Page 1
– INSTALLATION & MAINTENANCE MANUAL – Advanced Color Wired Remote Controller Conference Room MODEL CIW02-H Temp Cool Fan Speed Louver Menu A10720990A...
Page 2
Important Notice • Johnson Controls-Hitachi Air Conditioning pursues a policy of continuing improvement in design and performance in its products. As such, Johnson Controls-Hitachi Air Conditioning reserves the right to make changes at any time without prior notice. • Johnson Controls-Hitachi Air Conditioning cannot anticipate every possible circumstance that might involve a potential hazard.
Use only Johnson Controls-Hitachi Air Conditioning recommended, provided as standardized, or replacement parts. • Johnson Controls-Hitachi Air Conditioning will not assume any liability for injuries or damage caused by not following steps outlined or described in this manual. Unauthorized modifications to Johnson Controls-Hitachi Air Conditioning products are prohibited as they…...
Page 5
1. Safety Summary Take the following precautions to reduce the risk of property damage. • Do not touch the main circuit board or electronic components in the controller or remote devices. Make sure that dust and/or steam does not accumulate on the circuit board. •...
Page 6
When shielded cabling is applied, proper bonding and termination of the cable shield is required as per Johnson Controls-Hitachi Air Conditioning guidelines. Plenum and riser ratings for communication cables must be considered per application and local code requirements.
2. Installation Work 2. Installation Work (1) This packing contains the following parts. Installation & Maintenance Name CIW02-H Operation Manual Screw Manual Appearance M4 × 16mm Qty. (2) When arranging the advanced color wired remote controller and other controllers vertically, place them at least 2 inches(50mm) apart. more than 2 inches(50mm) [Installation Instructions] (1) Insert the edge of the slotted screwdriver into the groove at the bottom of the holding bracket, push and turn...
Page 8
2. Installation Work (2) Attach the controller to the holding bracket and connect the cable as follows. 1. In Case of Exposing the Controller Cable Trace-out Hole Cable Attach the stopper (plastic band) Band Stopper to the cable at the inside of (Field-Supplied) the draw-out hole.
When shielded cabling is applied, proper bonding and termination of the cable shield is required as per Johnson Controls-Hitachi Air Conditioning guidelines. Plenum and riser ratings for communication cables must be considered per application and local code requirements.
4. Entering Service & Installation 4. Entering Service & Installation Step1. Power On 1. Turn ON the power supply for all the indoor units. 2. For models equipped with an auto-address function, wait approximately 3 minutes. This function is being automatically performed. (There is a built-in 5-minute requirement according to the setting condition.) Step2.
5. Test Run 5. Test Run Step1. Enter Installation Menu Service & Installation (Mon) 16:30 1. Select "Installation Menu" and OK". press " Service Menu Installation Menu Check Menu Enter Back Step2. Enter "Test Run" Mode Installation Menu (Mon) 16:30 Test Run 1.
6. Function Selection 6. Function Selection Function Selection is set from Installation Menu. Step1. Select "Installation Menu" and press "OK". Service & Installation (Mon) 16:30 Service Menu Installation Menu Check Menu Enter Back Step2. Select "Function Selection "and press "OK". Installation Menu (Mon) 16:30 Test Run...
Page 13
6. Function Selection Table A. Optional Setting Items for Function Selection Individual Setting Item Optional Function Contents Setting Setting Condition Standard setting (Setpoint + 4 F))(*1) Removal Heating temperature compensation ○ Tset+2 C (*2) due to uneven heat load Tset+3 Tset+1 Circulator Function during Heating Unavailable...
Page 14
6. Function Selection Individual Setting Item Optional Function Contents Setting Setting Condition Standard setting (7 steps) ○ Change of Louver Swing Angle Cold draft (5 steps) High ceilings (5 steps) Unavailable ○ Turn ON unit after power outage Available Not used Not Used(Use as 00 setting conditions) Restroe unit operation status(ON/OFF) Unavailable...
Page 15
6. Function Selection Individual Setting Item Optional Function Contents Setting Setting Condition No Function • • • • Automatic OFF Timer Setting × 30 min. 90 min. 40 min. 45 min. Do not set them when two wired controllers are used. 50 min.
Page 16
6. Function Selection Individual Setting Item Optional Function Contents Setting Setting Condition Standard (19 Lower limit for cooling temperature × setting (*8) Standard (30 Upper limit for heating temperature × setting (*9) Not used Not used Not used Indication Indication of Hot Start ×...
Page 18
6. Function Selection Individual Setting Item Optional Function Contents Setting Setting Condition Not used C steps Setting temperature × C steps Not used Inlet Air Thermistor Outlet Air Thermistor Thermistor Selection (*13) × Thermistor of Wired Controller Remote Sensor Unavailable Temperature sensor display(*14) ×...
