Samsung MIM-B17 User Manual page 125

Data management server2, bacnet gateway, lonworks gateway for air conditioner
Hide thumbs Also See for MIM-B17:
Table of Contents

Advertisement

Contact Control Pattern Selection
1
Click [System Settings]
when DMS2 web page menu screen appears.
2
Click [Edit] from contact point pattern selection window.
3
Select the pattern you want to check.
 Pattern 1[No external input]:
No operation will be made when inputting contact
control signal.
 Pattern 2[Level(Emergency stop)]:
Commands that stop all operation of indoor unit and
disable remote control when inputting contact control
signal. In level emergency stop status, it will not be
controlled even if the command is from upper controller.
 Pattern 3[Level(Operation/Stop)]:
Level signal input timing.
It changes operation/stop status of all indoor units.
 Pattern 4[pulse (Operation/Stop,Disable/Enable)]:
Pulse signal. It changes operation/stop status of all indoor
units.
4
Click [Save] after setting is completed.
 [System environment setting]
125