ 230V Power Limit per PDU Phase Single phase PDU 46M4002 + Line Cord 40K9618 Type 30A/220V Outlets types nine IEC C19, three IEC C13 Power Capacity 6600VA @ 220V Power Limit per PDU...
Page 130
Three phase operation Figure 70: Outlets and amperage Each phase has three IEC C19 and one IEC C13 outlets.
Page 131
Single phase operation Figure 71: Outlets and amperage...
Page 132
32A (32A / Phase) 380-415VAC Three Phase Wye 96A Total Circuit Capacity 46M4002 40K9612 5903 Lenovo DPI IEC 309 P+N+G (4.3m) line cord 32A / 220-240VAC Single Phase 46M4002 40K9613 5904 Lenovo DPI IEC 309 P+N+G (4.3m) line cord...
Page 133
Specifications The following table are specifications for the 46M4002 1U C19/C13 PDU. Specifications Line cord PN Line cord PN Line cord PN Line cord PN Line cord PN Input Line 40K9611 40K9612 40K9613 40K9617 40K9618 Cord Type* Type 32A/380- 32A / 220- 63A/220V- 32A / 230V 30A / 230V...
Page 134
Accessory Kit These accessories are for supporting the racking of the Lenovo Switched and Monitored C19/C13 PDU in an Lenovo rack. Some parts may be unused, depending on how and where the PDU is installed. Refer to th e Racking section for information on racking the Lenovo C19/C13 PDU.
Page 135
Racking This section discusses mounting the 46M4002 1U C19/C13 PDU in the side of a rack, the side pockets of an Enterprise rack (0U space) and EIA (U space) of a rack. Mounting in side of a rack Mounting the 46M4002 in the side pocket requires the use of the vertical mounting brackets, shipped as part of the PDU accessory kit, see the Accessory Kit section for...
Page 136
Mounting In Lenovo Enterprise Rack (9308 & 1410) & Lenovo Enterprise V2 Rack (9363) Rear Zero Pocket (side pocket) Mounting the 46M4002 in the side pocket of an enterprise rack requires the use of the horizontal mounting bracket, shipped as part of the PDU accessory kit, see the s ection for additional information.
Page 137
Mounting in EIA (U space) of rack Mounting the 46M4002 in the U space of a rack requires the use of the 2 horizontal mounting rails and small brackets, shipped as part of the PDU accessory kit, see the Accessory Kit section for additional information.
Page 138
Installation and Maintenance Guide The following are the Installation and Maintenance manuals for the 1U 9 C19 / 3 C13 Switched and Monitored PDU 46M4002 http://www.ibm.com/support/entry/portal/docdisplay?lndocid=MIGR-5084069...
0U 24 C13 Switched and Monitored PDU This section discusses the 46M4119 0U 24 C13 Switched and Monitored PDU. This section is broken up into the following sections. Quick Specs • Front View and Outlets • Input Line Cord • Specifications •...
Page 140
Figure 77: Outlets and amperage The outlets are broken up into three groups, each group represents a group: A1 – A8, B1 – B8, and C1 – C8.
Input Line Cord The following input line cord is for connecting the PDU to an appropriate power circuits. This may include for example, the wall or floor outlets to provide power to the PDU. Refer to the 0U PDU Attached line cord and plugs section for a picture of the line cord plugs.
Accessories The following items make up the accessory kit that contains miscellaneous hardware for installing the Rack PDU in a rack cabinet. These are shipped with the PDU. Figure 78: Accessory kit Also included: 1 x DB9 to RJ-45 cable, and miscellaneous hardware kit for attaching the PDU and installing in a rack cabinet.
Racking This section discusses mounting for all Lenovo 0U PDU in the back of the Lenovo Standard racks (9307 and 9956), mounting in the back of the Lenovo Enterprise racks (9308 and 1410), and the Lenovo Enterprise rack v2 (9363), and the mounting in Lenovo racks with integrated PDU mounting keyholes (9362, 9361, and 9360).
Page 144
Mounting the 0U PDUs at the back of an Enterprise Rack Cabinet (9308 and 1410) and the Lenovo Enterprise V2 Rack (9363) requires the use of the two upper and two lower mounting brackets, shipped as part of the PDU accessory kit, see the Accessories section for additional information.