Page 19
6. Function Selection Individual Setting Item Optional Function Contents Setting Setting Condition Not used Not used Unavailable COOL only Operation mode with Setback × HEAT only COOL HEAT 2.0°C(3°F) 3.0°C(5°F) Temp. differential for the Setback × 4.0°C(7°F) operation 5.0°C(9°F) 1.0°C(2°F) 10 min.
Page 20
6. Function Selection Individual Setting Item Optional Function Contents Setting Setting Condition 100h 200h 400h FrostWash interval settings × 100h 100h 100h 100h Unavailable 10 min. 20 min. 30 min. 40 min. 50 min. Minimum Cool/Heat Time for Auto × 60 min.
Page 23
6. Function Selection NOTES: 1. Power ON, wait 3 minutes and then change the optional setting. 2. When changing the "CF" setting (changing the louver swing angle), restore the power supply or allow the louver to make one complete swing fully in the auto-swing mode to apply the optional setting.
7. Input/Output Setting 7. Input/Output Setting Set Input/output from the Installation Menu. Set Input/Output Service & Installation (Mon) 16:30 Step1. Select "Installation Menu" on the Service & Installation Service Menu screen and press "OK". Installation Menu Check Menu Enter Back Step2.
8. Main Remote Setting Table B. Input and Output Number Display and Connectors Input Number Display Factory Setting Port Setting Input/Output Indication Setting Item Indication Input 1 CN3 1-2 Remote ON/OFF 1 (Level) Input 2 CN3 2-3 Prohibiting Remote Control after Manual Stoppage Output 1 CN7 1-2 Operation...
Page 26
8. Main Remote Setting • Concerning main and sub controllers, the range of settings may differ for the functions shown below. Table D. Relation between Main/Sub Controller and Setting Range Function Main ○ × Power Saving Details Setting ○ × Details Setting Outdoor Unit Capacity Control...
9. Priority Setting 9. Priority Setting You can only set the operation mode and unit temperature setpoint from one specific controller (the main controller) in the same refrigerant system without having to use the central controller. The operation of sub controller is decided by the priority setting and power saving details setting of the main controller.
10. FrostWash 10. FrostWash FrostWash is available when applicable outdoor units and indoor units are connected. To use this function in VRF system, outdoor unit function selection item "F1" need to be configured on outdoor units. Please refer to the dedicated Service Manual for the FrostWash function. Please configure function selection F1 on the outdoor units, and then set the wired remote controller.
11. Setback Trigger Unit FrostWash setting on outdoor unit To use this function in the VRF system, function selection F1 needs to be configured on the outdoor units. FrostWash setting is disabled on the factory default setting. Set Function Selection F1 according to the following table. Auto-FrostWash Manual FrostWash "F1"...
12. Operation Lock/Unlock Setting 12. Operation Lock/Unlock Setting • This function disables the setting mode of the remote controller. Mode • In the operation lock, when the lock icon " " lights up, the mode cannot be changed by pressing " " or " ". •...
13. Password Setting 13. Password Setting The initial user password can be changed. If you forget the changed user password, a supervisor password can be used to set the user password again. The supervisor password is "5567". The password input effective time can be set also. It is not necessary to enter the password for a certain period after setting the password input effective time.
14. Hotel Mode Setting 14. Hotel Mode Setting This setting enables or disables the hotel mode. Step1. Select "Service Menu" on the Service & Installation screen and press "OK". Step2. Select "Hotel Mode" and press "OK". Step3. Press " " or " " to select enabled setting. Step4.
15. Power Saving Details Setting 15. Power Saving Details Setting This function provides the details for setting the power savings function. For the "Mode", select one item from each of the following settings, (1) outdoor unit capacity control, (2) indoor unit rotation control, and (3) intermittent control.
Page 34
14. Hotel Mode Setting Step7. Change level Intermittent Control Press " " or " " to select the item to set and press "OK". HIGH It changes in the order of "LOW → MED → HIGH" ↔ "LOW LOW only only"...
Page 35
14. Hotel Mode Setting Step6. Change the Fan Mode Time Rotation Control Select "Fan Mode Time" and press "OK". 10 min Press " " or " " to set the fan mode time. Press "OK" to 5 min confirm the setting. 3 min It changes as follows: "10 min"...
16. Temperature Range Restriction 16. Temperature Range Restriction The temperature range can be set by operating the remote controller. Set Temperature Range Step1. Select "Service Menu" on the Service & Installation screen Lower Limit for Cooling Operation and press "OK". 66°F 77°F Step2.
19. Room Name Setting 19. Room Name Setting Register the installation location of the controller. Register Room Name Step1. Select "Service Menu" on the Service & Installation screen and press "OK". Step2. Select "Set Room Name" and press "OK". Step3. Press " " to move cursor to font type. Press " " or " " to Set Room Name select the font type.
21. Adjusting Date/Time 21. Adjusting Date/Time Set the date and time. The setting is recommended in that it will be used to check the alarm history and set the schedule. Adjusting Date/Time Step1. While the air conditioner is stopped, press " " to select "Menu" and press "OK". While the air conditioner is operating, press "...