hit counter script

Honeywell CR7075 Product Data page 4

Two-stage lighting controller
Table of Contents

Advertisement

CR7075 TWO-STAGE LIGHTING CONTROLLER
Wiring
CAUTION
Electrical Shock or Equipment Damage Hazard.
Can shock individuals or short equipment
circuitry.
Disconnect power supply before installation.
IMPORTANT
• All wiring must agree with applicable codes,
ordinances and regulations.
• When wiring the input power, apply only one source
of power to the CR7505A.
• With line-voltage loads, the power and load voltage
must be the same.
Refer to chart on the inside of the controller cover or Fig. 3 for
locating the power inputs, photocell sensor inputs, TOD and
load relay terminals. Refer to Fig. 4 through 7 for typical wiring
and application examples.
NOTES:
The photocell sensor has no polarity.
Wire to terminal strip T2, terminals 4 and 5.
Access to the terminals can be gained through
standard conduit knockouts (A-E) located around
the perimeter of the enclosure.
Use knockout A only for the photocell sensor
and TOD wiring.
Photocell wires should be at least 18 AWG two
conductor. If not run in watertight conduit, use
suitable insulation for outdoor wiring.
Shielded wiring is not required.
The Two-Stage Lighting Control System consists of
two components:
— CR7075 Two-Stage Lighting Controller.
— C7057 Cadmium Sulfide Photocell Sensor.
This system offers independent series 60 control of two
separate lighting banks based on user determined ambient
light intensity level via a single sensor.
Set point indexing is relative. The SET-RUN switch removes
the integrating time delay (short cycle protection) circuitry in
the SET position. In the RUN position (normal operation) there
is a 30 ±10 second time delay for both light fall and light rise
initiated relay action.
Two independent Time Of Day (TOD) inputs are provided to
override a relay energized condition of either output. This
function is generated by a contact closure from an EMS
controller or time clock with normally open contacts, i.e.,
W7505, S7005, etc., between terminals 1 and 2 (stage 1) and
terminals 2 and 3 (stage 2) of terminal strip T2 (Fig. 6 and 7).
These inputs have priority over any time delay action.
63-2180—1
C
CAUTION
ONE POWER SOURCE ONLY
LINE POWER
B
120
COM
VAC
A
Fig. 3. Knockout locations and internal device layout.
WHITE
L1
BLACK
L2
1
T.O.D. 1
T.O.D. 2
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND
OVERLOAD PROTECTION AS REQUIRED.
Fig. 4. Wiring for 120 or 240 Vac input and load.
4
D
OUTPUT 1
OUTPUT 2
240
N0
COM NC
N0
COM NC
VAC
SET
RUN
LIGHT LEVEL
6
5
6
5
4
7
7
3
8
8
T.O.D. 1
9
2
9
T.O.D. 2
10
1
10
POWER
STAGE 1
STAGE 2
SENSOR
LOAD 1
CAUTION
ONE POWER SOURCE ONLY
LINE POWER
OUTPUT 1
OUTPUT 2
120
240
COM
N0
COM NC
N0
VAC
VAC
SET
RUN
LIGHT LEVEL
6
5
4
7
1
3
8
T.O.D. 1
2
9
2
T.O.D. 2
10
1
3
POWER
STAGE 1
4
SENSOR
5
E
4
3
2
1
M1040
LOAD 2
COM NC
6
5
4
7
3
8
9
2
1
10
STAGE 2
M1043

Advertisement

Table of Contents
loading

Table of Contents