Page 145
Mounting In the Back of Lenovo Racks with Integrated PDU Mounting Keyholes (9362, 9361, and 9360) Mounting the 0U PDUs at the back of a rack with mounting key holes is displayed in Figure Figure 81: Rack with mounting keyholes at the rear...
Installation and Maintenance Guide The following are the Installation and Maintenance manuals for the 0U 24 C13 Switched and Monitored PDU 46M4119 http://www.ibm.com/support/entry/portal/docdisplay?lndocid=MIGR-5086798...
Three Phase Front View and Outlets The 46M4137 Lenovo 0U 12 C13 / 12 C19 Switched and Monitored PDU. This PDU comes with an attached line cord for three phase operation. The following figure displays the front view of the PDU.
Page 148
Figure 83: Outlets and amperage Note: Derated 16A MAX available per breaker. The outlets are broken up into 6 groups across 3 phases, A1-A4 and B1-B4 represent phase 1, C1-C4 and D1-D4 represent phase 2, and E1-E4 and F1-F4 represent phase 3. Refer to the Specifications section for additional information.
Input Line Cord The following input line cord is for connecting the PDU to an appropriate power circuits. This may include for example, the wall or floor outlets to provide power to the PDU. Refer to the 0U PDU Attached line cord and plugs section for a picture of the line cord plug.
Accessories The following items make up the accessory kit that contains miscellaneous hardware for installing the Rack PDU in a rack cabinet. These are shipped with the PDU. Figure 84: Accessory kit Also included: 1 x DB9 to RJ-45 cable, and miscellaneous hardware kit for attaching the PDU and installing in a rack cabinet.
Racking This section discusses mounting for the Lenovo 0U PDU in the back of the Lenovo Standard racks (9307 and 9956), mounting in the back of the Lenovo Enterprise racks (9308 and 1410), and the Lenovo Enterprise rack v2 (9363), and the mounting in Lenovo racks with integrated PDU mounting keyholes (9362, 9361, and 9360).
Page 152
Mounting the 0U PDUs at the back of an Enterprise Rack Cabinet (9308 and 1410) and the Lenovo Enterprise V2 Rack (9363) requires the use of the two upper and two lower mounting brackets, shipped as part of the PDU accessory kit, see the Accessories section for additional information.
Installation and Maintenance Guide The following are the Installation and Maintenance manuals for the Lenovo 0U 12 C13 / 12 C19 Switched and Monitored PDU. 46M4137 http://www.ibm.com/support/entry/portal/docdisplay?lndocid=MIGR-5086798...
Line Cords and Plugs The following section displays the plugs used on each PDU line cord. The following sections are covered. Universal Rack PDU line cord plugs • Front End PDU Line cord plugs • 1U PDU Detached line cord plugs •...
39Y8955 Universal Rack PDU 230VAC (Italy CEI 23-16) 39M5297 – C19 to Italy CEI 23-16 (1.8m) @ 230VAC Single Phase 39M5298 – C19 to Italy CEI 23-16 (2.5m) @ 230VAC Single Phase 39M5299 – C19 to Italy CEI 23-16 (4.3m) @ 230VAC Single Phase Used with: 39Y8955 –...
39Y8957 Universal Rack PDU 230VAC (UK BS 1363/A) 39M5293 – C19 to UK BS 1363/A (1.8m) @ 230VAC Single Phase 39M5294 – C19 to UK BS 1363/A (2.5m) @ 230VAC Single Phase 39M5295 – C19 to UK BS 1363/A (4.3m) @ 230VAC Single Phase Used with: 39Y8957 –...
39Y8960 Universal Rack PDU 220-240VAC (Brazil NBR 14136) 39M5357 – C19 to Brazil NBR 14136 (1.8m) @ 220-240VAC Single Phase 39M5358 – C19 to Brazil NBR 14136 (2.5m) @ 220-240VAC Single Phase 39M5359 – C19 to Brazil NBR 14136 (4.3m) @ 220-240VAC Single Phase Used with: 39Y8960 –...
39Y8962 Universal Rack PDU 220VAC (Argentina IRAM 2073) 39M5341 – C19 to Argentina IRAM 2073 (1.8m) @ 220VAC Single Phase 39M5342 – C19 to Argentina IRAM 2073 (2.5m) @ 220VAC Single Phase 39M5343 – C19 to Argentina IRAM 2073 (4.3m) @ 220VAC Single Phase Used with: 39Y8962 –...
