System Settings (Continued)
138
E-
6
Tracking completed message will appear.
Select Zone initialization mode you want and click [OK].
Not initialize: No zone information initialization will be
made.
Initialize individually: Initialize zone information as
Initialize by group: Initialize zone information as group
Note
If tracking is executed successfully when interface
module is set for communication mode setting by
channel, virtual centralized controller will be assigned
to each channel.
For about centralized controller's address, address
11~15 will be assigned to channel 0~4 for each.
If there is interface module communication channel,
tracking for centralized controller will be restricted
for the centralized controller which are in the range of
0~10.
If there is no searched interface module, centralized
controller, and SIM/PIM, it is regarded as DVM tracking
failure.
If there are devices which have same address, first
searched device will be registered only.
The number of centralized controller contains the
number of virtual centralized controller which is used
in interface module communication.
The number of indoor unit contains the number of
indoor unit, ERV, AHU, and GHP.
If you execute tracking, system setting will be initialized.
If tracking result does not match with actual installation
information, there can be critical error in additional
functions such as power distribution.
Make sure that tracking information matches to actual
installation information after tracking.
individual mode.
mode.