If the time interval between two defrost cycles is changed
when the system is in operation, the new time interval will
not be applied until after the next time defrosting has
occurred.
E09 Defrost time (0 = no defrosting)
E10 Max. display delay
after defrosting
During the defrosting process, the last current tempe-
rature before defrosting started is retained in the dis-
play. After defrosting, the display returns to the instan-
taneous temperature when the stored value is reached
again or, at the latest, after time E10 has elapsed.
E11 Operating of relay
if sensor T1 defective
E12 "On" time at E11
E13 "Off" time at E11
Exiting programming mode:
Press the
key after the last level has been entered.
7.2 Sensor calibration (parameter E06)
The sensor can be calibrated.
Note on sensor calibration: Additional line resistance of 7
case, caused by sensor cable extension, results in a change in the
temperature display by +1K.
How to proceed: Measure the temperature with a calibrated
thermometer or submerge the sensor in well-mixed ice water (0 °C).
Compare the measured temperature with the temperature shown on
the unit display.
If the measured temperature is lower than the one displayed, set the
negative difference as the programming value (e.g. - 2 K).
0 to 99 mins.
0 to 99 mins.
0 = Relay
1 = Relay
2 = On/off in
1 to 99 mins.
1 to 99 mins.
11
25 mins.
15 mins.
2
de-energized
permanently
energized
sequence,
according to
the times set
in E12 and
E13.
15 mins.
15 mins.
in each