Front End PDU Line cord plugs This section covers all the plugs on each line cord for the Front End PDU which includes: 39Y8934 Front End 220-240VAC / 32A Cord (IEC 309 P+N+G) • 39Y8935 Front End 220-240VAC / 63A Cord (IEC 309 P+N+G) •...
Page 161
39Y8935 Front End 220-240VAC / 63A Cord (IEC 309 P+N+G) IEC 309 P+N+G (2.5m) - 63A 220- 240VAC Single Phase Only a receptacle or a connector is needed to mate with the plug on the PDU input line cord. See the Additional Plug Information on page in this document for...
Page 162
39Y8936 Front End 220VAC / 30A Cord (KSC 8305 30A) P+N+G (Shin Ju P/N SJ-P3302) Korea connector Note: Note that this is not the same cord as the 40K9618 cord. PDU line cord connector pin out is different. Used with: 39Y8936 –...
Page 163
39Y8937 Front End 230VAC / 32A Cord (AUS/NZ 3112 32A) P+N+G (PDL P/N 56P332) Australia/New Zealand connector Note: Note that this is not the same cord as the 40K9617 cord. PDU line cord connector pin out is different. Used with: 39Y8937–...
Page 165
40K9611 – DPI 32A Cord (IEC 309 3P+N+G) IEC-309 3P+N+G (4.3m) 32A, 3P5W plug (Type 532P6W) 32A (32A / Phase) 380-415VAC Three Phase Wye 96A Total Circuit Capacity Only a receptacle or a connector is needed to mate with the plug on the PDU input line cord.
40K9612 – DPI 32A Cord (IEC 309 P+N+G) IEC 309 P+N+G (4.3m) - 32A / 220-240VAC Single Phase Only a receptacle or a connector is needed to mate with the plug on the PDU input line cord. See the Additional Plug Information on page in this document for further details on IEC309.
40K9613 – Lenovo DPI 63A Cord (IEC 309 P+N+G) IEC 309 P+N+G (4.3m) - 63A / 220-240VAC Single Phase Only a receptacle or a connector is needed to mate with the plug on the PDU input line cord. See the...
0U PDU Attached line cord and plugs This section covers all the plugs on each line cord for the 1U Rack PDUs which include line cords: Attached 16A 3ph Cord (IEC309 3P+N+G) • Attached 32A 1ph Cord (IEC309 P+N+G) • Attached 32A 3ph Cord (IEC309 3P+N+G) •...
Attached 32A 1ph Cord (IEC309 P+N+G) IEC 309 P+N+G 3.0 meter (4.3m) - 32A / 220-240VAC Single Phase Only a receptacle or a connector is needed to mate with the plug on the PDU input line cord. See the Additional Plug Information on page in this document for further details on IEC309.
Attached 32A 3ph Cord (IEC309 3P+N+G) IEC-309 3P+N+G 3.0 meter 32A , 3P5W plug (Type 532P6W) 32A (32A / Phase) 380-415VAC Three Phase Wye 96A Total Circuit Capacity Only a receptacle or a connector is needed to mate with the plug on the PDU input line cord.
Higher Voltage DC PDU Line cord and hard wiring The following section discusses the Higher Voltage DC (HVDC) line cord and hard wiring. HVDC Line cord and plug 90A@240-380VDC cable 4.3 meter Pig-tail termination (hardwired, no plug). Three stranded copper conductors, each with a cross section of 25 sq. mm. Used with: HVDC PDU: 44T0966 –...
Re-termination for A/NZ When using the 40K9611 in Australia or New Zealand, a licensed electrician will be required to re-wire the plug. The IEC-309 3P+N+G will need to be replaced with a Clipsal 5 Round Pin, 32A, Three Phase Wye plug (P/N 56PA532). The following pictures depict the rewired plug on 40K9611 for A/NZ.
The EMP reports the local temperature and humidity values to management tools such as Lenovo Systems Director Active Energy Manager (AEM) or to the PDU web interface. The following image shows an example of the EMP connected to an Lenovo Monitored PDU communication port via a CAT5 cable.
Part Number Description 46M4113 Optional Lenovo Environmental Monitoring Probe (EMP) Kit You can install the device anywhere on the rack by using either the screws or the self-adhesive hook-and-loop fasteners. Once attached to the rack, connect the CAT5 cable to the PDU Sensor connector (1U PDU) or the Ethernet connector (0U PDU) as seen below.
