What you want to view
Status of transmitter operation at the present
time.
Present failsafe output direction, which depends
on the position of the internal failure mode alarm
jumper.
Present sensor temperature (±5°C) measured by
circuitry in the transmitter's sensor.
Present information in the message (or
scratchpad) area.
Note: Some values for PV, PV LRV and PV URV may not be visible in some displays, (due to the limitations
of the communicator display). To view these values you must use the down arrow key to select the
value and then press the right arrow key to display the value in detail.
10/05
ST 3000 HART Transmitter Release 300 User Manual
8— Operation - Accessing Operation Data
What to do
Select: Device setup
Diag/Service
Device status
Select either "Critical" or "Non-Critical" from the
"Device status" display.
Warnings, status messages, and error messages
appear on screen as necessary. Refer to Section
11 in this manual for further information.
Select: Device setup
Detailed setup
Output condition
Analog output
Read AO Alrm typ from "Analog output" display.
ST3000: PT 3011
Analog output
1
AO
2
AO Alrm typ
3
Loop test
4
D/A trim
5
Scaled D/A trim
HELP
Choose: Device setup
Detailed setup
Sensors
Read SV from "Sensors" display
ST3000: PT 3011
Sensors
1
PV
2
PV unit
3
Sensor information
4
SV
5
SV unit
HELP
Choose: Device setup
Basic setup
Device information
Message
Read present information in "Message" display.
ST3000: PT 3011
Message
XXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXX
CALIBRATED BY JOE 12 02 98
HELP
DEL
11.990 mA
Hi
HOME
-0.0134 inH2O
inH2O
23.42 degC
degC
HOME
ESC
ENTER
89