hit counter script

Temperature Setting - Honeywell TRADELINE Y594 User Manual

Multistage thermostat subbase package
Hide thumbs Also See for TRADELINE Y594:
Table of Contents

Advertisement

VERTICAL
OUTLET
BOX
1
HORIZONTAL
OUTLET
BOX
SUBBASE
SUBBASE
MOUNTING SCREWS (2)
CAPTIVE
MOUNTING SCREWS (2)
1 NOT INCLUDED WITH UNIT.
2 ACCESSORY PARTS AVAILABLE (193121A).
Fig. 1. Installation of subbases and thermostat on
outlet box.
TOP
MOUNTING
HOLES (2)
SPIRIT LEVEL
MOUNTING
HOLES (2)
Fig. 2. Leveling the subbase.
FOR STRAIGHT
INSERTION–
STRIP 5/16 in. (8 mm)
BARRIER
SUBBASE TERMINAL SCREW
Fig. 3. Wiring connections.
MOUNTING
SCREWS (2)
1
COVER
ADAPTER
PLATE
RING
2
THERMOSTAT
THERMOSTAT
O L
C O
8 0
COVER
7 0
6 0
5 0
8 0
7 0
6 0
5 0
A T
H E
8 0
7 0
6 0
5 0
THERMOSTAT
WIRING
CABLE OPENING
TERMINAL
POST (2) FOR
TO SPRING FINGER
MOUNTING
CONTACTS ON THE
THERMOSTAT
THERMOSTAT
(UP TO 12)
FOR WRAPAROUND–
STRIP 7/16 in. (11 mm)
M928
Y594 (MULTISTAGE THERMOSTAT SUBBASE) PACKAGE
Note the tabs along the top inside edge of the
thermostat base. The tabs fit into the subbase
notches. Mount the thermostat on the subbase and
2
tighten the captive mounting screws. See Fig. 1. Do
not overtighten captive mounting screws. This can
damage the threads in the subbase.
Place the upper edge of the thermostat cover on the
base and swing cover downward until it engages
retaining posts on base. Tighten the locking cover
screws if assembly is provided.
SETTING
Setting the 2nd Stage (Y594G1666 and
Y594G1674 Only) Heat Anticipator
Set the adjustable heat anticipator to match its primary control
current draw. If the primary control nameplate has no rating or
if further adjustment is necessary, use the following procedure
to measure the current draw of each stage:
Remove thermostat from the subbase. Make sure
the power is on.
Connect an ac ammeter of appropriate range
between the heating terminals of the subbase:
Stage 2: between W2 and R.
Move the system switch to HEAT or ON.
After one minute, read the ammeter and record the
reading.
Remount the thermostat and use a ballpoint pen to
set the adjustable heat anticipator(s) to match the
M6009
reading(s) measured in step 4. See Fig. 8.

Temperature Setting

Move the heating and cooling levers to the desired
positions. The minimum differential between heating and
cooling setpoints is 3 F (2 C). Some thermostat models
have nonadjustable lever stops, which set the maximum
heating control point at 68 F or 72 F (20 C or 22 C) and
the minimum cooling control point at 78 F (26 C). Do not
attempt to exceed these limits. Some models have only
one lever for heating and cooling.
Subbase Setting
Available subbase system switch positions vary by
thermostat model. Positions control thermostat operation
as follows:
OFF: Heating and cooling systems are off. If the fan
switch is at the AUTO position, the fan is also off.
HEAT: Heating system is controlled by the thermostat.
Cooling system is off.
M927
COOL: Cooling system is controlled by the thermostat.
Heating system is off.
ON: Thermostat automatically switches between heat
and cool modes, depending on the indoor tempera-
ture.
SUPL. HT.: Supplemental heat is energized. Cooling
system is off. Compressor cannot operate.
Fan switching positions control fan operation as follows:
ON: Fan operates continuously.
AUTO: Fan operates with heat pump and supplemental
heat as controlled by the thermostat.
3
69-0920

Advertisement

Table of Contents
loading

Table of Contents