For these reasons, if you are running a system with 95W CPUs for example, it is not realistic to provide the rating number as an accurate guide for your systems power load. Use the Lenovo Power Configurator tool to better define your hardware's power draw. The tool is available for download from: http://www.ibm.com/systems/bladecenter/resources/powerconfig.htm...
NeXtScale System Chassis Label Rating The following table represents the label rating numbers for the NeXtScale System Chassis. Chassis Power Power Power 100-127V 200-240V Supply Supplies Supplies Max Rating Rating Wattage Standard n1200 900W 6.8A / 5A / Supply Supply n1200 1300W 6.9A /...
System x Tower Server Label Rating The following table represents the label rating numbers for System x Tower Servers. Server Power Power Server Ratings Redundant Supply Supplies Wattag 100-127V Standar Max 100- 200- 220- 127V 208V 240V x3100 x3100 (4348) 310W 4.5A 2.25A...
Page 181
x3400 x3400 (7973, 670W 2.5A 7974) x3400 (7975, 835W 6.5A 3.25A 7976) x3400 M2 (7836, 670W 7837) x3400 M2 (7836, 920W 7837) x3400 M3 (7378, 670W 7379) Server Power Power Server Ratings Redundant Supply Supplies Wattag 100-127V Standar Max 100- 200- 220- 127V...
System x Rack Server Label Rating The following table represents the label rating numbers for System x Rack Servers. Server Power Power Server Ratings Redundant Supply Supplies Wattag 100-127V Standar Max 100- 200- 220- 127V 208V 240V x3250 x3250 (4364, 350W 4365) x3250 M2 (4190,...
Page 183
x3620 x3620 M3 (7376) 460W 5.3A 2.6A x3620 M3 (7376) 675W 7.8A 3.8A x3630 x3630 M3 (7377) 675W 7.8A 3.8A Server Power Power Server Ratings Redundant Supply Supplies Wattag 100-127V Standar Max 100- 200- 220- 127V 208V 240V x3630 M4 (7158) 550W 6.5A 3.3A x3630 M4 (7158) 750W...
iDataPlex Chassis Label Rating The following table represents the label rating numbers for the Storwize Storage Units. Chassis Slot Power Supply Number of Power Chassis Rating Configuration Wattage Supplies Standard Max 2U Flex Chassis 2 Planars 900W High 100V – 8.62A (7831, 6385) Efficiency 110V –...
Page 188
Chassis Slot Power Supply Number of Power Chassis Configuration Wattage Supplies Rating Standard 3U Storage 900W High 100V – 7.61A Chassis Efficiency 110V – 6.90A (7834, 6386) 115V – 6.52A 120V – 6.28A 127V – 5.90A 200V – 3.73A 208V – 3.59A 220V –...
Server Label Rating The following table represents the label rating numbers for Lenovo xSeries Servers. Server Power Power Server Ratings Redundant Supply Supplies Wattage 100-127V Standard Max 100- 200- 220- 127V 208V 240V x100 310W 4.5A 2.25A x206 400W 5.5A...
Additional Plug Information The following section discusses more details on the PDU plugs. IEC 320 Connectors The following table displays the plug types for different hardware such as monitors, switches, servers, high-end servers, power distribution units (PDUs), and Uninterruptable Power Supplies (UPSs). Name Amp Rating (A) Connector...
Rong Fend RF-203P Connector The following table displays the plug type for the Higher Voltage DC PDU. Name Connector AMP Rating For systems requiring DC power from a DC RF-203P 10/15A power source. IEC 309 Plug Sleeve Ratings The color of the sleeve around a plug indicates its voltage rating. The colors and ratings are listed below.
IEC 309 Pin Decode The following table is a break down of the Hubbell (HBL) part number.
Page 196
The numbers and letters circled in red below is an example HBL part number: HBL460R9W. The P/N: HBL460R9W plug description is listed below: HBL460R9W = 4 pin (3ph), 60A, Receptacle, 9 ground (G) clock face pin position, Watertight. Note: The number of pins indicates the phase: 3 pins = 1ph, 4 pins = 3ph and 5 pins Δ, = 3 ph Y...
Ingress Protection (IP) Decode Example: IP67 = Ingress Protection / Dust-Tight / Temporary Immersion Three Phase Power Calculation Diagrams The following figures explain three phase power values for various amperage. 60A Three Phase Delta Power Calculations...