hit counter script

Zones Available; Zone Message; 4: Loop Setup; Class - Honeywell Fire-Lite Alarms ES-200XI Manual

Addressable fire alarm control panel
Table of Contents

Advertisement

Master Programming Level
To program a waterflow circuit as nonsilenceable, refer to "System Setup" on page 74.
NOTE: Zone Types are only relevant for Central Station reporting. Changing a zone type will only change how it is reported to the Central
Station.

Zones Available

ZONE SETUP
1=ZONE TYPES
2=ZONES AVAILABLE

3=ZONE MESSAGE

Zone Setup Screen #3
The display will show all of the zones that are still available for programming. Note that an up and/or down arrow may appear in the upper
right corner of the display, indicating that additional screens of zone information exists. Press the up or down arrow key to view additional
screens.
Zone Message
ZONE SETUP
1=ZONE TYPES
2=ZONES AVAILABLE
3=ZONE MESSAGE
Zone Setup Screen #3
Pressing the down arrow key will display additional screens for Zones up to Z99. Press the number key corresponding to the Zone to be pro-
grammed. Screens will be displayed allowing the programmer to select Audio Messages 1 through 14. When an audio message is selected,
the display will return to the Zone Message screen, showing the message selected for that particular zone. In the example above, Zone 001
has been programmed for Audio Message 1.
3.5.4 Loop Setup
PROGRAMMING
1=LOOP SETUP
2=SYSTEM SETUP
3=FUTURE USE
Programming Screen #2

Class

To program the SLC Class for the selected loop, press 1 for Class, while viewing Loop Setup Screen. In the preceding example, the control
panel is programmed for Class B SLC wiring as indicated by the B to the right of Class in the display. To change the wiring style, press 1 to
toggle the display to read Class A. Each press of the 1 key will cause the display to toggle between Class B and Class A.
NOTE: If the FACP reports an open fault on an SLC Loop programmed for Class A, the trouble condition will latch at the FACP. When the SLC
Loop has been repaired, the Reset button must be pressed at the FACP (at least 2 minutes after the trouble has been repaired) to clear the SLC
trouble.

Loop Protocol

Loop Protocol refers to the SLC loop mode of operation. Refer to "Wire Requirements" on page 146 for wire specifications based upon SLC
protocol. There are two Loop Protocols available:
CLIP (Classic Loop Interface Protocol) - which is used for the older legacy addressable devices such as the M300 Series modules and
detectors
LiteSpeed (factory default setting) - used for the 350 Series or newer addressable devices for quicker response times. Note that the
legacy devices can operate only in CLIP mode while the newer devices are compatible with CLIP and LiteSpeed modes of operation
Pressing 2 while viewing the Loop Setup Screen will toggle between CLIP and LiteSpeed Protocols.

Device Addressing

It is important to note that the ES-200X addressable device capacity is 99 detectors and 99 control/monitor modules. Newer devices can be
set to addresses higher than 99 but these addresses will not function with the ES-200X.
Note that it is permissible to mix old and new devices on the same loop but the FACP must be set for CLIP mode when older devices are
installed.
ES-200X Series Manual — P/N LS10131-000FL-E:F 5/23/2022
Pressing 2 while viewing Zone Setup Screen #3 will display the following screen:
ZONES AVAILABLE
001 002 003 004 005
006 007 008 009 010
011 012 013 014 015
Pressing 3 while viewing Zone Setup Screen #3 will display the following screen:
1=Z000
2=Z001
3=Z002
Loop Setup allows the programmer to configure the SLC Loop for NFPA Class A or Class B wiring and to
select the loop protocol. Pressing 1 while viewing Programming Screen #2 will cause the following screen to
be displayed:
1=CLASS
2=PROTOCOL LITESPEED
ZONE MESSAGE
NO MESSAGE
MESSAGE 1
NO MESSAGE
LOOP SETUP
B
Loop Setup Screen
Programming
73

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fire-lite alarms es-200xcFire-lite alarms es-200x

Table of Contents