2=Zones; 3: Trouble Reminder - Honeywell Fire-Lite Alarms ES-200XI Manual

Addressable fire alarm control panel
Table of Contents

Advertisement

Operating Instructions
Entering the three digit detector address will cause the control panel to display the current status of the selected device. For example, if a
detector with address 001 on the SLC loop is entered, a display similar to the following will appear:
The information in the preceding display includes:
NORMAL - the present status (could also be ALARM, TROUBL, DISABL, etc.)
SMOKE (PHOTO) - the device type which is a photoelectric smoke detector (could also be ION for ionization smoke detector)
NORTH CLASSROOM - the Adjective/Noun label for this device
Z005 - the first of five possible assigned software zones
1D001 - 1 = SLC Loop, D = Detector, 001 = Address 001
V - Alarm Verification Enabled (V = Yes, * = No)
S - Silenceable for control modules (S = Yes, * = No)
W - Walktestable for control and monitor modules (W = Yes, * = No)
Pressing the down arrow key, while viewing the screen shown above, will allow the operator to view additional programming information
about the selected device, such as:
Enable/Disable Status
Device Type
Alarm Verification On/Off (for detectors)
Walktest Yes/No
PAS (Positive Alarm Sequence) Yes/No (for detectors only)
Pre-Signal Yes/No (for detectors and monitor modules)
Zone Assignments (five maximum)
Chamber Value
Adjective/Noun descriptor
Silenceable Yes/No (for control modules)
MNS Override Enabled/Disabled (for control modules)
Wireless Yes/No (for detectors only)
Sounder Base Yes/No (for detectors only)
Sounder Base Values and Zone Assignments (for detectors only)
4.24.2 Zones
READ STATUS
1=SYSTEM POINT

2=ZONES

Read Status Screen #1
From the preceding screens, the control panel operator can view:
Zones Installed - all software zones programmed into the system (99 maximum)
Zones Enabled - all software zones that are enabled
Zones Disabled - all software zones that have been disabled
Special Purpose - on or off programming for Special Purpose Zones 97 reserved for PAS, 98 reserved for Pre-signal, 99 reserved for Two
Stage, and 96 for Local Alarm
Zone Type - the Type assigned to each installed zone (default is Alarm)
Zone Message - the Message assigned to each installed zone
4.24.3 Trouble Reminder
READ STATUS
1=TROUBLE REMINDER
2=TIMERS
3=NAC
Read Status Screen #2
The screen indicates whether the Trouble Reminder feature is set to sound every 4 or 24 hours.
118
NORMAL SMOKE(PHOTO)
NORTH CLASSROOM
Pressing 2 while viewing Read Status Screen #1 will cause the following screens to be displayed:
ZONES
1=ZONES INSTALLED
2=ZONES ENABLED
3=ZONES DISABLED
Zones Screen #1
Pressing 1 while viewing Read Status Screen #2 will display the following screen:
TROUBLE REMINDER
TROUBLE REM
Z005
V
1D001
ZONES
1=SPECIAL PURPOSE
2=ZONE TYPE
3=ZONE MESSAGE
Zones Screen #2
24HR
ES-200X Series Manual — P/N LS10131-000FL-E:F 5/23/2022
Read Status