Honeywell VFD Overview ‘Honeywell VFD’ is a general-purpose Drive solution and meet automation requirements in process and general application, where is needed to control motors (inductive, single phase and three phase), and to bring the better performance and effectively management the whole system.
As a supplement to the display, there are some indicator lamps for status of operation. Most of the Drive's parameter Setups can be changed immediately via the integral control panel. A Keyboard to be connected via a plug to the front of the Honeywell VFD is available as a module basically or optionally.
Page 3
Parameter Config and Copier-HAC It’s a tool for configuring/monitoring the parameters remotely, without any Keyboard. All series of Honeywell VFD has one or two comm port to interface with other external device, which are serial port and Ethernet port (installed optionally).
Specifications Honeywell VFD HAC10 The HAC10 is based on the market oriented for miniaturization, high reliability and cost-competitive with performance. Stable Vector control Starting torque of 150%/0.5Hz is produced and provides robust power in the low-speed region. The motor auto-tuning function is optimized to maximize motor performance.
Four modes: linear torque characteristic curve, self-set V/F curve, V/F curve torque reduction characteristic curve (1.1 to 2.0 power), square V/F curve Two ways: linear acceleration and deceleration, S curve acceleration and deceleration Acce. / Dece. curve Four sets of acceleration and deceleration time, the time unit is 0.01s, the longest is 650.00s Using the power supply voltage compensation function, the rated Rated output voltage...
Types and Characteristics of Control Modes The VFD can select AM-V/F control (initial setting) and AM-open loop vector control. Asynchronous motor V/F control • It means that when the frequency (F) is variable, the ratio of the control frequency to the voltage (V) remains constant. •...
Page 8
Wirings • Electronic thermal motor protection against overload. • The frequency converter is protected against short-circuits on motor terminals U, V, W. • Monitoring of the intermediate circuit voltage ensures that the frequency converter cuts out if the intermediate circuit voltage is too low or too high. •...
Page 9
As there are several pulse types in practice, please see the detailed description for the specific wiring. For 0.4kW to 5.5kW Honeywell VFDs, the COM and GND terminals are two-in-one function terminals and are combined externally as GND terminals; for 7.5kW to 22kW Honeywell VFDs, both COM and GND terminals are available.
Page 10
(3) Auxiliary Terminal Output Capability Terminal Function definition Max output 10V auxiliary power supply output, constitutes loop +10V 50mA with GND. Analog monitor output, constitutes loop with GND. As frequency, voltage signal, max output 2mA 24V auxiliary power supply output, constitutes loop +24V 100mA with COM.
More details: Connection diagram of jumper caps "+24V", "PLC", "COM (5) Main Circuit Wiring Main circuit terminal arrangement and definition Main Circuit Terminal Arrangement and Definition of HAC10 Series Honeywell VFDs Terminal Terminal name Terminal function definition DC power output, (-) for DC bus negative, (+) for DC bus DC power terminal positive, terminal block for 7.5kW-22kW models.
(7) Wiring of the main circuit of single-phase 220V class machine Table 3-5: Recommended single-phase 220V class machine main circuit wire diameter and fixed torque Recommended copper Main circuit terminal Recommended core cable specifications Model screw specifications fixed torque (N·m) (mm) mm2(AWG)...
Page 13
HAC10 series Honeywell VFD control circuit terminal arrangement and definition Terminal Items Terminal name Terminal function definition symbol Provide +10V power supply to the outside, the maximum External +10V output current: 50 mA is generally used as external +10V-GND power supply potentiometer working power supply, potentiometer resistance range: 1KΩ...
(11) Keypad function Built-in Built-in dual-line Symbol single-line Function keypad keypad Hz: Frequency A: Current V: Voltage A/V: Current or Unit indicator Voltage RPM: Revolutions Per Minute %: Percentage On: Forward running status Status indicator Blinking: Reverse running status Off: Stop status Menu button Press to enter the function menu interface in standby or Menu button...
Jog/Reverse Select the function of this button by parameter [F11.02]. LED Status Indicator In the following chart: represents light on, represents light off, represents flashing. Light off: stop status Lights on: running forward Running lights Blinking: Reverse running Light off: stop state Lights on: running forward Button Blinking: Reverse running...
Page 18
Honeywell VFD HAC310 ac300-t3-2r2g left HW.png HAC310 generates a more powerful performance through its superior V/F control, V/F PG, slip compensation, and sensor less vector control. The HAC310 focuses on a user-friendly interface and environment-friendly features including a 7-Seg LED keyboard and optionally graphic LCD Keyboard, electro-thermal functions for motor protection, and protection for input/output phase loss.
