hit counter script

Samsung MIM-B17 User Manual page 27

Data management server2, bacnet gateway, lonworks gateway for air conditioner
Hide thumbs Also See for MIM-B17:
Table of Contents

Advertisement

Set upper temperature limit by pressing [] and [].
3
 Click 'Heat upper limit' to apply the upper temperature limit setting.
 When indoor unit is operating in heat mode, DMS2 controls indoor unit as upper
temperature limit if the desired temperature is higher than upper temperature limit.
 Upper temperature limit can be set in the range of 16°C(61°F)~30°C(86°F).
 When an indoor unit is operating in Heat mode and the upper temperature limit is
applied, you cannot set the desired temperature higher than the upper temperature
limit.
Set lower temperature limit by pressing [] and [].
4
 You can set lower temperature limit by clicking 'Cool lower limit'.
 When indoor unit is operating in cool mode, DMS2 controls indoor unit as lower
temperature limit if the desired temperature is lower than lower temperature limit.
 Lower temperature limit can be set in the range of 18°C(65°F)~30°C(86°F).
 When indoor unit is operating in Cool or Dry mode and the low temperature limit is
applied, you cannot set the desired temperature lower than the lower temperature
limit.
Note
 You cannot set the lower and upper temperature limit of ERV, ERV PLUS,
and Fresh duct.
27
E-

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Mim-b18Mim-d00a

Table of Contents