20 | Vertical configurability
3. Locate the BACK left condensate drain and
remove and retain plastic plug covering the
cutout. (Figure#65)
Figure # 65
4. Reinstall the removed plastic plugs in the
original Condensate Drain Location.
5. Route the flexible plastic tube from FRONT left
corner post to BACK left. (Figure#66)
Avoid kinking the hose and/or creating a dip
which could act as a second internal p-trap.
Double trapped drain lines will not drain
properly.
Figure # 66
6. Measure and cut the condensate drain hose to
the appropriate length.
7. Insert spring onto condensate drain hose.
6 720 220 406 (2013/1)
8. Reinstall condensate drain plastic fitting and
bushing in its new location.(Figure#67)

HRP Switch Relocation

The HRP Pump Disconnect Switch is shipped loose
inside unit E-Box, to be connected to either FRONT
right corner post or BACK right corner
post.(Figure#68)
1. From the inside of the unit remove (2) wires
connected to HRP Pump Disconnect Switch.
Subject to change without prior notice
SM Series Heat Pump
Figure # 67
Figure # 68
SM Series Heat Pump