Frequency Digital setting: 0.01 Hz; Analog setting: maximum frequency × ±0.05%. resolution Automatic torque compensation: 0.0% to 100.0%. Torque compensation Manual torque compensation: 0.0% to 30.0%. Four modes: linear torque characteristic curve, self-setting V/F curve, reduced torque V/F curve characteristic curve (to the power of 1.1 to 2.0), and square V/F curve. Two modes: linear acceleration and deceleration, S-Curve acceleration and deceleration.
Page 20
Model Selection Guide Table II Table III Table I Key number Keypad E: Manual (English) Motor Rating(kW) HAC: Honeywell AC-Drive C: Manual (Chinese) 7-seg LED keypad 310: Product name 0: Future option LCD keypad Future Option Input Rating (Voltage) EMC Filter...
Page 21
Item Specification Power supply Supplied by the VFD - insulated power source from the VFD’s internal circuit Communication speed 1,200/2,400/9,600/19,200/38,400/57,600/115,200 bps Control procedure Asynchronous communications system Character system Modbus-RTU, Profibus-DP, CAN open Parity check None/Even/Odd (2) Ethernet Optionally, Ethernet communication is used for interface with clients. Item Specification Transmission Speed...
Page 22
(3-2) CANopen Items Description Network Topology Bus Topology Communication Baud Rate 20kbps, 50kbps, 125kbps, 250kbps, 500kbps, 1Mkbps Max. number of Node 64 nodes (Including Master) With 1 Master connected to network, the maximum number of VFD nodes is 63 (64-1). Device Type AC Drive Supported Communication Type...
Page 23
Items Description Communication protocol PROFInet IO CC-A Communication speed 100 Mbps (3-6) Option IO modules Image Items Description 5 V differential signal input, support HAC300-PG01 (5V) maximum frequency 500 kHz, with input Differential PG card signal disconnection detection function. 12 V differential or OC signal input, support HAC300-PG01 (12V) a maximum frequency of 500 kHz, with input Differential PG card...
Page 24
For HAC310, parts of the general VFD burn- HAC300-SL-A1.1 in program can be opened to the core agents Flash card (authorized by the regional director.) (3-7) Dual Ethernet Items Description Transmission Specifications Protocols Profibnet, ModbusTCP Transmission speed (Mbps) 10/100/1000 Transmission method Baseband Maximum distance between nodes 100m (Node-Switch) / 328 fts...
Page 25
18.5 —— —— —— —— —— —— —— —— —— —— —— —— 1200 —— 1340 —— 1500 —— 1620 —— 1000 1980 1080 (2) Default time data of Acceleration and Deceleration The default acceleration and deceleration of the VFD vary with the power level. See the table below for details. VFD power rating (kW) Default of acceleration and deceleration time (s) 6.00...
Page 26
75.0 24.00 90.0 30.00 110.0 36.00 160.0 48.00 185.0 54.00 200.0 60.00 220.0 and above 60.00 (3) Default Voltage Protection Point The default voltage value of the VFD includes voltage level, rated voltage, undervoltage suppression point, undervoltage point, overvoltage suppression point, overvoltage point and dynamic braking point, etc. See the table below for details.
Asynchronous motor closed-loop vector control • This control mode is used where high-precision speed control or torque control is required, and high-precision speed control is required even at zero speed. • An encoder must be installed at the motor end, and the VFD must be equipped with a PG card of the same type as the encoder.
Page 28
Table 3-1: Environmental conditions required for reliable operation of HAC310 series VFDs Environment Requirements Installation site Indoor installation, free of direct sunlight. Use temperature -10°C~+50°C Storage temperature -30°C~+60°C Ambient humidity No condensation below 95% RH. Please install the VFD in the following places: ●...
Wirings (1) Wirings Electronic thermal motor protection against overload. • The frequency converter is protected against short-circuits on motor terminals U, V, W. • Monitoring of the intermediate circuit voltage ensures that the frequency converter cuts out if the intermediate circuit voltage is too low or too high. •...
Page 30
Terminal Definition of Function Maximum Output and voltage type. 24 V auxiliary power output, forming a +24V 100mA loop with COM. Open collector output: the action object DC24V/50mA can be set by program. Illustration and description of PID switch function Position Position Function Description...
(b)Wiring method of NPN characteristic transistor: Enabled inner 24V power supply Enabled external 24V power supply +24V External 24V power supply +24V +24V +24V (Default short connected ) Shield Cable Shield Cable Note: Jumper between"+24V"and"PLC" need be removed when external 24V power supply was chosen. Wirings for Main Circuit (1) Terminal Arrangements Table 3-2: Arrangement and Definition of Terminals of HAC310 Series VFD Main Circuit...
Page 32
Grounding terminal, with the grounding resistance < 10 Ω. Grounding (2) Cable Recommendations for Single/Three-phase 220Vac Specifications of Specifications of Screws for Main Recommended Model Recommended Copper Circuit Terminal Fixed Torque (N·m) Core Cable (mm2) (AWG) (mm) HAC310T/S2-R40G 0.8~1.0 1.5mm (14) HAC310T/S2-R75G 0.8~1.0...
Page 36
710 kW 0.8Ω 70.0kW 100% Table 3-8: Recommended specifications of brake resistors for HAC310 series VFDs Single/Three-Phase 220 V Resistance Power Motor Power (kW) Resistance Value Braking Torque (%) (W or kW) 400Ω 0.4 kW 100W 100% 200Ω 0.75 kW 120W 100% 100Ω...
Page 37
Keypad function Built-in Built-in dual- Symbol single-line Function line keypad keypad Hz: Frequency A: Current V: Voltage A/V: Current or Voltage Unit indicator RPM: Revolutions Per Minute %: Percentage On: Forward running status Status indicator Blinking: Reverse running status Off: Stop status Menu button Menu button Press to enter the function menu interface in standby or...
Page 38
LED Status Indicator In the following chart: represents light on, represents light off, represents flashing. Light off: stop status Lights on: running forward Running lights Blinking: Reverse running Light off: stop state Lights on: running forward Button Blinking: Reverse running Light on: Monitor this value Unit indicator Hz、A、V、RPM、%...
Page 39
(1) RING topology with DLR (2) STAR Topology (3) Profibus-DP (with PROFINET) MasterVert Specifications, HAC_V00...
HAC Builder System Requirement Category Requirement Windows Windows 7/8/10 Processor 1 GHz or higher 1 GB (32-bit) or 2 GB (64-bit) 16 GB (32-bit) or 20 GB (64-bit) Interface CANopen, RS485, Baud rate=1200 to 57600bps Others .NET3.5 framework HAC Builder is a configuration tool to configure parameters and monitoring the operating conditions on- real time, uploading the parameters from drives.
Page 41
(2) Parameter Reading and Writing (3) Trend (3) Real Time Monitoring (3) Function Code Comparison MasterVert Specifications, HAC_V00...
More information is available at the ODVA website, WWW.ODVA.org PROFINET and PROFIBUS-DP A Siemens Scalance switch coupled with a Rockwell ETAP allow the Honeywell VFD to connect to a PROFINET MRP network. Standards and Approvals Item...
Page 43
Item Specification Title Number Issue date Safety requirements for electrical equipment for measurement, control, and laboratory use –Part EN 61010-1 2010 1: General requirements EMC directive: Title Number Issue date Programmable controllers- Part 2: Equipment IEC 61131-2 2007 requirements and Tests Electrical equipment for measurement, control, and laboratory use –...
Page 44
Model Selection Guide and Accessories HAC10 Key numbers Availability Description Selection VFD and Voltage Honeywell VFD HAC10, 3-phase 200 ~ 240VAC (Note 1) HAC10T2- Type Honeywell VFD HAC10, 3-phase 380 ~ 480VAC (Note 1) HAC10T3- TABLE I Motor Rating •...
Page 45
HAC10 Accessories and Spare parts Category Description Part Number Keypad Single line LED keypad 50188977-001 AC10 VFD buckle 50188977-002 Dual line LED keypad 50188977-003 LCD keypad 50188977-004 PG card Differential PG card 50188977-005 Resolver PG card 50188977-006 Interface Options CANopen Communication card 50188977-007 Profibus Communication card 50188977-008...
Page 47
TABLE II a. Keypad • • • LED Keypad (Note 2) E _ _ _ _ LCD Keypad (Note 3) C _ _ _ _ b. EMC Filter Non-EMC _ N _ _ _ C2, Built-in EMC _ X _ _ _ •...
Page 48
Input Rating 3-phase 380~440V (-15%~+10%) , None of Brake, with Reactor HAC3103- 055G 75HP 55.0kW E None DC Reactor S LED Keypad Standard IO HAC3103- 075G 100HP 75.0kW E DC Reactor S LED Keypad None Standard IO HAC3103- 090G 125HP 90.0kW E None DC Reactor S...
Page 49
HAC310 Accessories and Spare parts Category Description Part Number Keypad Single line LED keypad 50188977-001 AC10 VFD buckle 50188977-002 Dual line LED keypad 50188977-003 LCD keypad 50188977-004 PG card Differential PG card 50188977-005 Resolver PG card 50188977-006 Interface Options CANopen Communication card 50188977-007 Profibus Communication card 50188977-008...
Page 50
For more information To learn more about Honeywell’s products, visit https://process.honeywell.com or contact your Honeywell account manager. Honeywell Process Solutions 2101 CityWest Boulevard Houston, TX 77042 Honeywell House, Arlington Business Park Bracknell, Berkshire, England RG12 1EB UK Shanghai City Centre, 100 Zunyi Road Shanghai, China 200051 34-VT-03-02 | Rev 1.0.0 | March 2023...